Alarm · SINAMICS G130, G150, S120, S150

A02005Function generator: Drive does not exist

What it means

A02005 comes from the function generator (FG). The function generator is tied to another drive object of the converter by number: the function generator drive number in p4815 specifies which drive object it connects to and works with. The drive raises this alarm when that drive object does not exist, i.e. no drive object with the number entered for the connection is present in the converter. It is a parameterization/configuration message, so the cure lies in the setup, not in replacing hardware.

Why it appears

  • The drive object that the function generator is set to connect to does not exist — the drive object number stored for this connection (p4815, function generator drive number) does not match any drive object actually present.

What to check

  1. Read out p4815 (function generator drive number) to see which drive object number the function generator uses for its connection.
  2. Compare this number with the drive objects that actually exist in the converter configuration.
  3. Enter the number of an existing drive object in p4815, so that the function generator connects to a drive object that is present.
  4. Restart the function generator once the number has been corrected.

Parameters the manual names

  • p4815 (function generator drive number / FG drive number) — holds the number of the drive object the function generator connects to; correct it here so that it points to a drive object that actually exists.

Acknowledging and restarting

The alarm resets itself once its cause has been removed: correct p4815 so that it refers to an existing drive object, then restart the function generator. No acknowledgement of its own is needed for this alarm — removing the cause and restarting the function generator is enough.

What differs between the drive families

Straight from the manuals' own fields — A02005 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1499
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2724

The drives this code lives on

A02005 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A02005 mean on a SINAMICS converter?

It comes from the function generator: the drive object that the function generator is set to connect to does not exist. The drive object number for this connection is stored in p4815.

How do I clear alarm A02005?

Enter the number of a drive object that actually exists in p4815 (function generator drive number) and then restart the function generator. The alarm resets as soon as the cause is removed and the function generator is restarted.

Does A02005 trip the drive?

No automatic reaction is triggered by this alarm; it only signals that the function generator connection points to a drive object that does not exist.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.