Alarm · SINAMICS G130, G150, S120, S150

A32920Encoder 2: Temperature sensor fault

What it means

A32920 is the temperature sensor fault of the Encoder 2 sensing channel: while evaluating the motor temperature sensor connected there, the drive detected a fault. The manuals describe the condition identically for Sensor Module Encoder 2 across the drive families, so the message means the same thing on all of them. Depending on the drive's configuration, the same condition can also be issued as a fault or be signalled without a reaction.

Why it appears

  • Wire breakage or the sensor is not connected — fault cause 1 (= 01 hex): KTY: R > 1630 Ohm, PT1000: R > 1720 Ohm.
  • The measured resistance is too low — fault cause 2 (= 02 hex): PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm.
  • The Sensor Module itself can be the cause: the manual names a hardware defect or incorrect calibration data as the reason for replacing it.

What to check

  1. Check that the encoder cable is the correct type and is correctly connected.
  2. Check the temperature sensor selection in p0600 to p0603 — p0600 sets the motor temperature sensor for monitoring and p0603 the CI: motor temperature signal source.
  3. Replace the Sensor Module — the manual gives a hardware defect or incorrect calibration data as the reason.

Reading the message value

The drive puts two pieces of information into the message value: the fault cause (%1) and the channel number (%2). You read them in r0949 (fault value) or r2124 (alarm value). The individual information is coded as follows in the message value (r0949/r2124): 0000yyxx hex: yy = channel number, xx = error cause

  • xx = 01 hex (fault cause 1): wire breakage or sensor not connected — KTY: R > 1630 Ohm, PT1000: R > 1720 Ohm.
  • xx = 02 hex (fault cause 2): measured resistance too low — PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm.
  • Additional values are only for internal Siemens troubleshooting.

Parameters the manual names

  • r0949 — fault value: shows the coded message value (0000yyxx hex) while the condition is present as a fault.
  • r2124 — alarm value: shows the same coding while A32920 is present as an alarm.
  • p0600 — motor temperature sensor for monitoring: check the sensor selected here as part of the temperature sensor selection in p0600 to p0603.
  • p0603 — CI: motor temperature signal source: also part of the sensor selection to be checked for this message.

Acknowledging and restarting

As an alarm, A32920 requires no acknowledgement. If the drive's configuration raises the same condition as a fault, it must be acknowledged immediately so the drive can be restarted. The manual names no separate reset action: the cause is removed with the checks above — cable type and connection, the sensor selection in p0600 to p0603, or a Sensor Module replacement.

The same on every family

Every manual that describes A32920 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Sensor Module Encoder 2SINAMICS S120, S150 List Manual · p. 3130
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Sensor Module Encoder 2SINAMICS G130, G150 List Manual · p. 1806

The drives this code lives on

A32920 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A32920 on my SINAMICS mean?

It is the Encoder 2 temperature sensor fault: while evaluating the motor temperature sensor connected to Encoder 2, the drive detected a problem — a wire break or an unconnected sensor, or a measured resistance that is too low.

Which resistance limits are behind A32920?

Fault cause 1 (= 01 hex) is wire breakage or sensor not connected: KTY: R > 1630 Ohm, PT1000: R > 1720 Ohm. Fault cause 2 (= 02 hex) is measured resistance too low: PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm.

How do I fix alarm A32920?

Check that the encoder cable is the correct type and is correctly connected, then check the temperature sensor selection in p0600 to p0603. If the cause remains, replace the Sensor Module — the manual names a hardware defect or incorrect calibration data as the reason.

Where can I read the fault cause and channel number for A32920?

In r0949 (fault value) or r2124 (alarm value), coded 0000yyxx hex: yy is the channel number, xx the error cause (01 hex wire breakage, 02 hex resistance too low). Additional values are only for internal Siemens troubleshooting.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A32xxx group · SINAMICS manuals · Siemens manuals