Alarm · SINAMICS S120, S150

A07091Drive: determined current controller dynamic response invalid

What it means

A07091 is issued when the current-controller measurement belonging to one button tuning has finished with a poor result. One button tuning is activated with p5300 = 1, and the drive then measures the current controller after the pulses have been enabled. If the evaluation finds that the current control loop was not appropriately set, the drive raises this alarm and writes an alarm value to r2124 that tells whether the dynamic response came out too low or the current controller came out unstable. PRBS — Pseudo Random Binary Signal (binary noise) — is the test signal of this measurement; its amplitude is set in p5296, and an amplitude set too high is one of the possible triggers.

Why it appears

  • The current controller is set incorrectly.
  • The PRBS amplitude in p5296 is set too high.

What to check

  1. Read the alarm value in r2124 (interpret hexadecimal) to see whether the dynamic response was evaluated as too low or the current controller as unstable.
  2. Repeat the measurement with a smaller excitation amplitude: reduce p5296 and run one button tuning again with p5300 = 1.
  3. If required, adapt the current controller proportional gain in p1715.

Reading the message value

The drive stores an alarm value for this message in r2124; the manual says to interpret it hexadecimal. The value distinguishes the two evaluation findings:

  • 1: Dynamic response too low.
  • 2: Current controller unstable.

Parameters the manual names

  • p5300 (Autotuning selection): set to 1 to activate one button tuning; this starts the current controller measurement after the pulses have been enabled. Activate it again to repeat the measurement.
  • p5296 (FFT tuning PRBS amplitude): the excitation amplitude of the PRBS test signal — reduce it when the measurement has to be repeated after this alarm.
  • r2124 (Alarm value): holds this alarm's alarm value, read hexadecimal — 1 dynamic response too low, 2 current controller unstable.
  • p1715 (Force controller P gain): the current controller proportional gain, which you adapt if required when the evaluation fails.

Acknowledging and restarting

The manuals specify no acknowledgement procedure for this alarm. It is resolved through the remedy itself: adjust p5296 and/or p1715 as required and repeat the measurement by activating one button tuning again (p5300 = 1). Once an evaluation finds the current control loop appropriately set, the condition that raises A07091 is gone.

The same on every family

Every manual that describes A07091 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)Control Unit (CU)SINAMICS S120, S150 List Manual · p. 2785

The drives this code lives on

A07091 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07091 mean on SINAMICS S120?

It means the current-controller measurement that runs during one button tuning (p5300 = 1) evaluated the current control loop as not appropriately set. Alarm value 1 in r2124 means the dynamic response was too low, alarm value 2 means the current controller was unstable.

How do I fix A07091?

Repeat the measurement with a smaller excitation amplitude in p5296 and, if required, adapt the current controller proportional gain in p1715. Then run one button tuning again with p5300 = 1.

What is the PRBS amplitude p5296?

It is the amplitude of the Pseudo Random Binary Signal (binary noise) with which the current controller measurement is excited. If it is set too high, the evaluation fails and A07091 follows.

Does A07091 have to be acknowledged?

The manuals specify no acknowledgement for this alarm. The fix is to correct p5296 and/or p1715 and repeat the measurement.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.