AI helper
Describe the task — I'll match 3 WIKA models in 30 seconds
GDM-RC-100-T 1
GDM-RC-100-T
On order
WIKA · SF6 gas solutions · Family GDM

Hybrid gas density monitor with reference chamber

With Modbus ® interface or analogue 4 ... 20 mA signal
Range
0…12.5 bar
Output
Modbus RTU · 4 ... 20 mA
Protection
IP67
RoHS
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

Gas density is a crucial operating parameter for high-voltage switchgear. If the required gas density is not present, safe operation of the plant cannot be guaranteed.

The WIKA gas density measuring instruments provide reliable warnings against dangerously low gas levels, even under extreme ambient conditions. If the gas density drops as a result of a leakage, the switch contacts will switch. In addition to the traditional gas density monitor, with the model GDM-RC-100-T high-precision sensing technology and evaluation electronics are incorporated.

Via the on-site indication, the pressure based on 20 °C [68 °F] can be read directly on the instrument. With the integrated switch contacts, simple switching tasks can be realised quickly and without complication. The integrated or attached Modbus ® interface or 4 ... 20 mA sensing technology enable remote monitoring of the plant.

Special features

  • Ideally suited for smart grid or modernisation projects
  • Modbus ® delivers measured values for pressure, temperature and gas density as a digital signal
  • The 4 ... 20 mA version outputs the absolute pressure at 20 °C [68 °F] or the gas density in g/l as an analogue signal
  • Suitable for SF<sub>6</sub> and alternative insulating gases
  • Complete on-site indication of the density and vacuum range on a 100 mm [3.94 in] dial
Identification
ModelGDM-RC-100-T
Product familyGDM
SubcategoryHybrid gas density monitor with reference chamber
Measuring range
Pressure ranges0…10 bar · 0…12.5 bar
Density reference temperature20 °C
Process conditions
Process connectionG1/2 B
Electrical characteristics
Output signalModbus RTU · 4 ... 20 mA
Switching contacts4
Materials
Wetted parts materialStainless steel
Operating environment
Ambient temperature−40…+80 °C
IP ratingIP67
Certifications and approvals
CertificationsRoHS
Additional details
Temperature compensationYes
Tables from datasheet
Basic information
Measurement principleReference gas measurement
Nominal size of the optical indication100 mm[3.94 in]
Self-indication in case of malfunctionIntegrated into the instrument, the switch contact is actuated in case of leakage in the reference chamber
Measuring element
Type of measuring elementBellows measuring system with reference chamber, piezo pressure sensor with temperature compensation
Accuracy specifications
Switching accuracy Calibration pressure established by means of reference isochore, generated by Prof. Bier
-1 ...+5 bar at 20 °C [-14.50 ... +72.51 psi at 68 °F]±70 mbar [±1.01 psi] at calibration pressure at 20 °C [68 °F], gaseous phase ±100 mbar [±1.45 psi] at calibration pressure at -30 ...+50 °C [-22 ...+122 °F], gaseous phase
-1 ...+9 bar at 20 °C [-14.50 ... +130.53 psi at 68 °F]±100 mbar [±1.45 psi] at calibration pressure at 20 °C [68 °F], gaseous phase ±150 mbar [±2.17 psi] at calibration pressure at -30 ...+50 °C [-22 ...+122 °F], gaseous phase
-1 ... +11.5 bar at 20 °C [-14.50 ... +166.79 psi at 68 °F]±150 mbar [±2.17 psi] at calibration pressure at 20 °C [68 °F], gaseous phase ±200 mbar [±2.90 psi] at calibration pressure at -30 ...+50 °C [-22 ...+122 °F], gaseous phase
Calibration pressureFirst switch point below filling pressure
Indication accuracy
-1 ...+5 bar at 20 °C [-14.50 ... +72.51 psi at 68 °F]±70 mbar [±1.01 psi] at calibration pressure at 20 °C [68 °F], gaseous phase ±100 mbar [±1.45 psi] at calibration pressure at -30 ...+50 °C [-22 ...+122 °F], gaseous phase
