AI helper
Describe the task — I'll match 3 WIKA models in 30 seconds
TC10-0 1
TC10-0
On order
WIKA · Temperature measurement · Family TC10

Thermocouple

Thermocouple industrial assembly with spring-loaded measuring insert, suitable for use in standard thermowells or with fixed fitting.
Range
-40…1260 °C
Output
HART · 4-20 mA
Protection
IP65
CERoHSEACINMETROCCCGOSTKazInMetrMTSCHSBelGIMUkrSEPROUzstandardATEXIECExFMCSAEx UkraineEMCEx i (gas) Zone 0, 1, 2Ex i (dust) Zone 20, 21, 22Ex d (gas) Zone 1, 2Ex d (dust) Zone 21Ex e (gas) Zone 1, 2Ex n (gas) Zone 2Ex t (dust) Zone 21, 22Ex d IIC Gb T6/T5/T4Ex d IIB + H2 Gb T6/T5/T4Ex nA (gas) Zone 2
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

Thermocouples in this series can be combined with a large number of thermowell designs. Use without a thermowell is permitted when using a fixed (welded) fitting.

A wide variety of possible combinations of sensor, connection head, insertion length, neck length, connection to thermowell etc. are available for the thermometers; suitable for almost any thermowell dimension.

for further approvals see page 2

Thermocouple, model TC10-0, industrial assembly

Special features

  • Sensor ranges from -40 ... +1,260 °C [-40 ... +2,300 °F]
  • For mounting in all standard thermowell designs
  • Spring-loaded measuring insert (replaceable)
  • Explosion-protected versions
  • Fixed fitting (welded) measuring insert
Identification
ModelTC10-0
Product familyTC10
SubcategoryThermocouple
Measuring range
Temperature ranges−40…+1260 °C · −40…+1200 °C · −40…+1000 °C · −40…+900 °C · −40…+800 °C · −40…+750 °C · −40…+350 °C · +0…+1260 °C · +0…+870 °C · +0…+760 °C · +0…+370 °C
Accuracy
Safety integrity level (SIL)SIL 2 (IEC 61508 / IEC 61511)
Process conditions
Process connection
½ NPT¾ NPTG ½ BG ¾ BM14 x 1.5M18 x 1.5M20 x 1.5M24 x 1.5Tapered threadsParallel threadsNipple-union-nipple neck tubeNon-divisible neck tubeDouble threaded hex bushing
Process temperature−40…+1260 °C
Electrical characteristics
Output signalHART · 4-20 mA
Electrical connectionConnection head (BS, BSZ-H, KN4-A, KN4-P, 1/4000, 7/8000)
Materials
Probe materialSheathed cable (mineral-insulated cable, MI cable), Sheathed cable (mineral-insulated cable)
Operating environment
Ambient temperature−40…+80 °C
IP ratingIP65
Certifications and approvals
Certifications
CERoHSEACINMETROCCCGOSTKazInMetrMTSCHSBelGIMUkrSEPROUzstandardATEXIECExFMCSAEx UkraineEMC
Explosion protection
