Fault · SINAMICS G130, G150, S120, S150

F05051Parallel circuit: Power unit pulse enable missing

What it means

F05051 reports that in a parallel circuit of power units, the pulses of one or several of the paralleled units could not be enabled — the pulse enable of a power unit in the parallel circuit is missing. The fault value names the power unit concerned, so the message tells you both what happened (a missing pulse enable) and where (which power unit number). The manuals describe this fault for the parallel power-unit circuit on G130, G150, S120 and S150.

Why it appears

  • One or several power units in the parallel circuit did not enable their pulses; the pulse enable for at least one of the paralleled power units is missing. Both manual entries for this code give this same cause, so it applies to the whole parallel circuit rather than to one particular drive configuration.

What to check

  1. Acknowledge the faults that are still present on the power units of the parallel circuit.
  2. Inhibit the pulses of the affected power unit — the unit whose number appears in the fault value — via p7001.

Reading the message value

  • The drive stores the number of the power unit involved as the fault value.
  • Read this value in r0949 as a decimal number (not as a bit pattern): the decimal figure is the number of the power unit whose pulse enable is missing.

Parameters the manual names

  • r0949 — fault value; for F05051, interpreted as a decimal number, it identifies the power unit in the parallel circuit that is involved.
  • p7001 — Par_circuit power units enable (PU enable); the parameter with which the pulses of the affected power unit are inhibited, as the remedy for this fault requires.

Acknowledging and restarting

Acknowledge the fault itself once the remedy has been carried out: the power unit faults that are still present are acknowledged first, then the pulses of the power unit named in the fault value are inhibited via p7001.

What differs between the drive families

Straight from the manuals' own fields — F05051 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: OFF2 (NONE, OFF1) Vector: OFF2 (NONE, OFF1, OFF3, STOP2)IMMEDIATELYApplication/technological function faulted (17)Power ModuleSINAMICS S120, S150 List Manual · p. 2748
G130, G150Vector: OFF2 (NONE, OFF1, OFF3, STOP2) Infeed: OFF2 (NONE, OFF1)IMMEDIATELYApplication/technological function faulted (17)Power ModuleSINAMICS G130, G150 List Manual · p. 1521

The drives this code lives on

F05051 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F05051 mean?

That in a parallel circuit the pulses of one or several power units could not be enabled. The fault value tells you which power unit is involved.

How do I find the affected power unit for F05051?

Read the fault value in r0949 as a decimal number — that number is the power unit involved in the parallel circuit.

How do I clear fault F05051?

Acknowledge any power unit faults that are still present, inhibit the pulses of the affected power unit via p7001, and then acknowledge the fault itself.

Which SINAMICS drives can issue F05051?

The fault is described for the parallel power-unit circuit on G130, G150, S120 and S150.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.