On the display
The control panel shows Warning - Condenser - High small temperature difference. The manuals print this wording for the message, and it is the only variant given. The manual describes it as a manual reset warning.
What it means
This warning is set when the condenser small temperature difference is greater than the condenser small temperature difference warning threshold. The threshold is a service programmable setpoint on the maintenance screen, and its default value is 8.0°F (4.4°C). One manual also prints the default as 6.0°F (3.3°C) and records that it was changed to 8.0°F (4.4°C). When the message appears, the condenser small temperature difference has exceeded this setpoint.
Why it appears
- The condenser small temperature difference is greater than the condenser small temperature difference warning threshold — a service programmable setpoint on the maintenance screen with a default of 8.0°F.
What to check
- Open the maintenance screen and read the condenser small temperature difference warning threshold, which is set there as a service programmable setpoint.
- Compare the current condenser small temperature difference with that threshold: the warning is set while the difference is greater than the threshold, and the reset becomes possible once the difference is less than or equal to the threshold.
Setpoints and thresholds
- Condenser small temperature difference warning threshold — service programmable setpoint on the maintenance screen.
- Default value: 8.0°F (4.4°C). One manual also prints the default as 6.0°F (3.3°C) before it was changed to 8.0°F (4.4°C).
Reset and restart
This warning is reset manually. The manual states: reset when the condenser small temperature difference is less than or equal to the condenser small temperature difference warning threshold, the Maintenance Acknowledge key is pressed, Cond High Small Temp Diff is selected, and the code 0726 entered
. The reset therefore requires Cond High Small Temp Diff to be selected, the Maintenance Acknowledge key to be pressed and the code 0726 to be entered, and it is only possible while the condenser small temperature difference is at or below the threshold.
Questions engineers ask
How do I reset the YORK YK 'Warning - Condenser - High small temperature difference'?
Select Cond High Small Temp Diff, press the Maintenance Acknowledge key and enter the code 0726. The reset only works when the condenser small temperature difference is less than or equal to the warning threshold on the maintenance screen.
What is the condenser small temperature difference warning threshold on a YORK YK?
It is a service programmable setpoint on the maintenance screen. The default is 8.0°F (4.4°C); one manual also prints an earlier default of 6.0°F (3.3°C) that was changed to 8.0°F (4.4°C).
Why does my YORK YK show 'Warning - Condenser - High small temperature difference'?
The warning is set when the condenser small temperature difference is greater than the condenser small temperature difference warning threshold. That is the only cause the manual gives for this message.
Messages next to this one
Source
Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from:
All YORK YK messages: fault codes · YORK YK documentation · YORK manuals