Ex i (gas) Zone 0, 1, 2Ex i (dust) Zone 20, 21, 22Ex d (gas) Zone 1, 2Ex d (dust) Zone 21Ex e (gas) Zone 1, 2Ex n (gas) Zone 2Ex t (dust) Zone 21, 22Class I, division 1, group B, C, D, T6 type 4/4XClass II or III, division 1, group E, F, G type 4/4XEx d IIC Gb T6/T5/T4Ex d IIB + H2 Gb T6/T5/T4Ex nA (gas) Zone 2ATEX: II 1G Ex ia IIC T1...T6 Ga, II 2G Ex db IIB+H2 T6...T4 Gb, II 2G Ex eb IIC T1...T6 GbIECEx: Ex ia IIC T1...T6 Ga, Ex db IIB+H2 T6...T4 GbFM: Class I, Div 1, Groups B, C, D, T6; Class II/III, Div 1, Groups E, F, GCSA: Class I, Div 1, Groups B, C, D, T6; Class II/III, Div 1, Groups E, F, GEAC: 0Ex ia IIC T6...T1 Ga, 1Ex d IIC T6...T4 GbEx Ukraine: II 1G Ex ia IIC T1...T6 Ga, II 2G Ex db IIC T6...T4 GbINMETRO: II 1G Ex ia IIC T1...T6 GaCCC: Ex ia IIC T1~T6 Ga, Ex d IIC T4~T6 Gb
Additional details
Sensor typeType K/J/E/N/T
Sensor classClass 1, Class 2, Standard, Special
Probe diameter3 mm
ThermowellYes
Datasheet languagesEN, DE
Tables from datasheet
ApprovalExplosion protection
Ex i (gas) Zone 0, 1, 2Ex i (dust) Zone 20, 21, 22Ex d (gas) Zone 1, 2Ex d (dust) Zone 21Ex e (gas) Zone 1, 2Ex n (gas) Zone 2
ATEXxxxxxx
IECExxxxxxx
FM--xx--
CSA--xx--
EACxxxx-x
Ex Ukrainexxxx--
INMETROxx----
CCCxxxxxx
Measuring element
Type of sensorThermocouple per IEC 60584-1 or ASTM E230 Types K, J, E, N,T
Hot junction■ Ungrounded (standard) ■ Grounded (welded to the sheath)
Marking of the polarityThe colour coding at the positive poles of the instrument decides the correlation of polarity and terminal
Single thermocouple
Dual thermocouple
Validity limits of the class accuracy per EN 60584-1
Type KClass 2 Class 1-40 ... +1,200 °C [-40 ... +2,192 °F] -40 ... +1,000 °C [-40 ... +1,832 °F]
Type JClass 2 Class 1-40 ...+750 °C [-40 ... +1,382 °F] -40 ...+750 °C [-40 ... +1,382 °F]
Type EClass 2 Class 1-40 ...+900 °C [-40 ... +1,652 °F] -40 ...+800 °C [-40 ... +1,472 °F]
Type NClass 2 Class 1-40 ... +1,200 °C [-40 ... +2,192 °F] -40 ... +1,000 °C [-40 ... +1,832 °F]
TypeTClass 2 Class 1-40 ...+350 °C [-40 ...+662 °F] -40 ...+350 °C [-40 ...+662 °F]
Validity limits of the class accuracy in accordance with ASTM-E230
Type KStandard Special0 ... 1,260 °C [32 ... 2,300 °F] 0 ... 1,260 °C [32 ... 2,300 °F]
Type JStandard Special0 ... 760 °C [32 ... 1,400 °F] 0 ... 760 °C [32 ... 1,400 °F]
Type EStandard Special0 ... 870 °C [32 ... 1,598 °F] 0 ... 870 °C [32 ... 1,598 °F]
Type NStandard Special0 ... 1,260 °C [32 ... 2,300 °F] 0 ... 1,260 °C [32 ... 2,300 °F]
TypeTStandard Special0 ... 370 °C [32 ... 698 °F] 0 ... 370 °C [32 ... 698 °F]
ModelMaterialCable entry thread sizeIngress protection (max.) 1) IEC/EN 60529CapSurfaceConnection to neck tube
BSAluminium■ M20 x 1.5 ■ ½NPTIP65 2)Flat cover with 2 screwsBlue, painted (RAL 5022)■ M24 x 1.5 ■ ½NPT
BSBSZ, BSZ-K BSZ-HBSZ-H, AluminiumBSS ■ M20 x 1.5 ■ ½NPTBSS-H IP65 2)BVS BVS Raised hinged cover with cylinder head screw(NuG) Blue, painted (RAL 5022)1/4000 ■ M24 x 1.5 ■ ½NPT
ModelExplosion protection
WithoutEx i (gas) Zone 0, 1, 2Ex i (dust) Zone 20, 21, 22Ex e (gas) Zone 1, 2Ex t (dust) Zone 21, 22
BSxx---
BSZ-Hxxxx 3)x 3)
View all (20)
ModelMaterialCable entry thread sizeIngress protection (max.) 1) IEC/EN 60529CapSurfaceConnection to neck tube
KN4-AAluminium■ ½NPT ■ M20 x 1.5IP65 2)Screw-on lidBlue, painted (RAL 5022)■ M24 x 1.5 ■ ½NPT
KN4-P 4)Polypropylene½NPTIP65 2)Screw-on lidWhite½NPT
BVC 1/4000 FAluminium■ ½NPT ■ ¾NPT ■ M20 x 1.5IP66 2)Screw-on lidBlue, painted (RAL 5022)½NPT
5/6000 1/4000 S7/8000 Stainless steel7/8000 DIH50 ■ ½NPT ■ ¾NPT ■ M20 x 1.5KN4-P andere Anschlussgehäuse IP66 2)BVC Screw-on lidNatural finish½NPT
7/8000WAluminium■ ½NPT ■ ¾NPT ■ M20 x 1.5IP66 2)Screw-on lidBlue, painted (RAL 5022)½NPT
7/8000 DIH50 7/8000 Sandere Anschlussgehäuse Stainless steelKN4-P ■ ½NPT ■ ¾NPT ■ M20 x 1.5BVC IP66 2)Screw-on lidNatural finish½NPT
ModelExplosion protection
WithoutEx i (gas) Zone 0, 1, 2Ex i (dust) Zone 20, 21, 22Ex t (dust) Zone 21, 22Ex nA (gas) Zone 2
KN4-Axx---
KN4-P 4)x----
1/4000 Fxx---
1/4000 Sxx---
7/8000Wxx---
7/8000 Sxx---
Measuring insert
VersionsVibration-resistant, sheathed cable (mineral-insulated cable, MI cable)
Optimal heat transferRequirement■ Correct measuring insert length ■ Correct measuring insert diameter
Bore diameter of the thermowellMax. 1 mm[0.04 in] larger than measuring insert diameter
Gap widthFor joint width > 0.5 mm[> 0.02 in] between thermowell and measuring insert: →Negative impact on heat transfer →Unfavourable response behaviour of the thermometer
Measuring insert diameter Ø d■ 3.0mm ■ 6.0mm ■ 8.0mm ■ 1/8 in or 0.125 in [3.17 mm] ■ 3/16 in or 0.188 in [4.75 mm] ■ 1/4 in or 0.250 in [6.35 mm]
Other measuring insert diameters on request
Insertion lengthWhen fitting the measuring insert into a thermowell, it is very important to determine the correct insertion length (= thermowell length for bottom thicknesses of ≤ 5.5 mm[≤ 0.22 in]). In order to ensure that the measuring insert is firmly pressed down onto the bottom of the thermowell, the insert must be spring-loaded (spring travel: 0 ... 10 mm[0 ... 0.39 in]).
Spring travelMax. 10 mm[0.39 in]
Transmitter modelsModel T16Model T32
Transmitter data sheetTE 16.01TE 32.04
Figure
Output
4 ...20mAxx
HART ® protocol-x
Input■ Type K ■ Type J ■ Type E ■ Type N ■ TypeT■ Type K ■ Type J ■ Type E ■ Type N ■ TypeT
Explosion protectionOptionOption
Possible mounting positions for transmittersModel T16Model T32
BS○-
BSZ-H●●
KN4-A○○
KN4-P○○
1/4000○○
7/8000○○
Operating conditions
Ambient and storage temperature-40 ...+80 °C [-40 ...+176 °F]
Vibration resistanceThe information on vibration resistance refers to the tip of the measuring insert. →For detailed specifications on the vibration resistance of Pt100 sensors, see Technical information IN 00.17 at www.wika.de.
