What it means
F35001 is raised when the Safety Basic Functions are used via the TM54F and the TM54F has been parameterized incorrectly (incorrect parameter assignment). With this functionality only four signals are permissible: STO active, SS1 active, internal event and safe state. Everything else is an illegal assignment. The two things the drive checks are the failsafe digital inputs (F-DI, Failsafe Digital Input), which must all carry the value 0 or 255, and the signal sources of the failsafe digital outputs (F-DO, Failsafe Digital Output), which must not select signals from the Safety Extended Functions.
Why it appears
- The Safety Basic Functions are used via TM54F and the TM54F has been assigned incorrect parameters.
- One or more parameters in the range p10024 ... p10038 are not set to 0 or 255.
- p10039 or one of the parameters p10042 ... p10045 uses signals from the Safety Extended Functions, although with the Safety Basic Functions only STO active, SS1 active, internal event and safe state may be parameterized.
What to check
- Read the fault value in r0949 as a binary number to localize the problem: bits 0 ... 3 show the drive group with an illegal F-DI, bits 4 ... 7 show the F-DO with an incorrect link.
- Check the setting of the failsafe digital inputs (F-DI) used for the Safety Extended Functions and set them to a value of 0 or 255 (p10024 ... p10039).
- Check the setting of the signal sources for the failsafe digital outputs (F-DO) and correct them if necessary (p10042 ... p10045).
Reading the message value
- The drive stores the fault value in r0949; interpret the value in binary.
- Bit 0 = 1: drive group 1 error
- Bit 1 = 1: drive group 2 error
- Bit 2 = 1: drive group 3 error
- Bit 3 = 1: drive group 4 error
- Bits 0 ... 3 together specify for which drive group an illegal F-DI was parameterized.
- Bit 4 = 1: F-DO 0 error (p10042)
- Bit 5 = 1: F-DO 1 error (p10043)
- Bit 6 = 1: F-DO 2 error (p10044)
- Bit 7 = 1: F-DO 3 error (p10045)
- Bits 4 ... 7 together specify for which F-DOs incorrect links were specified.
Parameters the manual names
- p10024 ... p10038 — the F-DI parameters (p10024 = SI Motion SS2 input terminal, processor 1, through p10038 = SI TM54F Emergency Stop input terminal): each must carry the value 0 or 255.
- p10039 — SI Motion Safe State signal selection (processor 1): check that its signal source does not come from the Safety Extended Functions.
- p10042 ... p10045 — the F-DO signal sources (p10042 = SI Motion F-DO signal sources, processor 1, through p10045 = SI TM54F F-DO 3 signal sources; p10043 and p10044 belong to F-DO 1 and F-DO 2): correct any link that selects a Safety Extended Functions signal.
- r0949 — fault value: read it in binary to see which drive group and which F-DO parameter the fault is reporting.
Acknowledging and restarting
F35001 is a parameterization fault and only disappears once the F-DI and F-DO assignments have been corrected. Acknowledge the fault immediately after the correction; the acknowledgement requires a POWER ON, so switch the drive's power supply off and back on again before restarting.
What differs between the drive families
Straight from the manuals' own fields — F35001 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | — | — | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 3197 |
| G130, G150 | NONE | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1867 |
The drives this code lives on
F35001 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F35001 mean on a SINAMICS drive?
It means the Safety Basic Functions are used via TM54F and the TM54F has been parameterized incorrectly. Only STO active, SS1 active, internal event and safe state may be parameterized in this mode.
How do I fix fault F35001?
Check the F-DI settings and set them to 0 or 255 (p10024 ... p10039), then check the F-DO signal sources and correct them if necessary (p10042 ... p10045). Afterwards acknowledge the fault with a POWER ON.
What does the F35001 fault value in r0949 tell me?
Read r0949 as a binary number. Bits 0 ... 3 name the drive group for which an illegal F-DI was parameterized, and bits 4 ... 7 name the F-DO with an incorrect link, from bit 4 = F-DO 0 (p10042) to bit 7 = F-DO 3 (p10045).
Why does F35001 appear even though I only use the Safety Basic Functions?
Because in this mode every F-DI parameter must be set to 0 or 255 and no signal source may be taken from the Safety Extended Functions. Either a value in p10024 ... p10038 differs from 0 and 255, or p10039 or p10042 ... p10045 selects a Safety Extended Functions signal.