What it means
F49200 means that the excitation sequence control has signalled a fault. In the conditions the manual lists, an expected feedback signal from the excitation was not received within the monitoring time, or the excitation group signal fault is present directly. Which of these applies is stored bit by bit in the fault value r0949. The signal can also be generated via p6500[59]. Both list manuals that carry this code describe it identically; they differ only in whether the fault value is to be interpreted hexadecimal or binary.
Why it appears
- The excitation sequence control signals a fault: a feedback signal expected from the excitation was not received within the monitoring time, the excitation group signal fault is present, or the switch-on command for the excitation was reset although pulse enable is still available or the excitation current actual value has not yet fallen below a minimum value.
- The signal can also be generated via p6500[59].
What to check
- Check the excitation.
- Check the commands, feedback signals and BICO interconnections.
- If bit 4 of the fault value is set, increase the switch-off delay time p1647.
Reading the message value
The drive writes the fault value into r0949. The G130/G150 manual asks to interpret the value hexadecimal, the S120/S150 manual binary; the bit assignment is the same:
- Bit 0: When switched off or when switching off the excitation, the signal "excitation ready feedback signal" was not received within the monitoring time.
- Bit 1: After an ON command, the signal "excitation ready feedback signal" was not received within the monitoring time.
- Bit 2: After the pulses were enabled, the signal "excitation operational feedback signal" was not received within the monitoring time.
- Bit 3: The "excitation group signal fault" signal is present.
- Bit 4: The switch-on command for the excitation was reset, although pulse enable (r0899.11) is still available, or the excitation current actual value has still not fallen below a minimum value.
Parameters the manual names
- r0949 — fault value: read it after the fault to see which bit, and therefore which excitation condition, triggered F49200.
- p1647 — excitation switch-off delay time: increase it when bit 4 is set, as the remedy for this fault specifies.
Acknowledging and restarting
The drive coasts down and must be acknowledged before it will start. Acknowledge the fault immediately once the cause has been remedied.
What differs between the drive families
Straight from the manuals' own fields — F49200 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | OFF2 | IMMEDIATELY | General drive fault (19) | None | SINAMICS G130, G150 List Manual · p. 1934 |
| S120, S150 | — | — | General drive fault (19) | None | SINAMICS S120, S150 List Manual · p. 3290 |
The drives this code lives on
F49200 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F49200 in SINAMICS mean?
It means the excitation sequence control has signalled a fault — usually an excitation feedback signal that was not received within the monitoring time. The exact condition is stored bit by bit in the fault value r0949.
How do I clear fault F49200?
Check the excitation and check the commands, feedback signals and BICO interconnections. If bit 4 is set, increase the switch-off delay time p1647, then acknowledge the fault immediately.
Which bit in r0949 belongs to which F49200 condition?
Bits 0 and 1 mean the excitation ready feedback signal was missing — when switching off or after an ON command — bit 2 the excitation operational feedback signal after pulse enable, and bit 3 the excitation group signal fault itself. Bit 4 means the switch-on command for the excitation was reset although pulse enable (r0899.11) is still available or the excitation current actual value has not yet fallen below a minimum value.
Can F49200 be generated deliberately?
Yes — the manual notes that this signal can be generated via p6500[59].