Fault codes in this document

Master Motherboard

Code / displayMeaningCauseActionPage
RUI CLASS A TROUBLE (LED1)Master motherboard LED indicating an RUI Class A trouble.27
RUI PRIMARY SHORT TROUBLE (LED2)Master motherboard LED indicating an RUI primary short trouble.27
RUI SECONDARY SHORT TROUBLE (LED3)Master motherboard LED indicating an RUI secondary short trouble.27
Negative Ground FaultNegative ground fault occurring on the RUI.Some devices that connect to RUI have inherently grounded shield terminals, in which case 24 C cannot be used. If 24 C is used (RUI SHIELD jumper P9 position 1–2), a Negative Ground Fault will occur.35

CPU Card LEDs

Code / displayMeaningCauseActionPage
Bad Master CRC or No Master PresentBootloader status indicated during system start up. LED4 On, LED3 Off, LED2 Off, LED1 Off.29
Diagnostic Fail – RAMBootloader status indicated during system start up. LED4 On, LED3 Off, LED2 Off, LED1 On.29
Diagnostic Fail – Bootloader CRCBootloader status indicated during system start up. LED4 On, LED3 Off, LED2 On, LED1 Off.29

LED/Switch Controller Card

Code / displayMeaningCauseActionPage
LED 1 (COMM LOSS LED)Illuminates if communication loss between the controller and the CPU occurs. It is independent of jumper P1. If the LED/switch controller is used in a remote annunciator with the communication loss feature activated (jumper P1 position 2–3), LED 1 of the first connected display card illuminates and the piezo on the LED/switch controller sounds.Communication loss between the controller and the CPU.The indication is silenced via the corresponding switch (switch 1 on the first display card).46

Basic TIC LED Indicators

Code / displayMeaningCauseActionPage
LED1Indicates communication loss with the CPU.53
LED2Indicates when an RUI ground fault search is active.53
LED4Indicates an RUI Style 7 primary trouble.53
LED5Indicates an RUI Style 7 secondary trouble.53

NIC Card LED Indications

Code / displayMeaningCauseActionPage
LED1 (yellow)Illuminates when: the host 4100 requests it to illuminate; a transmission fails; the NIC is off-line with the 4100 host; the NIC needs to be configured.A transmission fails; the NIC is off-line with the 4100 host; the NIC needs to be configured.61

SPS LED Indications

Code / displayMeaningCauseActionPage
LED1 (yellow)Illuminates when NAC 1 is ON or in Fault.79
LED2 (yellow)Illuminates when NAC 2 is ON or in Fault.79
LED3 (yellow)Illuminates when NAC 3 is ON or in Fault.79
LED4 (yellow)Illuminates to indicate a communications loss with the system CPU; normally off.If this LED is blinking, try re-loading the slave exec from the master.79
LED5 (yellow)
Slow blink
Class A open circuit Fault.79
LED5 (yellow)
Fast blink
Short circuit Fault.79
LED5 (yellow)
On steady
No devices detected/ channel failure.79
LED6 (yellow)
Single blink
Positive earth fault.79
LED6 (yellow)
Double blink
Negative earth fault.79
LED6 (yellow)
Triple blink
Battery Fault.79
LED6 (yellow)
Quadruple blink
Charger Fault.79
LED6 (yellow)
On steady
Overcurrent fault.79

Troubleshooting an SPS

Code / displayMeaningCauseActionPage
IDNet Power Monitor TroubleThere is no output voltage from the power supply.80
Extra DeviceOne or more extra devices are present on the loop, i.e. devices that have not been configured for the IDNet channel. Only one message appears, regardless of the number of extra devices found.Extra devices present on the loop that have not been configured for the IDNet channel.80
Class A TroubleThere is an open circuit fault detected on the IDNet channel.A hardware reset is required to reset the fault indication.80
Earth Fault SearchDisplayed during the Earth Fault Search diagnostic function. The front panel display indicates how far along the search process has progressed (10%, 25%… 75%), and then shows the results of the search. The result either identifies the offending circuit or indicates that the earth fault could not be found. SPS circuits (IDNet, NAC, and aux power) are searched.Earth Fault Search diagnostic function initiated.System alarm and fault processing is suspended during the search.80
Short CircuitA short circuit fault is detected on the IDNet channel.Short circuit on the IDNet channel.This status clears automatically when the short circuit is removed.80
Channel FailEach device on the IDNet channel has been configured, but none of the configured devices are communicating on the channel. This message does not appear if there are no configured devices on the IDNet channel.None of the configured devices are communicating on the channel.80
No Answer/Bad AnswerThe 4100ES is put into a diagnostic mode and finds a device not responding, or responding unreliably.Device not responding, or responding unreliably.Refer to the 4100 Fault Finding Guide (LT0565) for information on how to perform this diagnostic.80
Output AbnormalAbnormal output condition at field devices.24 V is not present on TrueAlarm devices; TrueAlarm sensor bases with relay driver outputs are not properly supervised; isolator devices are in isolation mode.80
Mains fail faultAC mains supply failure.Generated when the DC voltage drops below 20.3 V (nominally 204 Vac). The AC input is supervised.76
SPS Over CurrentSPS over current fault in the system.T-GEN 50 draws a large in-rush current when it is first turned on (e.g. when powered from a NAC output).Can only be cleared by pressing the 4100ES System Reset button. The T-GEN 50 should not be powered from a NAC output.91

Troubleshooting IDNet Faults

Code / displayMeaningCauseActionPage
IDNet Power Monitor TroubleThere is no output voltage from the IDNet power supply.Replace the IDNet card.107
Extra DeviceOne or more extra devices (i.e. devices that have not been configured for the IDNet channel) are found on the ID-Net loops, or a device is at an incorrect address. Only one message appears, regardless of the number of extra devices found.Extra devices on the IDNet loops, or a device at an incorrect address.Viewing the fault log will reveal the extra device address.107
Class A TroubleThere is an open circuit on the IDNet channel.After fixing the wiring fault, a hardware reset is required to reset the trouble.107
Earth Fault SearchThe IDNet card is searching for earth faults on the IDNet line.Earth fault search active on the IDNet line.When this message is displayed, the IDNet card cannot show any alarms or other statuses.107
Short CircuitA short circuit is detected on the IDNet channel.This status clears automatically when the short circuit is removed.107
Channel FailDevices have been configured, but none of the devices are communicating on the channel. This message does not appear if there are no configured devices on the IDNet channel.None of the configured devices are communicating on the channel.107
No AnswerA device is missing.Device missing.107
Bad AnswerA faulty device or a noisy communications channel.Faulty device or noisy communications channel.107
Output AbnormalAbnormal output condition.24 V is not present on TrueAlarm devices; TrueAlarm sensor bases with relay driver outputs are not properly supervised; isolator devices are in isolation mode.107

Using Install Mode

Code / displayMeaningCauseActionPage
Install Mode ActiveSingle fault indication shown while any device is in the Install Mode list. Devices in the Install Mode list will not produce fault indications, even if they are missing or faulty — all the individual device faults are hidden behind a single Install Mode Active fault.One or more internal modules or external devices have been added to the Install Mode list.When the system is fully commissioned, the Install Mode list should be empty.109

Brigade Interfaces

Code / displayMeaningCauseActionPage
SPS CPU FaultHardware fault signal; the Fault (Trouble) relay on the Alarm Relay Card is link connected to this signal.122

Search Results

Code / displayMeaningCauseActionPage
Non-point faultA ground that cannot be traced to an addressable point (for example, a shield). Non-point faults can be displayed for each of the following items: Channel Output (IDNet Card; MAPNET Interface Card); RUI Channel (Master Controller Card).Once you have been directed to an earth ground fault and corrected it, it is recommended that you restart the system (warm- or cold-start).139
Point faultA ground at a specific addressable point. Point faults can be found at any point in the system that connects to field wiring.Once you have been directed to an earth ground fault and corrected it, it is recommended that you restart the system (warm- or cold-start).139
CARD 2, IDNET CARD (250 POINTS)
M1, CHANNEL OUTPUT EARTH FAULT
Earth fault between the IDNet channel output and the first isolator on the line.139
CARD 2, IDNET CARD (250 POINTS)
M1-18, 4009A NAC EARTH FAULT
Earth fault detected on the 4009 IDNet NAC Extender before the repeater connected to that circuit is turned on.139
CARD 2, IDNET CARD (250 POINTS)
M1-18, 4009A REPEATER EARTH FAULT
Earth fault detected after the repeater connected to that circuit is turned on.139
CARD 2, IDNET CARD (250 POINTS)
M1-3, IDNET ISOLATOR EARTH FAULT
Earth fault detected after the IDNet isolator was turned on.139
CARD 2, IDNET CARD (250 POINTS)
M1, EARTH FAULT SEARCH FAULT CLEAR FAIL
Fault not cleared — an IDNet channel that has been isolated for fault detection still has the earth fault.139
FAULT NOT FOUND
FAULT CLEAR FAIL
The search could not locate the fault, but it acknowledges that a fault exists. FAULT NOT FOUND is returned for a Location Earth Fault Search; FAULT CLEAR FAIL for an IDNet Channel Earth Fault Search.One or more internal wiring earth(s) in the system; system defects (hardware or software, such as a failed isolation circuit); an intermittent earth that occurs inconsistently; the cable to the service port may be grounded due to the remote PC's 3-prong plug; the fault is on an auxiliary output that was excluded from the search.The problem may have to be found manually and then corrected. Once corrected, it is recommended that you restart the system (warm- or cold-start).140

Every row above cites the page of this document it came from, and each one is re-read against that page by an automatic check before publication.

Product codes covered

LT0350

Manufacturer document, published here as reference material for equipment we supply. The original lives at docs.johnsoncontrols.com. The rights holder may ask us to take it down — we will.