Fault · SINAMICS G120, G120XA, G130, G150, S120, S150

F30080Power unit: Current increasing too quickly

What it means

F30080 is raised by the Power Module when the current in the power unit rises too quickly: The power unit has detected an excessive rate of rise in the overvoltage range. The drive switches off immediately and the motor coasts down. Before the drive can run again, the cause must be removed and the fault acknowledged.

Why it appears

  • The closed-loop control is parameterized incorrectly.
  • The motor has a short-circuit or a fault to ground (frame).
  • In U/f operation, the up ramp is set too low.
  • In U/f operation, the rated current of the motor is much greater than that of the power unit.
  • On an infeed: high discharge and post-charging currents after a line voltage dip.
  • On an infeed: high post-charging currents when motoring with an overloaded motor and a DC link voltage dip.
  • On an infeed: short-circuit currents at switch-on because there is no commutating reactor.
  • The power cables are not correctly connected.
  • The power cables exceed the maximum permissible length.
  • The power unit is defective.

Two further causes apply only on a parallel switching device (r0108.15 = 1); the manuals print them for the modular converters, while the G120 and G120XA manuals confine themselves to the causes above:

  • A power unit has tripped (switched off) due to a ground fault.
  • The closed-loop circulating current control is either too slow or has been set too fast.

What to check

  1. Check the motor data and, if required, carry out commissioning again.
  2. Check the motor circuit configuration (star-delta).
  3. In U/f operation, increase the up ramp.
  4. In U/f operation, check the assignment of rated currents of motor and power unit.
  5. On an infeed: check the line supply quality, reduce the motor load and verify that the line reactor is correctly connected.
  6. Check the power cable connections.
  7. Check the power cables for short-circuit or ground fault.
  8. Check the length of the power cables.
  9. Replace the power unit.
  10. On a parallel switching device (r0108.15 = 1), additionally check the ground fault monitoring thresholds (p0287) and the setting of the closed-loop circulating current control (p7036, p7037).

Reading the message value

The drive stores the fault cause in r0949 as a binary value. Interpret the value bitwise to find the affected phase:

  • Bit 0: Phase U
  • Bit 1: Phase V
  • Bit 2: Phase W

Parameters the manual names

  • r0949 — read the fault value here and interpret it bitwise: bit 0 phase U, bit 1 phase V, bit 2 phase W.
  • r0108 — bit 15 shows whether the converter is a parallel switching device; only then do the additional ground-fault and circulating-current causes and checks apply.
  • p0287 — ground fault monitoring threshold; check this setting when a power unit in a parallel switching device has tripped due to a ground fault.
  • p7036 — proportional gain of the closed-loop circulating current control; check it on a parallel switching device whose control reacts too slowly or too quickly.
  • p7037 — integral time of the closed-loop circulating current control; check it together with p7036 on a parallel switching device.

Acknowledging and restarting

The power unit switches off immediately and the motor coasts down. Remove the cause first, then acknowledge the fault immediately — the drive will not start again until F30080 has been acknowledged.

What differs between the drive families

Straight from the manuals' own fields — F30080 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYPower electronics faulted (5)Power ModuleSINAMICS S120, S150 List Manual · p. 2967
G130, G150OFF2IMMEDIATELYPower electronics faulted (5)Power ModuleSINAMICS G130, G150 List Manual · p. 1672
G120OFF2IMMEDIATELYPower electronics faulted (5)SINAMICS G120 · p. 918
G120XAOFF2IMMEDIATELYSINAMICS G120XA PN converter · p. 1163

The drives this code lives on

F30080 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F30080 mean?

The Power Module has detected an excessive rate of rise in the overvoltage range — the current is increasing too quickly. The power unit switches the drive off and the motor coasts down.

How can I see which phase triggered F30080?

Read the fault value in r0949 and interpret it bitwise: bit 0 stands for phase U, bit 1 for phase V and bit 2 for phase W.

How do I clear and restart after F30080?

Remove the cause first — for example the motor data, the power cables or, on an infeed, the line reactor. Then acknowledge the fault immediately; the drive will not start until it has been acknowledged.

Why does F30080 occur on my infeed?

The manuals list high discharge and post-charging currents after a line or DC link voltage dip and short-circuit currents at switch-on without a commutating reactor. Check the line supply quality, reduce the motor load and verify the line reactor connection.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.