What it means
The drive raises fault F36895, titled “Hub DRIVE-CLiQ (CU): Alternating cyclic data transfer error”, when it detects a DRIVE-CLiQ communication error on the path from the DRIVE-CLiQ Hub Module in question to the Control Unit. The cause recorded in this case is fault cause 11 (= 0B hex): a synchronization error during alternating cyclic data transfer. The message entry itself names the component number and the fault cause, so the entry identifies which Hub Module reported the error and why. The G130/G150 and S120/S150 list manuals describe this fault identically.
Why it appears
- A DRIVE-CLiQ communication error has occurred from the DRIVE-CLiQ Hub Module in question to the Control Unit.
- The recorded fault cause is 11 (= 0B hex): a synchronization error occurred during alternating cyclic data transfer.
What to check
- Carry out a POWER ON as the remedy in the manual states; no further checks or actions are described for this fault.
- Note the cross-reference in the remedy to p9915, the DRIVE-CLiQ data transfer error shutdown threshold master.
Reading the message value
- The message value contains two items: the component number and the fault cause.
- The manual codes this information in the message value (r0949/r2124) as
0000yyxx hex: yy = component number, xx = error cause
. - For F36895 the error-cause portion carries 11, the synchronization error during alternating cyclic data transfer.
Parameters the manual names
- r0949 (fault value): holds the message value of this fault, coded 0000yyxx hex, so the component number and fault cause of the Hub DRIVE-CLiQ error can be read from it.
- r2124 (alarm value): named by the manual next to r0949 as the place where the coded message value of this entry is stored.
- p9915 (DRIVE-CLiQ data transfer error shutdown threshold master, DQ fault master): the parameter the remedy of this fault cross-refers to.
Acknowledging and restarting
Acknowledge the fault immediately. The only remedy the manual gives is Carry out a POWER ON.
No further acknowledgment or restart steps are described for this fault.
The same on every family
Every manual that describes F36895 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | IMMEDIATELY | Internal (DRIVE-CLiQ) communication error (12) | Terminal Board (TB) | SINAMICS S120, S150 List Manual · p. 3258 |
| G130, G150 | NONE | IMMEDIATELY | Internal (DRIVE-CLiQ) communication error (12) | Terminal Board (TB) | SINAMICS G130, G150 List Manual · p. 1920 |
The drives this code lives on
F36895 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS fault F36895 mean?
It reports a DRIVE-CLiQ communication error from the DRIVE-CLiQ Hub Module in question to the Control Unit. The recorded fault cause is 11 (= 0B hex), a synchronization error during alternating cyclic data transfer.
How do I clear fault F36895?
Acknowledge the fault immediately and carry out a POWER ON. The manuals give no further remedy for this fault.
What is stored in the message value of F36895?
The component number and the fault cause, coded in r0949/r2124 as 0000yyxx hex, where yy is the component number and xx is the error cause.
Which parameter belongs to fault F36895?
The remedy cross-refers to p9915, the DRIVE-CLiQ data transfer error shutdown threshold master. The coded message value itself is read in r0949 and r2124.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F36xxx group · SINAMICS manuals · Siemens manuals