-1 ...+9 bar at 20 °C [-14.50 ... +130.53 psi at 68 °F]±100 mbar [±1.45 psi] at calibration pressure at 20 °C [68 °F], gaseous phase ±150 mbar [±2.17 psi] at calibration pressure at -30 ...+50 °C [-22 ...+122 °F], gaseous phase
-1 ... +11.5 bar at 20 °C [-14.50 ... +166.79 psi at 68 °F]±150 mbar [±2.17 psi] at calibration pressure at 20 °C [68 °F], gaseous phase ±200 mbar [±2.90 psi] at calibration pressure at -30 ...+50 °C [-22 ...+122 °F], gaseous phase
Switch hysteresisMeasuring rangeHysteresis level
-1 ...+5 bar at 20 °C [-14.50 ... +72.51 psi at 68 °F]Typically < 90 mbar[< 1.30 psi] 1)
-1 ... +7.5 bar at 20 °C [-14.50 ... +108.77 psi at 68 °F]Typically < 150 mbar[< 2.17 psi] 1)
-1 ... +11.5 bar at 20 °C [-14.50 ... +166.79 psi at 68 °F]Typically < 220 mbar[< 3.19 psi] 1)
Lower switch hysteresis on request
Measuring range
Measuring range■ 0 ... 10 bar abs. at 20 °C [0 ... 145.03 psi abs. at 68 °F] SF₆ gas ■ 0 ... 12.5 bar abs. at 20 °C [0 ... 181.29 psi abs. at 68 °F] SF₆ gas
Maximum overpressure1.43 times the measuring range
Minimum bursting strength30 bar [435.11 psi]
Dial
Scale rangeEnd of measuring range1.3 bar or 1.8 bar [18.85 psi or 26.10 psi] above the first switch point and below the filling pressure
Scale graduation■ Single scale (divided into sections of different colours) ■ Double scale (divided into sections of different colours) ■ Triple scale (divided into sections of different colours)
MaterialAluminium
View all (20)
Process connection
StandardEN 837
Thread sizeG1/2 B
ConnectionAxial or radial
Spanner flats22 mm[0.86 in]
MaterialStainless steel
Switch contacts
Switch modelPotential-free change-over contact
Number of switches■ 1 x switch contact ■ 2 x switch contact ■ 3 x switch contact ■ 4 x switch contact Up to four switch contacts possible as change-over contacts
Switching functionChange-over contact
Switching direction■ Falling density ■ Rising density
Switch point settingIn accordance with customer specification, max. difference of lowest to highest contact: 4 bar [58.01 psi]
Maximum switching cycles10,000 mechanical and electrical
Insulation resistance of contact> 100MΩ
Min. switching current10mA
Min. switching voltage12V
CircuitsGalvanically isolated
Monitoring functions
Self-monitoringIntegrated into the instrument, the switch contact is actuated in case of leakage in the reference chamber
Electrical characteristics
Auxiliary power [V]Resistive load [A]Inductive load [A]
≤ DC 305 1)3 1)
≤ DC 5011
≤ DC 750.750.75
≤ DC 1250.50.03
≤ DC 2500.250.03
≤ AC 1255 1)2 1)
≤ AC 2505 1)2 1)
Electrical connection
Connection type12-pin TTI plug-in terminal
Wire cross-section■ Min.0.25mm 2 ■ Max.2.5mm 2
GroundingIn cable socket
Material
Material (wetted)
Reference chamber (pressure element)Stainless steel, filled with reference gas
Process connectionStainless steel
Material (in contact with the environment)
Case and coverAluminium die-casting, powder-coated
Cable gland of the switch contacts→ For cable glands, see &#x27;Versions of cable glands for model GDM-RC-100-T with integrated gas density sensor&#x27;
MovementBrass
PointerAluminium, black
WindowLaminated safety glass
DialAluminium
Operating conditions
Place of useIndoor/Outdoor
AltitudeUp to 2,000 m[6,562 ft] above sea level
Medium temperature range-40 ...+80 °C [-40 ...+176 °F], gaseous phase
Operating temperature-40 ...+80 °C [-40 ...+176 °F], gaseous phase
Ambient temperature range-40 ...+80 °C [-40 ...+176 °F], gaseous phase
Storage temperature-40 ...+70 °C [-58 ...+158 °F]
Humidity≤ 95 %relative humidity
CondensationNon-condensing Compensating diaphragm against condensation
Helium leak test≤ 1 x 10 -8 mbar x l/s
