Fault · Simplex 4100ES · Fire alarm control unit

Simplex 4100ESNegative Ground Fault

On the display

The panel prints Negative Ground Fault. This is the only wording the manuals give for the message, and it is listed as a fault of the CPU motherboard configuration. The message concerns the RUI shield connection on the CPU motherboard.

What it means

The manuals define the message as a negative ground fault occurring on the RUI — in other words, a ground fault arising from the RUI shield connection on the CPU motherboard. It points to how the RUI shield is set up on the board rather than to a trouble elsewhere on the system.

Why it appears

  • Some devices that connect to the RUI have inherently grounded shield terminals. The manual states that for such devices 24 C cannot be used.
  • The fault appears when the 24 C setting is used anyway: the RUI SHIELD jumper P9 on the CPU motherboard is placed in position 1-2 while devices with inherently grounded shield terminals are connected to the RUI. The manual says plainly that if 24 C is used in this case, a Negative Ground Fault will occur.

What to check

  1. Look at what is connected to the RUI. Some RUI devices have inherently grounded shield terminals, and for these the 24 C setting cannot be used.
  2. On the CPU motherboard, locate the RUI SHIELD jumper P9 and note its position.
  3. If P9 sits in position 1-2 (the 24 C setting) while grounded-shield devices are on the RUI, this is exactly the condition the manual names as the cause of the fault.
  4. Reposition P9 so that 24 C is no longer selected, since the manual states that 24 C cannot be used with such devices.

Setpoints and thresholds

  • RUI SHIELD jumper P9 on the CPU motherboard: position 1-2 selects the 24 C setting. With RUI devices whose shield terminals are inherently grounded, 24 C cannot be used and produces the Negative Ground Fault.

Questions engineers ask

What does Negative Ground Fault mean on a Simplex 4100ES?

It is a negative ground fault occurring on the RUI. The manuals trace it to the RUI shield connection on the CPU motherboard.

Why does my 4100ES show a Negative Ground Fault?

The manuals give one cause: devices connected to the RUI that have inherently grounded shield terminals, while the RUI SHIELD jumper P9 is in position 1-2 so that the 24 C setting is used. In that case the manual states 24 C cannot be used and the fault will occur.

How do I fix a Negative Ground Fault on a 4100ES?

Check the devices on the RUI and the RUI SHIELD jumper P9 on the CPU motherboard. If P9 is in position 1-2 (the 24 C setting) and grounded-shield devices are connected, reposition P9 so that 24 C is no longer used.

Which jumper controls the RUI shield on the 4100ES CPU motherboard?

P9, the RUI SHIELD jumper. Position 1-2 is the 24 C setting, and it is this setting that the manual names as the trigger of the Negative Ground Fault with grounded-shield RUI devices.