Fault · SINAMICS G130, G150, S120, S150

F49156Cooling unit: Cooling liquid temperature has exceeded the fault threshold

What it means

SINAMICS raises F49156 when the temperature of the cooling liquid at the intake of the power unit has exceeded the fault threshold that applies to that unit. The threshold is not a universal figure: it is taken from the power unit's hardware description data and is, for example, 52 ... 55 °C. The manuals that describe this code for the G130/G150 and for the S120/S150 describe it in the same words, so the explanation below applies across those families.

Why it appears

  • The temperature of the cooling liquid at the intake has exceeded the fault threshold specified for the power unit.

What to check

  1. Check the cooling system.
  2. Check the ambient conditions.

Acknowledging and restarting

The drive coasts down (OFF2) when this fault trips and will not restart until the fault has been acknowledged. Once the cooling problem has been remedied, acknowledge the fault immediately and restart the drive in the normal way. The manual defines no additional reset or power-up procedure for this code.

The same on every family

Every manual that describes F49156 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYAuxiliary unit faulted (20)NoneSINAMICS S120, S150 List Manual · p. 3289
G130, G150OFF2IMMEDIATELYAuxiliary unit faulted (20)NoneSINAMICS G130, G150 List Manual · p. 1932

The drives this code lives on

F49156 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F49156 mean?

It reports that the cooling liquid intake temperature has exceeded the fault threshold specified for the power unit. The drive coasts down (OFF2) when the fault trips.

At what cooling liquid temperature does F49156 trigger?

The threshold depends on the power unit and is stored in its hardware description data. As an example, the manuals give 52 ... 55 °C.

How do I fix and reset fault F49156?

Check the cooling system and the ambient conditions. Once the cause has been remedied, acknowledge the fault immediately — the drive will not restart until it has been acknowledged.

Which SINAMICS drives can report F49156?

The code is described for SINAMICS G130, G150, S120 and S150. Other cooling-unit conditions of the same cooling unit are reported under their own codes, such as F49150 to F49155.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.