Fault · SINAMICS S120, S150

F37899HF Damping Module: Unknown fault

What it means

F37899 — HF Damping Module: Unknown fault — means that the HF Damping Module has reported a fault which the Control Unit firmware cannot interpret. The manual explains that this happens when the firmware on the HF Damping Module is more recent than the firmware on the Control Unit, so the Control Unit receives a fault number it simply does not know. That unknown fault number is stored in r0949 and is to be interpreted as a decimal value. The drive normally raises this condition as a fault, but depending on its configuration the same event can also be output as an alarm or as a message without a reaction — the manual lists it with the message classes N and A as well.

Why it appears

  • The HF Damping Module has reported a fault that the Control Unit firmware cannot interpret.
  • The firmware on the HF Damping Module is more recent than the firmware on the Control Unit, so the Control Unit does not recognize the reported fault.

What to check

  1. Read the fault number reported by the HF Damping Module from r0949 (interpret the value as decimal). If required, look up the significance of this new fault in a more recent description of the Control Unit.
  2. Replace the firmware on the HF Damping Module by an older firmware version — the manual references r0168 for this step.
  3. Alternatively, upgrade the firmware on the Control Unit instead; the version installed there can be read from r0018.

Reading the message value

  • The drive shows the message value as New message: %1 — the newly reported fault of the HF Damping Module.
  • The fault value in r0949 is the fault number itself, interpreted as a decimal value.
  • The manual gives no bit-by-bit decoding; because the Control Unit firmware cannot interpret this fault, it points to a more recent description of the Control Unit for the significance of the number.

Parameters the manual names

  • r0949 — fault value: read the fault number that the HF Damping Module has reported (interpret decimal).
  • r0168 — the parameter the manual references when replacing the HF Damping Module firmware with an older version.
  • r0018 — Control Unit firmware version: read the installed CU firmware version here when deciding to upgrade it.

Acknowledging and restarting

This fault triggers no automatic drive response — the drive does not change its operating state, it only signals the fault. Once the firmware versions have been brought back in line, acknowledge the fault immediately; the acknowledgment specification for this code also includes POWER ON, so re-power the drive as part of clearing it. When the same condition is output as an alarm or as a message without a reaction, there is likewise no automatic response and nothing to acknowledge.

The same on every family

Every manual that describes F37899 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)IMMEDIATELY (POWER ON)General drive fault (19)NoneSINAMICS S120, S150 List Manual · p. 3277

The drives this code lives on

F37899 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F37899 mean on SINAMICS S120 or S150?

The HF Damping Module has reported a fault that the Control Unit firmware cannot interpret. This normally happens when the firmware on the HF Damping Module is more recent than the firmware on the Control Unit.

How do I clear fault F37899?

Read the reported fault number from r0949 (decimal), then either replace the HF Damping Module firmware with an older version (r0168) or upgrade the Control Unit firmware (r0018). Acknowledge the fault immediately and re-power the drive as part of clearing it.

Why does the drive keep running with F37899 active?

The drive takes no automatic action on this fault — it only signals it and does not change its operating state. No shutdown is triggered.

What is stored in r0949 for F37899?

The fault number reported by the HF Damping Module, interpreted as a decimal value. Its significance can be looked up in a more recent description of the Control Unit.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F37xxx group · SINAMICS manuals · Siemens manuals