Safety shutdown · YORK YK · Water-cooled centrifugal chiller

YORK YKMotor - Cooling coil leak

On the display

The panel shows Motor - Cooling coil leak. This exact wording is the only form the manuals print for this message, and it belongs to the chiller's safety fault messages — a message of this kind means the unit has carried out a safety shutdown.

What it means

The motor cooling coil leak detector has registered a fault condition for at least 3 s continuously. Which sensor input produced the trip depends on the type of sensor the motor cooling coil leak protection setpoint enables: with an optical sensor, the input to the motor monitoring board goes high to indicate a leak; with a float switch, the input goes low to indicate a leak. The manual classifies this trip as a safety shutdown.

Why it appears

  • The motor cooling coil leak detector registered a fault condition continuously for at least 3 s.
  • With an optical sensor, the input to the motor monitoring board goes high to indicate a leak.
  • With a float switch, the input goes low to indicate a leak.

Setpoints and thresholds

  • The motor cooling coil leak protection setpoint enables the type of sensor employed — an optical sensor or a float switch.
  • When the motor cooling coil leak protection setpoint is set to disabled, this safety shutdown does not occur.

Reset and restart

The chiller can be started again only once the leak sensor no longer indicates a leak and the event has been cleared from the display. The two manuals for this model describe the clearing action differently: one instructs to press the CLEAR FAULT key on the display, the other to press the Clear button next to the listed event on the Systems Details Screen. Once the sensor no longer indicates a leak and the event has been cleared in either of these ways, the chiller can be started.

Questions engineers ask

What does 'Motor - Cooling coil leak' mean on a York YK chiller?

The motor cooling coil leak detector has registered a fault condition for at least 3 s continuously, which trips this safety shutdown. With an optical sensor the input to the motor monitoring board goes high to indicate a leak; with a float switch the input goes low.

How do I clear the Motor - Cooling coil leak fault on a York YK?

First the leak sensor must no longer indicate a leak. Then press the Clear button next to the listed event on the Systems Details Screen — the other manual for this model describes pressing the CLEAR FAULT key on the display — after which the chiller can be started.

Does this York YK trip appear if the motor cooling coil leak protection setpoint is disabled?

No. The manual states this safety shutdown does not occur when the motor cooling coil leak protection setpoint is set to disabled; the same setpoint enables the type of sensor employed.

Messages next to this one

Source

Written from the manufacturer's manuals for the YORK YK; every number and designation on this page is checked against them before publication. The row of the manual this message comes from: