What it means
The power unit reports that, referred to the supply voltage, the DC link voltage is too high: the device supply voltage (p0210) was reduced, and the DC link voltage still present is too high for this new, lower supply voltage. DC link precharging cannot be completed, because this could place some converter components at risk. The drive's configuration decides whether the condition is signalled as this alarm or with no reaction (N).
Why it appears
- The device supply voltage (p0210) was reduced.
- At the same time, a DC link voltage is present that is too high when referred to the new supply voltage — the alarm is only output if both conditions are satisfied simultaneously.
- As a result, DC link precharging cannot be completed, since continuing could place some converter components at risk.
What to check
- Read the alarm value in r2124, interpreting it as a decimal number: it gives the voltage to which the DC link voltage must, in the meantime, be reduced in order to complete precharging.
As a minimum, reduce the DC link voltage to the voltage specified in the alarm value.
- Wait for the alarm to clear on its own — it is withdrawn automatically once the DC link voltage drops below the voltage specified in the alarm value.
- While the alarm is active, do not try to enable the pulses: the drive then outputs fault F07802.
Reading the message value
- The alarm value is stored in r2124 and must be interpreted as a decimal number.
- It contains the voltage value to which the DC link voltage must, in the meantime, be reduced in order to complete precharging, in volts [V].
Parameters the manual names
- p0210 (Drive unit line supply voltage / U_connect) — the device supply voltage whose reduction is the trigger of this alarm; the DC link voltage is judged against the value stored here.
- r2124 (Alarm value) — read here, interpreted as a decimal number, the voltage to which the DC link voltage must be reduced so that precharging can be completed.
Acknowledging and restarting
No acknowledgement action is required: the alarm is withdrawn automatically as soon as the DC link voltage drops below the voltage specified in the alarm value (r2124). Do not enable the pulses in the meantime — if an attempt is made to enable the pulses while the alarm is still active, the drive outputs fault F07802.
The same on every family
Every manual that describes A30079 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Infeed faulted (13) | Power Module | SINAMICS S120, S150 List Manual · p. 2966 |
The drives this code lives on
A30079 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A30079 mean on a SINAMICS S120 or S150?
The power unit reports that the DC link voltage is too high when referred to the supply voltage, because the device supply voltage (p0210) was reduced. DC link precharging cannot be completed, since this could place some converter components at risk.
How do I clear alarm A30079?
Reduce the DC link voltage to at least the voltage given in the alarm value r2124. The alarm is then withdrawn automatically as soon as the DC link voltage drops below that value, with no acknowledgement action.
What does the alarm value of A30079 tell me?
r2124, interpreted as a decimal number, contains the voltage in volts to which the DC link voltage must, in the meantime, be reduced in order to complete precharging.
Why does fault F07802 appear together with A30079?
The drive outputs fault F07802 if an attempt is made to enable the pulses even though the alarm is active. Let the DC link voltage drop below the value in r2124 first, so that the alarm is withdrawn.
Codes next to this one