SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS G130, G150, S120, S150

F49152Cooling unit: ON command feedback signal missing

What it means

F49152 is raised when the feedback signal confirming the ON command of the cooling unit is missing. The drive issues the ON command to the cooling unit and waits for the feedback signal; if it does not arrive within the starting time set in p0260, the drive trips. The same fault is raised if the feedback was present at switch-on but fails while the cooling unit is running.

Why it appears

  • After the ON command was issued, the feedback signal was not received within the starting time selected in p0260.
  • The feedback signal failed in operation.
  • The cooling unit was stopped by an external signal.

What to check

  1. Check the wiring between the cooling unit and the input terminal (Terminal Module).
  2. Check the wiring between the output terminal (Terminal Module) and the cooling unit.
  3. Check the external control device for the cooling unit.

Parameters the manual names

  • p0260 (Cooling unit starting time 1, RKA start time 1) — the window after the ON command in which the cooling unit feedback must arrive; if the feedback is not received within this time, the drive raises F49152.

Acknowledging and restarting

On this fault the drive coasts down (OFF2) and the fault must be acknowledged immediately — the drive will not start again until it has been acknowledged. Eliminate the cause first, then acknowledge the fault and restart the drive.

The same on every family

Every manual that describes F49152 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYAuxiliary unit faulted (20)NoneSINAMICS S120, S150 List Manual · p. 3288
G130, G150OFF2IMMEDIATELYAuxiliary unit faulted (20)NoneSINAMICS G130, G150 List Manual · p. 1931

The drives this code lives on

F49152 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F49152 mean on a SINAMICS drive?

The drive switched its cooling unit on, but the feedback signal confirming the ON command is missing. Either the feedback did not arrive within the starting time set in p0260, or it failed while the cooling unit was running.

Which parameter belongs to F49152?

p0260, the cooling unit starting time (RKA start time 1). If the ON command feedback is not received within this time, the drive raises F49152.

How do I fix fault F49152?

Check the wiring between the cooling unit and the input and output terminals of the Terminal Module, and check the external control device for the cooling unit. Then acknowledge the fault immediately and restart the drive.

Why did my drive trip F49152 even though the cooling unit was working before?

The fault also comes when the feedback signal fails in operation, or when the cooling unit was stopped by an external signal.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F49xxx group · SINAMICS manuals · Siemens manuals