What it means
The manuals call this message Monitoring underspeed threshold fallen below alarm
: the drive has detected that its speed has fallen below the alarm threshold for the lower speed. That threshold is speed threshold 2 (p2155), used together with the hysteresis p2140. The monitoring is active either because it was enabled with p2149.6 = 1, or because it is activated automatically internally for a separately excited synchronous motor in closed-loop torque control without an encoder (p1300 = 20, p1501 set). While the speed is below the threshold, status bit r2197.1 = 1. Whether the alarm is actually output depends on the control mode: in closed-loop control without an encoder it is only output for an excited motor (r0056.4 = 1); in closed-loop control with an encoder it is always output. A07821 is an alarm without an automatic shutdown and without an acknowledgement requirement.
Why it appears
- The speed has fallen below the alarm threshold for the lower speed (speed threshold 2, p2155, with hysteresis p2140).
- The monitoring is active: it was enabled with p2149.6 = 1, or it is automatically active internally for a separately excited synchronous motor in closed-loop torque control without an encoder (p1300 = 20, p1501 set) — in the second case the alarm can appear without explicit activation.
What to check
- Check the parameterization of the threshold: p2155 and p2140.
- If the parameterization is correct, reduce the load if required.
- For generator applications, switch on an additional unit.
Parameters the manual names
- p2149 (Monitoring configuration): set bit 6 to 1 (p2149.6 = 1) to activate this underspeed monitoring.
- p2155 (Speed threshold 2): holds the lower-speed threshold whose parameterization you check when the alarm appears.
- p2140 (Hysteresis speed 2): the hysteresis belonging to that threshold, checked together with p2155.
- p1300 (Open-loop/closed-loop control operating mode): value 20 is the closed-loop torque control mode in which the monitoring is automatically active for a separately excited synchronous motor without an encoder.
- p1501 (BI: Change over between closed-loop speed/torque control): set together with p1300 = 20, it identifies the torque-control mode in which the monitoring switches on automatically.
Acknowledging and restarting
A07821 requires no acknowledgement and does not force the drive to shut down. It clears itself once the speed is back above the threshold; status bit r2197.1 = 1 shows that the value is still below it. If the alarm keeps returning, check the threshold values in p2155 and p2140, reduce the load if required, and for generator applications switch on an additional unit.
The same on every family
Every manual that describes A07821 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | NONE | Application/technological function faulted (17) | Control Unit (CU) | SINAMICS G130, G150 List Manual · p. 1598 |
| S120, S150 | NONE | NONE | Application/technological function faulted (17) | Control Unit (CU) | SINAMICS S120, S150 List Manual · p. 2867 |
The drives this code lives on
A07821 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A07821 mean on a SINAMICS drive?
The speed has fallen below the alarm threshold for the lower speed (speed threshold 2, p2155). It is an alarm, not a fault: the drive does not shut down and no acknowledgement is needed.
How do I reset or clear A07821?
No acknowledgement is required — the alarm clears itself once the speed is back above the threshold. If it keeps coming back, check p2155 and p2140 and reduce the load if required.
Which parameter sets the A07821 underspeed threshold?
p2155 (Speed threshold 2), with the hysteresis p2140. The monitoring itself is activated with p2149.6 = 1.
When is A07821 output in closed-loop control without an encoder?
Only for an excited motor (r0056.4 = 1); with an encoder the alarm is always output. For a separately excited synchronous motor in closed-loop torque control without an encoder (p1300 = 20, p1501 set), the monitoring is automatically active internally.