Fault · SINAMICS G120, G120XA, G130, G150, S120, S150

F02152OA: Insufficient memory

What it means

The Control Unit does not have enough memory for the functions configured on it: the drive raises F02152 when too many functions have been configured — for example too many drives, function modules, data sets, blocks, Technology Extensions (TEC) or OA applications. On Control Units that use Technology Extensions the code is titled 'TEC: insufficient memory'; on the G120/G120XA, where the equivalent items are the Open Architecture applications, it is titled 'OA: Insufficient memory'. The drive's configuration decides whether the condition appears as a fault or as an alarm (A); as an alarm it triggers no reaction and needs no acknowledgment.

Why it appears

  • Too many functions have been configured on this Control Unit — e.g. too many drives, function modules, data sets and blocks.
  • Which extra functions are counted depends on the Control Unit: on drives with Technology Extensions, the configured Technology Extensions (TEC) belong to the list; on the G120/G120XA, the OA (Open Architecture) applications do.

What to check

  1. Read the fault value in r0949 and interpret it as a decimal number; the manual reserves this value for internal Siemens troubleshooting, so it is mainly useful when working with support.
  2. Change the configuration on this Control Unit so that fewer functions are configured: fewer drives, function modules, data sets and blocks.
  3. On a Control Unit with Technology Extensions, configure fewer Technology Extensions (TEC); on the G120/G120XA, configure fewer OA applications.
  4. If the configured functions are all genuinely required, use an additional Control Unit.

Reading the message value

  • The drive writes the fault value to r0949; interpret it as a decimal number.
  • The manual publishes no bit or field decoding for this code — the value is Only for internal Siemens troubleshooting.

Parameters the manual names

  • r0949 — fault value of this message; for F02152 read it as a decimal number, knowing that its content is meant for internal Siemens troubleshooting only.

Acknowledging and restarting

The drive stops with OFF1. The fault is acknowledged immediately, and a POWER ON — the power supply must be switched off and on again — is additionally required before the drive can run again. Apply the remedy (a reduced configuration or an additional Control Unit) before returning the drive to service.

What differs between the drive families

Straight from the manuals' own fields — F02152 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150OFF1IMMEDIATELY (POWER ON)Hardware/software error (1)NoneSINAMICS G130, G150 List Manual · p. 1511
S120, S150OFF1IMMEDIATELY (POWER ON)Hardware/software error (1)NoneSINAMICS S120, S150 List Manual · p. 2736
G120OFF1IMMEDIATELY (POWER ON)Hardware/software error (1)SINAMICS G120 · p. 866
G120XAOFF1IMMEDIATELY (POWER ON)SINAMICS G120XA PN converter · p. 1115

The drives this code lives on

F02152 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F02152 mean?

It means the Control Unit has too many functions configured — e.g. too many drives, function modules, data sets, blocks, Technology Extensions (TEC) or OA applications — and its memory is no longer sufficient.

How do I fix fault F02152?

Change the configuration on the Control Unit so that fewer functions are configured, or use an additional Control Unit. Then acknowledge the fault immediately and perform a POWER ON before restarting.

Why is it called 'TEC: insufficient memory' in one manual and 'OA: Insufficient memory' in another?

Both are the same code, F02152. The title follows the function group on the Control Unit: TEC stands for Technology Extension, OA for Open Architecture.

What is stored in the fault value of F02152?

The drive writes it to r0949 as a decimal number. Per the manual it is only for internal Siemens troubleshooting, so there is no decoding to evaluate on site.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.