On the display
The panel prints Negative Ground Fault. This is the only wording the manuals give for the message, and it is listed as a fault of the CPU motherboard configuration. The message concerns the RUI shield connection on the CPU motherboard.
What it means
The manuals define the message as a negative ground fault occurring on the RUI — in other words, a ground fault arising from the RUI shield connection on the CPU motherboard. It points to how the RUI shield is set up on the board rather than to a trouble elsewhere on the system.
Why it appears
- Some devices that connect to the RUI have inherently grounded shield terminals. The manual states that for such devices
24 C cannot be used
. - The fault appears when the 24 C setting is used anyway: the RUI SHIELD jumper P9 on the CPU motherboard is placed in position 1-2 while devices with inherently grounded shield terminals are connected to the RUI. The manual says plainly that if 24 C is used in this case, a Negative Ground Fault will occur.
What to check
- Look at what is connected to the RUI. Some RUI devices have inherently grounded shield terminals, and for these the 24 C setting cannot be used.
- On the CPU motherboard, locate the RUI SHIELD jumper P9 and note its position.
- If P9 sits in position 1-2 (the 24 C setting) while grounded-shield devices are on the RUI, this is exactly the condition the manual names as the cause of the fault.
- Reposition P9 so that 24 C is no longer selected, since the manual states that 24 C cannot be used with such devices.
Setpoints and thresholds
- RUI SHIELD jumper P9 on the CPU motherboard: position 1-2 selects the 24 C setting. With RUI devices whose shield terminals are inherently grounded, 24 C cannot be used and produces the Negative Ground Fault.
Questions engineers ask
What does Negative Ground Fault mean on a Simplex 4100ES?
It is a negative ground fault occurring on the RUI. The manuals trace it to the RUI shield connection on the CPU motherboard.
Why does my 4100ES show a Negative Ground Fault?
The manuals give one cause: devices connected to the RUI that have inherently grounded shield terminals, while the RUI SHIELD jumper P9 is in position 1-2 so that the 24 C setting is used. In that case the manual states 24 C cannot be used and the fault will occur.
How do I fix a Negative Ground Fault on a 4100ES?
Check the devices on the RUI and the RUI SHIELD jumper P9 on the CPU motherboard. If P9 is in position 1-2 (the 24 C setting) and grounded-shield devices are connected, reposition P9 so that 24 C is no longer used.
Which jumper controls the RUI shield on the 4100ES CPU motherboard?
P9, the RUI SHIELD jumper. Position 1-2 is the 24 C setting, and it is this setting that the manual names as the trigger of the Negative Ground Fault with grounded-shield RUI devices.
Messages next to this one
Source
Written from the manufacturer's manuals for the Simplex 4100ES; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: