What it means
F08700 is raised when the drive detects a CAN communications error on the connection to the higher-level control system. The manual splits the condition into two cases, which the fault value in r0949 (interpreted as a decimal number) tells apart: a send-telegram error counter that has run past the BUS OFF limit, and node life time monitoring that has expired. Depending on the drive's configuration, the same condition can also be issued as an alarm instead of a fault.
Why it appears
- Fault value 1 — BUS OFF: the error counter for the send telegrams has exceeded the BUS OFF value 255, and the bus has disabled the CAN controller. The manual names a bus cable short circuit, an incorrect baud rate and incorrect bit timing as causes.
- Fault value 2 — life time expired: the master no longer interrogated the CAN node status within its “life time”, obtained from the guard time (p8604[0]) multiplied by the life time factor (p8604[1]). The manual names an interrupted bus cable, a bus cable that is not connected, an incorrect baud rate, incorrect bit timing and a master fault as causes.
What to check
- Check the bus cable — fault value 1 points to a short circuit, fault value 2 to an interruption or a missing connection.
- Check the baud rate (p8622); an incorrect baud rate is listed for both fault values.
- Check the bit timing (p8623).
- Check the master — on fault value 2 it may itself be the faulty partner.
- Once the cause has been resolved, remember the manual's explicit requirement:
The CAN controller must be manually restarted with p8608 = 1 after the cause of the fault has been resolved!
Reading the message value
- The drive writes the fault value into r0949; interpret it as a decimal number.
- 1 — the error counter for the send telegrams has exceeded the BUS OFF value 255; the bus disables the CAN controller.
- 2 — the master has not interrogated the CAN node status for longer than its “life time”, obtained from the guard time (p8604[0]) multiplied by the life time factor (p8604[1]).
Parameters the manual names
- r0949 — read the fault value here, interpreted as a decimal number, to tell a BUS OFF condition (1) from an expired life time (2).
- p8604 — CAN life guarding: guard time [0] multiplied by life time factor [1] gives the life time within which the master must interrogate the node (fault value 2).
- p8622 — check here whether the set CAN bit rate matches the rest of the bus.
- p8623 — check here whether the selected CAN bit timing is correct.
- p8608 — set to 1 after the cause is resolved to clear the BUS OFF error and restart the CAN controller manually.
- p8641 — use it to set the fault response to this CAN error as required.
Acknowledging and restarting
Acknowledge the fault immediately; the drive only returns to a ready state once this is done. Resolving the cause alone is not enough: the manual requires that the CAN controller be restarted manually with p8608 = 1 after the cause of the fault has been resolved. The same condition can also appear as an alarm, depending on how the drive is configured.
What differs between the drive families
Straight from the manuals' own fields — F08700 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: NONE (OFF1, OFF2) Servo: OFF3 (NONE, OFF1, OFF2) Vector: OFF3 (NONE, OFF1, OFF2) Hla: OFF3 (NONE, OFF1, OFF2) | IMMEDIATELY | Communication error to the higher-level control system (9) | None | SINAMICS S120, S150 List Manual · p. 2925 |
| G130, G150 | Vector: OFF3 (NONE, OFF1, OFF2) Infeed: NONE (OFF1, OFF2) | IMMEDIATELY | Communication error to the higher-level control system (9) | None | SINAMICS G130, G150 List Manual · p. 1639 |
| G120 | OFF3 (NONE, OFF1, OFF2) | — | Communication error to the higher-level control system (9) | — | SINAMICS G120 · p. 899 |
The drives this code lives on
F08700 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault value 1 of F08700 mean?
The error counter for the send telegrams has exceeded the BUS OFF value 255, so the bus has disabled the CAN controller. The manual names a bus cable short circuit, an incorrect baud rate or incorrect bit timing as possible causes.
Why does F08700 occur with fault value 2?
The master has not interrogated the CAN node status for longer than its life time, calculated as the guard time (p8604[0]) multiplied by the life time factor (p8604[1]). Causes include an interrupted or unconnected bus cable, wrong baud rate or bit timing, and a master fault.
How do I clear F08700 after fixing the bus?
Acknowledge the fault, and after the cause has been resolved set p8608 = 1 to manually restart the CAN controller. The manual stresses that this restart step must not be skipped.
Can F08700 also appear as an alarm?
Yes. Depending on the drive's configuration, the same condition can also be issued as an alarm instead of a fault.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F08xxx group · SINAMICS manuals · Siemens manuals