What it means
F35886 is raised when a DRIVE-CLiQ communication error occurs from the involved Terminal Module (TM) to the Control Unit, so that data were not able to be sent. The list manuals for the G130, G150, S120 and S150 describe this code identically and give a single fault cause for it: 65 (= 41 hex), telegram type does not match the send list. The message value tells you which Terminal Module reported the error.
Why it appears
- A DRIVE-CLiQ communication error occurred from the Terminal Module (TM) involved to the Control Unit, and the data were not able to be sent.
- The fault cause entered in the message value is 65 (= 41 hex): the telegram type does not match the send list.
What to check
- Read the message value in r0949: the byte pair yy gives the component number, so you know which Terminal Module is involved; the fault cause appears in xx (here 41 hex, i.e. cause 65).
- The remedy in the manuals is a single step:
Carry out a POWER ON
.
Reading the message value
- Message value: Component number: %1, fault cause: %2.
- Coding in r0949/r2124: 0000yyxx hex, where yy = component number and xx = error cause.
- Fault cause 65 (= 41 hex): Telegram type does not match send list.
Parameters the manual names
- r0949 (fault value) — holds the message value of F35886 coded 0000yyxx hex; yy identifies the component number of the Terminal Module involved, xx the fault cause (65 here).
- r2124 (alarm value) — named by the manuals next to r0949 for this code; the same 0000yyxx hex coding of the message value applies.
Acknowledging and restarting
Acknowledge the fault IMMEDIATELY, as the manuals require, and carry out a POWER ON. If F35886 reappears after the POWER ON, the telegram type still does not match the send list of the Terminal Module identified in the message value.
The same on every family
Every manual that describes F35886 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF1 (OFF2) | IMMEDIATELY | Internal (DRIVE-CLiQ) communication error (12) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3239 |
| G130, G150 | OFF1 (OFF2) | IMMEDIATELY | Internal (DRIVE-CLiQ) communication error (12) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1901 |
The drives this code lives on
F35886 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F35886 mean on a SINAMICS drive?
It reports a DRIVE-CLiQ communication error from the involved Terminal Module (TM) to the Control Unit: the data could not be sent. The only fault cause given is 65 (= 41 hex), telegram type does not match the send list.
How do I clear fault F35886?
The manuals give one remedy: carry out a POWER ON, and acknowledge the fault IMMEDIATELY. The message value in r0949 (coded 0000yyxx hex) tells you which Terminal Module was involved.
What does fault cause 65 mean for F35886?
65 (= 41 hex) means the telegram type does not match the send list. It sits in the low byte xx of the message value; the high byte yy holds the component number of the Terminal Module.
Is F35886 the same on G130, G150, S120 and S150?
Yes, the list manuals describe this code identically for the Terminal Module component, with the same fault cause and the same POWER ON remedy.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.