Alarm · SINAMICS G130, G150, S120, S150

A35999TM: Unknown alarm

What it means

SINAMICS reports A35999 (TM: Unknown alarm) when a Terminal Module (TM) has issued an alarm that the firmware of the Control Unit (CU) cannot interpret — the CU simply does not know this alarm. The manual states that this can occur if the firmware on the Terminal Module is more recent than the firmware on the Control Unit, because newer component firmware can report alarms the older CU firmware has never seen. Depending on how the drive is configured, the same condition can also be output as a fault (F35999) or as a message without any reaction.

Why it appears

  • A Terminal Module has issued an alarm that the Control Unit firmware cannot interpret.
  • The firmware on the Terminal Module is more recent than the firmware on the Control Unit, so this new alarm is unknown to the CU.

What to check

  1. Identify the unknown alarm: the drive stores its alarm number in r2124, to be interpreted as a decimal value. The message text itself is composed as 'New message: %1'.
  2. If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
  3. Close the firmware gap in one of two ways: replace the firmware on the Terminal Module by an older firmware version (r0158).
  4. Alternatively, upgrade the firmware on the Control Unit (r0018) so the CU firmware matches the component again.

Reading the message value

  • Message value: 'New message: %1'.
  • Alarm value (r2124, interpret decimal): alarm number — the number of the alarm that the Terminal Module has raised and that the Control Unit firmware could not interpret.

Parameters the manual names

  • r2124 (alarm value): here the drive stores the alarm number of the unknown TM message; interpret the value as a decimal to see which new alarm arrived.
  • r0158 (listed in the parameter chapter as Voltage Sensing Module firmware version / VSM FW version): the remedy references this parameter when the Terminal Module firmware is to be replaced by an older version.
  • r0018 (Control Unit firmware version): the remedy references this parameter when the Control Unit firmware is to be upgraded.

Acknowledging and restarting

As an alarm, A35999 requires no acknowledgement and the drive takes no automatic action in response to it. If the drive configuration raises the same condition as a fault instead, that fault is acknowledged immediately — a POWER ON is sufficient. As long as the Terminal Module runs firmware newer than that of the Control Unit, alarms unknown to the CU can keep arriving, so the firmware downgrade on the TM or the upgrade of the CU is the actual remedy.

The same on every family

Every manual that describes A35999 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEGeneral drive fault (19)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3249
G130, G150NONENONEGeneral drive fault (19)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1911

The drives this code lives on

A35999 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A35999 TM: Unknown alarm mean?

A Terminal Module has issued an alarm that the Control Unit firmware cannot interpret. The manual says this can occur if the firmware on the Terminal Module is more recent than the firmware on the Control Unit.

How do I find out which alarm is behind A35999?

The alarm number is stored in r2124 and must be interpreted as a decimal; the message text itself reads 'New message: %1'. Its significance can be read in a more recent description of the Control Unit.

How do I fix A35999?

Either replace the firmware on the Terminal Module with an older version (r0158) or upgrade the firmware on the Control Unit (r0018), so the version gap between TM and CU is closed.

Does A35999 stop the drive or need to be acknowledged?

As an alarm it requires no acknowledgement and the drive takes no automatic action. If the same condition is output as a fault, it is acknowledged immediately — a POWER ON is sufficient.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A35xxx group · SINAMICS manuals · Siemens manuals