What it means
The Control Unit (CU) raises F01200 — CU: Time slice management internal software error
— when its time slice management detects an internal software error. The manuals tie this to the sampling time configuration: the sampling times may have been set inadmissibly, and too many different sampling times may have been set. The available time slices can also be used up, either by technology functions (e.g. DCC) or by the basic system itself. The drive coasts down when the fault trips and will only start again after the power supply has been switched off and on again. Which of these situations applies is recorded as a hexadecimal fault value in r0949.
Why it appears
- The Control Unit (CU) has detected an internal error in its time slice management.
- The sampling times may have been set inadmissibly; too many different sampling times may have been set.
- The time slices available to the CU are used up: technology functions (e.g. DCC) occupy too many of them (fault value 998), or the basic system does (fault value 999).
What to check
- Read the fault value in r0949 (interpret hexadecimal) to see whether technology functions or the basic system have occupied too many time slices.
- Check the sampling time setting in p0112, p0115, p4099, p9500 and p9511 — too many different sampling times may have been set.
- Contact Technical Support; the manual reserves additional fault values for internal Siemens troubleshooting only.
Reading the message value
The drive stores the fault value in r0949; the manual specifies interpreting it in hexadecimal.
- 998: too many time slices occupied by technology functions (e.g. DCC).
- 999: too many time slices occupied by the basic system.
- Additional values are provided only for internal Siemens troubleshooting.
Parameters the manual names
- r0949 — holds the fault value; read it in hexadecimal to tell the 998 case (technology functions) from the 999 case (basic system).
- p0112 — pre-setting of the sampling time of p0115 (t_sample for p0115); one of the settings to check for this fault.
- p0115 — sampling time for the supplementary functions (t_samp suppl_fct); one of the settings to check for this fault.
- p4099 — sampling time of the TM31 inputs/outputs (TM31 I/O t_sample); belongs to the sampling time review this fault calls for.
- p9500 — SI Motion monitoring clock cycle of the Control Unit (SI Mtn clock CU); belongs to the sampling time review this fault calls for.
- p9511 — SI Motion actual value sensing cycle clock of the Control Unit (SI Mtn act clk CU); belongs to the sampling time review this fault calls for.
Acknowledging and restarting
The fault is acknowledged immediately, and this acknowledgement takes the form of a power cycle: switch the power supply off and then on again before the drive will run. The drive coasts down while the fault is active. Before restarting, review the sampling time settings listed above; Technical Support is the manual's second remedy step.
The same on every family
Every manual that describes F01200 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | Control Unit (CU) | SINAMICS G130, G150 List Manual · p. 1393 |
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | Control Unit (CU) | SINAMICS S120, S150 List Manual · p. 2582 |
The drives this code lives on
F01200 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS fault F01200 mean?
It reports an internal software error in the Control Unit's time slice management. The manuals tie it to sampling times that may have been set inadmissibly, so that too many different sampling times occur or the time slices are used up.
What do fault values 998 and 999 in r0949 mean for F01200?
998 means too many time slices are occupied by technology functions (e.g. DCC); 999 means too many time slices are occupied by the basic system. Any other value is only for internal Siemens troubleshooting.
How do I acknowledge and clear F01200?
The drive coasts down and the fault is acknowledged by switching the power supply off and on again. Before restarting, check the sampling time settings in p0112, p0115, p4099, p9500 and p9511.
Which parameters are relevant for F01200?
The sampling time parameters p0112, p0115, p4099, p9500 and p9511, plus r0949, which holds the fault value and is interpreted in hexadecimal.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.