Standard6 g peak-to-peak, wire-wound measuring resistor or thin film
Option■ Vibration-resistant probe tip, max. 20 g peak-to-peak, thin-film measuring resistor ■ Highly vibration-resistant probe tip, max. 50 g peak-to-peak, thin-film measuring resistor
First index numberDegree of protection / Short descriptionTest parameters
Degrees of protection against solid foreign bodies (defined by the 1st index number)
5Dust-protectedPer IEC/EN 60529
6Dust-tightPer IEC/EN 60529
Degrees of protection against water (defined by the 2nd index number)
4Protected against splash waterPer IEC/EN 60529
5Protected against water jetsPer IEC/EN 60529
6Protected against strong water jetsPer IEC/EN 60529
7 1)Protected against the effects of temporary immersion in waterPer IEC/EN 60529
8 1)Protected against the effects of permanent immersion in waterAs agreed upon
Thermowell selection
ModelData sheetIllustration
TW10TW95.10
TW15TW95.15
TW20TW95.20
TW25TW95.25
TW30TW95.30
TW31TW95.31
TW50TW95.50
TW55TW95.55
LogoDescriptionCountry
EU declaration of conformityEuropean Union
LogoDescriptionCountry
EU declaration of conformity ATEX directive Hazardous areas - Ex i Zone 0 gas Zone 1 mounting to zone 0 gas Zone 1 gas Zone 20 dust Zone 21 mounting to zone 20 dust Zone 21 dust - Ex d Zone 1 gas Zone 1 gas Zone 21 dust - Ex e Zone 1 gas Zone 2 gas Zone 21 dust Zone 22 dustII 1G Ex ia IIC T1 ...T6 Ga II 1/2G Ex ia IIC T1 ...T6 Ga/Gb II 2G Ex ia IIC T1 ...T6 Gb II 1D Ex ia IIIC T125 ...T65 °C Da II 1/2D Ex ia IIIC T125 ...T65 °C Da/Db II 2D Ex ia IIIC T125 ...T65 °C Db II 2G Ex db IIB + H2T6 ...T4 Gb II 2G Ex db IIC T6 ...T4 Gb II 2D Ex tb IIIC T85 °C Db IP66 II 2G Ex eb IIC T1 ...T6 Gb 3) II 3G Ex ec IIC T1 ...T6 Gc X II 2D Ex tb IIICTX °C Db 3) II 3D Ex tc IIICTX °C Dc X II 3G Ex nA IIC T1 ...T6 Gc X II 3D Ex tc IIICTX °C Dc XEuropean Union
- Ex n Zone 2 gas Zone 22 dust IECEx - in combination with ATEX Hazardous areas - Ex i Zone 0 gas Zone 1 mounting to zone 0 gas Zone 1 gas Zone 20 dust Zone 21 mounting to zone 20 dust Zone 21 dust - Ex d Zone 1 gas Zone 1 gas Zone 21 dust - Ex e 2) Zone 1 gas Zone 2 gas Zone 21 dust Zone 22 dust - Ex n 2) Zone 2 gasEx ia IIC T1 ...T6 Ga Ex ia IIC T1 ...T6 Ga/Gb Ex ia IIC T1 ...T6 Gb Ex ia IIIC T125 ...T65 °C Da Ex ia IIIC T125 ...T65 °C Da/Db Ex ia IIIC T125 ...T65 °C Db Ex db IIB + H2T6 ...T4 Gb Ex db IIC T6 ...T4 Gb Ex tb IIIC T85 °C Db IP66 Ex eb IIC T1 ...T6 Gb 3) Ex ec IIC T1 ...T6 Gc X Ex tb IIICTX °C Db 3) Ex tc IIICTX °C Dc X Ex nA IIC T1 ...T6 Gc X Ex tc IIICTX °C Dc XInternational
Zone 22 dust FM Hazardous areas - Ex d (XP) Division 1 gas DivisionClass I, division 1, group B, C, D, T6 type 4/4XUSA and Canada
1 dust CSA Safety (e.g. electr. safety, overpressure, ...) Hazardous areas - Ex d (XP) Division 1 gasClass II or III, division 1, group E, F, Gtype 4/4X Class I, division 1, groups B, C, D, T6 type 4/4XUSA and Canada
LogoDescriptionCountry
EAC (option) Hazardous areasEurasian Economic Community
- Ex n Zone 2 gas 2Ex nA IIC T6 ...T1 Gc X Ex Ukraine Hazardous areas - Ex i Zone 0 gas II 1G Ex ia IIC T1 ...T6 Ga Zone 1 mounting to zone 0 gas II 1/2G Ex ia IIC T1 ...T6 Ga/GbUkraine
Zone 1 mounting to zone 0 gas II 1/2G Ex db IIC T6 ...T4 Ga/Gb Zone 21 dust II 2D Ex tb IIIC T85 °C Db INMETRO Hazardous areas - Ex i Zone 0 gas II 1G Ex ia IIC T1 ...T6 Ga Zone 1 mounting to zone 0 gas II 1/2G Ex ia IIC T1 ...T6 Ga/Gb Zone 20 dust Ex ia IIIC T125 ...T65 °C Da Zone 21 mounting to zone 20 dust Ex ia IIIC T125 ...T65 °C Da/Db 3)Brazil
CCC Hazardous areas - Ex i Zone 0 gas Ex ia IIC T1 ~ T6 Ga Zone 1 gas Ex ia IIC T1 ~ T6 Gb Zone 1 mounting to zone 0 gas Ex ia IIC T1 ~ T6 Ga/Gb Zone 2 gas Ex ic IIC T1 ~ T6 Gc Zone 21 dust Ex iaD 21 T65/T95/T125°C - Ex d Zone 1 gas Ex d IIB+H2 T4~T6 Gb Zone 1 gas Ex d IIC T4~T6 Gb Zone 21 dust Ex tD A21 IP66 T85°CChina
GOST Metrology, measurement technologyRussia
KazInMetrKazakhstan
-Metrology, measurement technology MTSCHS Permission for commissioningKazakhstan
BelGIM Metrology, measurement technologyBelarus
-UkrSEPRO Metrology, measurement technologyUkraine
Uzstandard
Metrology, measurement technologyUzbekistan
Certification typeMeasurement accuracyMaterial certificate
2.2 test reportxx
3.1 inspection certificatexx
DAkkS calibration certificatex-
Overview of versions
ModelDescription D
PIH-LConnection head with flat screw-on lid
PIH-HConnection head with high screw-on lid
PIH-WConnection head with high screw-on lid and window
PIR-LConnection head with flat screw-on lid, pipe or wall mounting
PIR-HConnection head with high screw-on lid, pipe or wall mounting
PIR-WConnection head with high screw-on lid and window, pipe or wall mounting E
Basic information
Materials
Lower part of the case PIX-X Explosion CONNECTION HEADAluminium die-casting EN AC-43500 AlSi10MnMg / AA 365.0; copper content ≤ 0,05% (low copper) drawing number 14654707.01
Screw-on lid scale 1:1Aluminium die-casting EN AC-43500 AlSi10MnMg / AA 365.0; copper content ≤ 0,05% (low copper) F reference DR 08 sheets 1 / 1
Window Check indicator sizeGlass ALEXANDER WIEGAND SE & Co. KG comments
Sealing language■ EPDM -60 ...+90 °C [-76 ... 194 °F] ■ MVQ-60 ...+110°C [-76 ... 230 °F], on request ■ FKM -20 ...+110°C [-4 ... 230 °F], on request www.wika.com D-63911 Klingenberg DEKLI1_EN_A4M_T00 26.04.2023 [inch]
Case surface
ColourLower bodyWIKA product grey RAL 7035
Screw-on lidWIKA product blue RAL 5022
Coating■ PE/PU (polyester/polyurethane) powder coating ■ 90 ±40 µm thickness ■ Electrically conductive per IEC 60243-1:2013 ■ The painted test objects / surfaces were subjected to a salt mist and condensation test per C5-M, per ISO 12944-6.The evaluation per ISO 4624, ISO 4628-2/-3/- 4/-5/-6, as well as the scored areas per ISO 12994 A.2 showed no significant abnormalities. ■ Cross-cut:GT 0 (...1) per ISO 2409:2013 - 1c or 2a
Basic information
Features■ Impact resistance of the window per IEC 60079-0:2017 point 26.4.2 ■ Pressure containment of case per IEC 60079-1:2014 point 15.2.3.2 ■ UV resistance per ISO 4892-3:2016 procedure A, cycle 3
Weight
Case with flat screw-on lid≤ 0.85 kg [≤ 1,9 lbs]
Case with high screw-on lid≤ 1.0 kg [≤ 2,2 lbs]
Case head with high screw-on lid and window≤ 1.1 kg [≤ 2,4 lbs]
Overview of connection threads
Head version for direct mounting on an electrical thermometerLeft Input ARight Input BBottom, to neck tube Input C
PIH-L, PIH-H, PIH-WM20 x 1.5ClosedM20 x 1.5, 1/2 NPT, 3/4 NPT
M20 x 1.5M20 x 1.5M20 x 1.5, 1/2 NPT, 3/4 NPT
1/2 NPTClosedM20 x 1.5, 1/2 NPT, 3/4 NPT
1/2 NPT1/2 NPTM20 x 1.5, 1/2 NPT, 3/4 NPT
3/4 NPTClosed1/2 NPT, 3/4 NPT