Fault · SINAMICS S120, S150

F37885HF Damping Module (CU): Cyclic data transmission error

What it means

F37885 is raised when cyclic DRIVE-CLiQ data transmission between the HF Damping Module and the Control Unit (CU) fails: the two nodes do not send and receive in synchronism. The fault value stored with the message identifies the component involved and the concrete fault cause.

Why it appears

  • DRIVE-CLiQ communication error from the damping module to the Control Unit — the nodes do not send and receive in synchronism.
  • Which individual fault cause applies is coded in the fault value of the message (see the decoding below).

What to check

  1. Check the supply voltage of the component involved — the HF Damping Module.
  2. Carry out a POWER ON.
  3. Replace the component involved.

Reading the message value

The message value combines the component number (%1) and the fault cause (%2). In r0949 / r2124 the information is coded as 0000yyxx hex, where yy = component number and xx = error cause. The manual lists the following fault causes for this code:

  • 26 (= 1A hex): sign-of-life bit in the receive telegram not set and the receive telegram is too early.
  • 33 (= 21 hex): the cyclic telegram has not been received.
  • 34 (= 22 hex): timeout in the telegram receive list.
  • 64 (= 40 hex): timeout in the telegram send list.
  • 98 (= 62 hex): error at the transition to cyclic operation.

Parameters the manual names

  • r0949 (fault value): shows the fault value of F37885 in the coded form 0000yyxx hex, so the component number and the fault cause can be read from it.
  • r2124 (alarm value): the value the manual names alongside r0949, in which the same coded information for this message can be read.

Acknowledging and restarting

The restart is part of the remedy itself: once the supply voltage of the component involved has been checked, a POWER ON is carried out. If this does not clear the fault, the component involved is replaced. The manual names no further acknowledgement steps for this fault.

The same on every family

Every manual that describes F37885 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Internal (DRIVE-CLiQ) communication error (12)NoneSINAMICS S120, S150 List Manual · p. 3274

The drives this code lives on

F37885 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F37885 mean on a SINAMICS S120 or S150?

It reports a cyclic DRIVE-CLiQ data transmission error between the HF Damping Module and the Control Unit: the two nodes do not send and receive in synchronism.

How do I fix fault F37885?

Check the supply voltage of the component involved and then carry out a POWER ON. If the fault still occurs, the component involved must be replaced.

What does the fault value of F37885 tell me?

Read in r0949 or r2124, it is coded 0000yyxx hex: yy is the component number and xx the fault cause, for example 33 (= 21 hex) when the cyclic telegram has not been received.

Which fault causes can be behind F37885?

The manual lists a missing sign-of-life bit with an overly early receive telegram (26), an unreceived cyclic telegram (33), a timeout in the telegram receive list (34), a timeout in the telegram send list (64) and an error at the transition to cyclic operation (98).

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.