Fault · SINAMICS G120XA

F07390Drive: DC link capacitor forming fault

What it means

F07390 reports that the “DC link capacitor forming” function was canceled with a fault: bit 3 of the forming status word r3382 is set (r3382.3 = 1), and the expected DC link voltage was out of tolerance. The drive coasts down (OFF2) and the fault must be acknowledged immediately before it can be started again.

Why it appears

  • The “DC link capacitor forming” function was canceled with a fault — the forming status word r3382 signals this in bit 3 (r3382.3 = 1).
  • The expected DC link voltage is out of tolerance.

What to check

  1. Check the drive device itself — supply voltage, terminals and the further points the manual’s checklist names.
  2. Set the activation and duration of the forming function again so that p3380 > 0.
  3. Restart the forming function with a 0/1 signal at p0840 (ON).

Parameters the manual names

  • r3382 (Forming status word / Forming ZSW): read it after the trip — bit 3 = 1 tells you that the forming function was canceled with a fault.
  • p3380 (Forming activation/duration / Form act/duration): set the activation/duration again once the cause is removed; the value must be greater than 0 for forming to run.
  • p0840 (BI: ON / OFF (OFF1)): the drive’s ON command — switch it from 0 to 1 to restart the forming function.

Acknowledging and restarting

Acknowledge the fault immediately after the cause has been removed. Then set the forming activation/duration again (p3380 > 0) and restart the forming function with a 0/1 signal at p0840 (ON).

The same on every family

Every manual that describes F07390 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G120XAOFF2IMMEDIATELYSINAMICS G120XA PN converter · p. 1126

Questions technicians ask

What does fault F07390 mean?

It reports that the DC link capacitor forming function was canceled with a fault (r3382.3 = 1) because the expected DC link voltage was out of tolerance.

How do I clear fault F07390?

Check the drive device (supply voltage, terminals), set the forming activation/duration again so that p3380 > 0, and restart forming with a 0/1 signal at p0840. Acknowledge the fault immediately beforehand.

How is forming restarted after F07390?

Give the drive an ON command: switch the signal at p0840 from 0 to 1. Forming must be activated again first with p3380 > 0.

Which parameters belong to F07390?

r3382 shows the forming status (bit 3 = forming canceled with fault), p3380 sets the forming activation/duration, and p0840 is the ON/OFF1 command used to restart forming.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals