What it means
A30076 is the power unit's warning that the energy absorbed by the internal braking resistor has exceeded the alarm threshold of 80 %. The condition matters while the power unit operates in generator mode: if generation continues unchanged, the absorbed energy can climb to the shutdown threshold. To avoid overheating of the braking resistor, the drive inhibits its use and outputs alarm A30077. Depending on how the drive is configured, the same condition can also be output without a reaction. The message value itself tells you how much energy the resistor has absorbed, so you can read the actual load directly from the alarm.
Why it appears
- The energy absorbed by the internal braking resistor has exceeded the alarm threshold of 80 %.
- The power unit is being operated in generator mode; if it keeps operating in generator mode, the absorbed energy can reach the shutdown threshold.
What to check
- Read the alarm value in r2124 (interpret decimal): it shows the energy absorbed by the braking resistor in Ws.
- Reduce the power when generating.
- With a DC link coupling, take the generating power of all of the coupled power units into consideration.
Reading the message value
- The message value (%1) is the alarm value in r2124; interpret it as a decimal number. It contains the energy absorbed by the braking resistor in Ws.
Parameters the manual names
- r2124 — alarm value of this message: read the energy absorbed by the braking resistor (in Ws) here, interpreting the value as a decimal number.
Acknowledging and restarting
No acknowledgement is required for this alarm, and the manuals describe no separate reset step. What they call for is an operational change: reduce the power when generating, taking the generating power of all of the coupled power units into account on a DC link coupling. To protect the braking resistor from overheating, its use is inhibited and alarm A30077 is output.
The same on every family
Every manual that describes A30076 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Braking Module faulted (14) | Power Module | SINAMICS S120, S150 List Manual · p. 2965 |
The drives this code lives on
A30076 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A30076 mean on a SINAMICS drive?
It means the energy absorbed by the internal braking resistor has exceeded the alarm threshold of 80 %. To avoid overheating, the drive inhibits use of the braking resistor and outputs alarm A30077.
How do I fix A30076?
Reduce the power when generating. On a DC link coupling, the generating power of all of the coupled power units must be taken into consideration.
Does A30076 have to be acknowledged?
No acknowledgement is required. The alarm reports a load condition on the internal braking resistor, and the remedy is to reduce the generating power.
Where can I see the absorbed energy behind A30076?
In the alarm value r2124, interpreted as a decimal number — it holds the energy absorbed by the braking resistor in Ws.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the A30xxx group · SINAMICS manuals · Siemens manuals