Alarm · SINAMICS G130, G150, S120, S150

A07820Drive: Temperature sensor not connected

What it means

A07820 is raised when the motor temperature sensor that the drive is configured to use for monitoring — the source selected in p0600 — is not available. The alarm value stored in r2124 tells you which of six configuration situations the drive has detected: a sensor type set in p0601 that the selection in p0600 cannot evaluate, a signal source that is not interconnected, a component with sensor evaluation that is missing or was removed while the drive was running, or a Motor Module whose firmware cannot evaluate the sensor at all (r0192.21). The alarm therefore points at the sensor configuration, not at an overtemperature.

Why it appears

  • The motor temperature sensor selected for monitoring in p0600 is not available to the drive.
  • Which of the six concrete situations applies is reported as the alarm value in r2124 — a mismatch between the sensor type in p0601 (SME or BICO), the evaluation selected in p0600 and the interconnected signal sources (p0603, p0608, p0609), a component with sensor evaluation that is missing or has been removed in the meantime, or a Motor Module on which evaluation is not possible (r0192.21).

What to check

  1. Read the alarm value in r2124 (interpret it decimal) to identify which of the six cases applies.
  2. Alarm value 1: in p0600 set an encoder with temperature sensor.
  3. Alarm value 2: interconnect p0603 with the temperature signal.
  4. Alarm value 3 or 4: set the available temperature sensor (p0600, p0601); alternatively set p4610 ... p4613 = 0 (no sensor), or interconnect p0608 or p0609 with an external temperature signal.
  5. Alarm value 5: connect the component with the temperature sensor and check the DRIVE-CLiQ connection.
  6. Alarm value 6: update the Motor Module firmware and connect the temperature sensor via an encoder.

Reading the message value

The message value %1 is the alarm value; the drive stores it in r2124, to be interpreted decimal:

  • 1 — p0601 = 10 (SME), but in p0600 not evaluated via encoder is selected.
  • 2 — p0600 = 10 (BICO), but the signal source (p0603) is not interconnected.
  • 3 — p0601 = 11 (BICO), but in p0600 not evaluated via BICO interconnection is selected (20 or 21).
  • 4 — p0601 = 11 (BICO) and p4610-p4613 > 0, but the associated signal source (p0608, p0609) is not interconnected.
  • 5 — Component with sensor evaluation not present or has been removed in the meantime.
  • 6 — Evaluation via Motor Module not possible (r0192.21).

Parameters the manual names

  • p0600 (Motor temperature sensor for monitoring) — the selection this alarm complains about; set an encoder with temperature sensor or the actually available sensor here.
  • p0601 (Motor temperature sensor type) — must agree with the evaluation selected in p0600; with p0601 = 10 (SME) or 11 (BICO), the matching signal source must be interconnected.
  • p0603 (CI: Motor temperature signal source) — interconnect this with the temperature signal when p0600 = 10 (BICO).
  • p4610 ... p4613 (sensor types 1 to 4, MDS) — set to 0 if no sensor is used; if they remain greater than 0, the associated signal source must be interconnected.
  • p0608 / p0609 (CI: Motor temperature signal source 2 / 3) — the signal sources to interconnect with an external temperature signal when p4610 ... p4613 stay greater than 0.
  • r2124 (Alarm value) — read it decimal to determine which of the six cases applies.
  • r0192 (Power unit firmware properties 1) — bit .21 shows whether evaluation via the Motor Module is possible at all.

Acknowledging and restarting

A07820 requires no acknowledgement and the drive does not trip on it. Once the sensor configuration in p0600/p0601 and the signal-source interconnections are corrected — or the missing component is reconnected — the alarm clears by itself.

What differs between the drive families

Straight from the manuals' own fields — A07820 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1598
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2866

The drives this code lives on

A07820 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A07820 mean?

The motor temperature sensor that monitoring is configured to use (selection in p0600) is not available. The alarm value in r2124 identifies the exact configuration problem among six cases.

How do I fix A07820?

Read the alarm value in r2124, then typically set p0600/p0601 to the sensor actually present and interconnect p0603 (or p0608/p0609) as its signal source. If the alarm value is 5, reconnect the component with sensor evaluation and check the DRIVE-CLiQ connection.

Do I have to acknowledge A07820?

No. The drive does not react to this alarm and no acknowledgement is required; it goes away on its own once the configuration is consistent.

What does alarm value 5 of A07820 mean?

The component with sensor evaluation is not present or has been removed in the meantime. Connect the component with the temperature sensor and check the DRIVE-CLiQ connection.