What it means
The drive raises F37896 when the properties of the HF Damping Module have changed in an incompatible fashion with respect to the properties that were read in when the drive booted. The fault value names the affected DRIVE-CLiQ component by its component number, so you can tell straight away which module is meant. The comparison is performed by the Control Unit (CU); as a typical trigger, the manual names the replacement of a DRIVE-CLiQ cable or of a DRIVE-CLiQ component. The manuals describe this code for the S120 and S150.
Why it appears
- The properties of the DRIVE-CLiQ component (HF Damping Module) named by the fault value no longer match the properties captured at boot — they have changed in a way that is incompatible with what the drive stored then.
- A DRIVE-CLiQ cable or a DRIVE-CLiQ component has been replaced; the manual gives this as one possible cause of the property change.
What to check
- Carry out a POWER ON so that the drive boots again and reads the component properties in afresh.
- If a component has been replaced, make sure the replacement is of the same component type and, if possible, has the same firmware version.
- If a DRIVE-CLiQ cable has been replaced, fit a cable with the same length as the original — or as close as possible to it — and comply with the maximum cable length.
Reading the message value
- The fault value contains the component number of the HF Damping Module whose properties have changed; the manual fills the placeholder in the message value with this component number.
Acknowledging and restarting
The fault is acknowledged immediately and requires no special measures. Acknowledging alone does not resolve the mismatch, because the properties are only read at boot: the remedy is therefore to carry out a POWER ON, after which the drive captures the properties of the HF Damping Module again. If you have replaced a component or a cable beforehand, observe the component-type, firmware-version and cable-length rules from the checks above before powering up.
The same on every family
Every manual that describes F37896 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | IMMEDIATELY | Internal (DRIVE-CLiQ) communication error (12) | None | SINAMICS S120, S150 List Manual · p. 3276 |
The drives this code lives on
F37896 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F37896 mean on a SINAMICS S120 or S150?
The properties of the HF Damping Module named by the fault value have changed in an incompatible fashion with respect to the properties read in when the drive booted. The Control Unit raises this fault.
Why does F37896 appear after I replaced a DRIVE-CLiQ component or cable?
The manual names the replacement of a DRIVE-CLiQ cable or component as a possible cause, because the replacement changes the properties the drive sees compared with boot.
How do I clear fault F37896?
Acknowledge the fault and carry out a POWER ON so the drive reads the component properties in again at boot. When replacing parts, use the same component type with if possible the same firmware version, and keep replacement cables at the original length or as close as possible to it.
What is stored in the fault value of F37896?
The component number of the affected HF Damping Module.