What it means
F07862 is one of the externally defined faults: the drive raises it when a condition put together from binary signals in the drive's own interconnection becomes active. Internally, the drive forms an AND logic operation from the binector inputs p2108, p3111 and p3112 (with p3112 entering negated) and initiates the fault on a 1/0 edge of this result, together with the switch-on delay p3110. The fault therefore does not come from a measured current or temperature, but from signal states that the interconnection at these parameters defines. Depending on the drive's configuration, the same condition can also be issued as an alarm (A) instead of a fault; in that variant the drive takes no reaction and no acknowledgement is required.
Why it appears
- The manual names only one cause:
The condition for "External fault 3" is satisfied.
What actually lies behind it depends on the signals interconnected at p2108, p3111 and p3112. - In mechanism, the fault is initiated by a 1/0 edge — the AND of the three binector inputs falls from 1 to 0 — with the switch-on delay p3110 belonging to the same triggering logic.
What to check
- Look up which signal sources are interconnected at the binector inputs p2108 (External fault 3), p3111 (External fault 3 enable) and p3112 (External fault 3 enable negated); these parameters define what External fault 3 watches in your plant.
- Check the state of these signals at the time of the fault: the AND result must have dropped from 1 to 0 for the fault to be initiated.
- Check the setting of the switch-on delay p3110, which is part of the same triggering logic.
- Eliminate the causes of this fault — restore the external signal condition so that the AND no longer evaluates to 0.
- Acknowledge the fault as described below before restarting.
Parameters the manual names
- p2108 (BI: External fault 3) — binector input that feeds the External fault 3 AND logic; start the search here to see which signal is interconnected.
- p3111 (BI: External fault 3 enable) — binector input that enables the fault and enters the same AND logic.
- p3112 (BI: External fault 3 enable negated) — binector input that enters the AND logic in negated form.
- p3110 (External fault 3 switch-on delay) — sets the switch-on delay applied when the 1/0 edge initiates the fault.
Acknowledging and restarting
Eliminate the causes of the fault first, then acknowledge it. The acknowledgement has to be done immediately; switching the power off and on (POWER ON) also acknowledges the fault. If the message is present only as an alarm (A), it requires no acknowledgement.
What differs between the drive families
Straight from the manuals' own fields — F07862 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Hla: OFF2 (NONE, OFF1, OFF3, STOP2) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | None | SINAMICS S120, S150 List Manual · p. 2871 |
| G130, G150 | Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Infeed: OFF2 (NONE, OFF1) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | None | SINAMICS G130, G150 List Manual · p. 1603 |
| G120 | OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) | IMMEDIATELY (POWER ON) | External measured value / signal state outside the permissible range (16) | — | SINAMICS G120 · p. 884 |
| G120XA | OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) | IMMEDIATELY (POWER ON) | — | — | SINAMICS G120XA PN converter · p. 1135 |
The drives this code lives on
F07862 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does F07862 External fault 3 mean on a SINAMICS drive?
The externally defined fault condition is satisfied: the AND of the binector inputs p2108, p3111 and p3112 has fallen from 1 to 0 (a 1/0 edge), and the fault is initiated together with the switch-on delay p3110.
How do I clear F07862?
Eliminate the cause so the AND result returns to 1, then acknowledge the fault immediately — a POWER ON also acknowledges it. If the message is issued as an alarm (A), no acknowledgement is needed.
Which parameters belong to External fault 3?
p2108 (External fault 3), p3111 (enable), p3112 (enable negated) and p3110 (switch-on delay). The fault is initiated by a 1/0 edge of the AND logic formed from these inputs.
Can F07862 also appear as an alarm?
Yes, the same condition can also be issued as an alarm (A); in that variant the drive takes no reaction and no acknowledgement is required.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.