Alarm · SINAMICS G130, G150, S120, S150

A07557Encoder 1: Reference point coordinate not in the permissible range

What it means

A07557 is raised when, while the encoder is being adjusted, the reference point coordinate that arrives through connector input CI:p2599 lies outside half of the encoder range. A value of this size cannot be adopted as the actual axis position. The largest value still permitted is shown in the supplementary information of the message. Depending on the drive's configuration, the same condition can also be issued as a fault, F07557.

Why it appears

  • The reference point coordinate received via connector input CI:p2599 during encoder adjustment lies outside half of the encoder range and therefore cannot be set as the actual axis position. The maximum permissible value is displayed in the supplementary information.

What to check

  1. Read the maximum permissible value from the supplementary information of the message.
  2. Set the reference point coordinate to a value less than that maximum — this is the value that arrives through connector input CI:p2599 (the EPOS reference point coordinate value, p2599).
  3. If the coordinate is fed from another signal, check the signal source selected in p2598, which supplies the reference point coordinate.

Parameters the manual names

  • p2599 — CO: EPOS reference point coordinate value; the parameter that carries the reference point coordinate being checked and that must be set below the maximum shown in the supplementary information.
  • p2598 — CI: EPOS reference point coordinate signal source; selects the signal source that supplies the reference point coordinate, and the place the manual points to when the coordinate has to be changed.

Acknowledging and restarting

As an alarm, A07557 needs no acknowledgement and the drive takes no automatic action. If the drive is configured to issue the same condition as a fault, F07557, the manual states: Reaction upon F: OFF1 (OFF2, OFF3) Acknowl. upon F: IMMEDIATELY — the fault must then be acknowledged IMMEDIATELY before the drive can be restarted.

The same on every family

Every manual that describes A07557 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEApplication/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2845
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1579

The drives this code lives on

A07557 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does A07557 on a SINAMICS drive mean?

During encoder adjustment, the reference point coordinate that arrives via connector input CI:p2599 lies outside half of the encoder range, so the drive cannot set it as the actual axis position. The largest permitted value is shown in the message's supplementary information.

How do I clear A07557?

Read the maximum permissible value from the supplementary information and set the reference point coordinate (p2599, supplied via the source selected in p2598) to a value less than that maximum.

Does A07557 have to be acknowledged?

No — as an alarm it requires no acknowledgement and the drive takes no automatic action. If the drive is configured to issue the condition as fault F07557 instead, it must be acknowledged IMMEDIATELY (reaction upon F: OFF1, OFF2, OFF3).

Which parameter holds the reference point coordinate?

p2599 is the EPOS reference point coordinate value that is checked, and p2598 selects the signal source that supplies it.