Vibration resistance4g at 50 mbar [0.72 psi] distance from the switch point, no contact bounce (20 ...80 Hz)
Shock resistance■ 50g / 11 ms, no contact bounce with 200 mbar [2.90 psi] distance from the switch point ■ 150g without damage
Ingress protection of the complete instrument■ IP65, IP67 for versions with integrated gas density sensor ■ IP67 for versions with attached gas density sensor
Permissible pollution degree2 (per EN 61010-1)
Weight in kgOn request (depending on configuration)
Packaging and instrument labelling
Product labelLasered onto the reference chamber, highest weather resistance
Dielectric strength test
Electric strength■ 2 kV pin on grounding (case) ■ 2 kV pin on pin (switch contact to switch contact) ■ 1 kV pin on pin within the switch contact - 1 minute
Compensated pressure range in bar abs. at 20 °C [psi abs. at 68 °F] (g/l SF₆)Pressure in bar abs. [psi abs.]TemperatureOutput parametersOutput signal
0 …2(12.28) [0 ... 29.00]0 …2.4 [0 ... 34.80]-40 …+80 °C [-40 ...+176 °F]■ Density ■ Pressure at 20 °C [68 °F] ■ Pressure ■ TemperatureModbus ® RTU
0 …3(18.65) [0 ... 43.51]0 …3.7 [0 ... 53.66]
0 ... 6 (38.87) [0 ... 87.02]0 ... 7.5 [0 ... 108.77]
0 …8(53.4) [0 ... 116.03]0 …10.1 [0 ... 146.48]
0 …10(68.96) [0 ... 145.03]0 …12.9 [0 ... 187.09]
0 …12(85.79) [0 ... 174.04]0 …15.7 [0 ... 227.70]
0 …16(124.64) [0 ... 232.06]0 …21.3 [0 ... 308.93]
Accuracy specifications
Accuracy 1)
Compensated pressure ranges in bar abs. at 20 °C [psi abs. at 68 °F] (g/l SF₆) 0 …2(12.28) [0 ... 29.00] 0 …3(18.65) [0 ... 43.51] 0 ... 6 (38.87) [0 ... 87.02]For -40 ... -20 °C [-40 ... -4 °F] For -20 ...+80 °C [-4 ...+176 °F]■ ±2% ■ ±1.5% ■ ±1.25% ■ ±0.75%
Accuracy specifications
Compensated pressure ranges in bar abs. at 20 °C [psi abs. at 68 °F] (g/l SF₆) 0 …8(53.4) [0 ... 116.03] 0 …10(68.96) [0 ... 145.03] 0 …12(85.79) [0 ... 174.04] 0 …16(124.64) [0 ... 232.06]For -40 ...+80 °C [-40 ...+176 °F]■ ±1.25% ■ ±0.6%
Pressure accuracy■ ±1 %at 20 °C [68 °F] ■ ±0.2 %at 20 °C [68 °F]
Temperature accuracy±1.5 K
Reference conditionsPer IEC 61298-1
Compensated pressure range in bar abs. at 20 °C [psi abs. at 68 °F] (g/l SF₆)Accuracy 1)Output parametersOutput signal
0 …2(12.28) [0 ... 29.00]■ ±2% ■ ±1.5%Absolute pressure at 20 °C [68 °F]4 ...20mA
0 …3(18.65) [0 ... 43.51]
0 ... 6 (38.87) [0 ... 87.02]
0 …8(53.4) [0 ... 116.03]
0 …10(68.96) [0 ... 145.03]
0 …12(85.79) [0 ... 174.04]
0 …16(124.64) [0 ... 232.06]
Density range in g/l SF 6 (compensated pressure range in bar abs. at 20 °C [psi abs. at 68 °F])Accuracy 1)Output parametersOutput signal
0 …10(1.64) [0 ... 145.03]■ ±2% ■ ±1.5%SF₆ gas density in g/l4 ...20mA
0 …16(2.59) [0 ... 232.06]
0 ... 25 (3.97) [0 ... 362.59]
0 …40(6.16) [0 ... 580.15]
0 …60(8.87) [0 ... 870.22]
0 …80(11.33) [0 ... 1,160.3]
Compensated pressure range in bar abs. at 20 °C [psi abs. at 68 °F] (g/l SF₆)Overload safety in bar abs. [psi abs.]Burst pressure in bar abs. [psi abs.]
0 ... 2 (12.28) [0 ... 29.00]6.2 [89.92]10 [145.03]
0 ... 3 (18.65) [0 ... 43.51]14.5 [210.30]24 [348.09]
0 ... 6 (38.87) [0 ... 87.02]14.5 [210.30]24 [348.09]
0 ... 8 (53.4) [0 ... 116.03]31 [449.61]52 [754.19]
0 ... 10 (68.96) [0 ... 145.03]31 [449.61]52 [754.19]
0 ... 12 (85.79) [0 ... 174.04]31 [449.61]52 [754.19]
0 ... 16 (124.64) [0 ... 232.06]62 [899.23]103 [1,493.89]
Case
Case material316L
Case options■ Cable outlet ■ Metal cable outlet, shield optionally connected (heavy-duty version)
Name in accordance with IUPAC 2) nomenclatureAbbreviationDescription (CAS no.)
Sulphur hexafluorideSF 62551-62-4
NitrogenN 27727-37-9
TetrafluoromethaneCF 475-73-0
Oxygen 3)O 27782-44-7
Carbon dioxideCO 2124-38-9
2,3,3,3-Tetrafluoro-2-(trifluoromethyl)propanenitrile 4)C4-FN (fluoronitrile)42532-60-5
HeliumHe7440-59-7
ArgonAr7440-37-1