Fault · SINAMICS S120, S150

F06851Infeed: Distributed infeed line monitoring tripped

What it means

F06851 means that the line monitoring of the distributed line infeed has tripped. The distributed infeed watches the connected line supply with the monitoring function that is parameterized in p5540 ... p5559; when that function responds, the infeed raises this fault and the drive coasts down. The message value carries the alarm value, which corresponds to the line monitoring status word r5542, so it shows which line monitoring status led to the trip.

Why it appears

  • The line monitoring of the distributed line infeed — the function parameterized in p5540 ... p5559 — has tripped.

What to check

  1. Check the line supply of the distributed line infeed.
  2. Check the parameterization of the line monitoring in p5540 ... p5559: the configuration of the monitoring is set in p5540, and p5559 contains the line monitoring LFRT frequency values.

Reading the message value

  • The message value is the alarm value that the drive stores in r2124 — interpret it hexadecimal.
  • The alarm value corresponds to the status word r5542, the line monitoring status word.

Parameters the manual names

  • r2124 — alarm value of this fault; read it hexadecimal to decode the message value of F06851.
  • r5542 — line monitoring status word; the alarm value of F06851 corresponds to this status word.
  • p5540 — line monitoring configuration; here the line monitoring of the distributed infeed is set up, so it is the first place to look when the parameterization is in question.
  • p5559 — line monitoring LFRT frequency values; part of the p5540 ... p5559 range whose parameterization the remedy has you check.

Acknowledging and restarting

The fault switches the infeed off and the drive coasts down; the fault must be acknowledged before the drive will start again. The acknowledgement can be made immediately, for example with the acknowledge function of the operator panel or the commissioning tool; the message table additionally specifies POWER ON. Restart the drive only after the line supply and the line monitoring parameterization (p5540 ... p5559) have been checked and the fault has been acknowledged.

The same on every family

Every manual that describes F06851 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2 (NONE)IMMEDIATELY (POWER ON)Network fault (2)NoneSINAMICS S120, S150 List Manual · p. 2772

The drives this code lives on

F06851 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F06851 on my SINAMICS mean?

It means that the line monitoring of the distributed line infeed has tripped. The code is described for the S120 and S150 infeeds, and the drive coasts down until the fault is cleared.

How do I fix fault F06851?

Check the line supply first, then check the parameterization of the line monitoring in p5540 ... p5559. Once the cause is removed, acknowledge the fault and restart the drive.

What is the message value of F06851?

The drive stores the alarm value in r2124; interpreted hexadecimal, it corresponds to the line monitoring status word r5542.

Which parameters belong to fault F06851?

p5540 (line monitoring configuration) and p5559 (line monitoring LFRT frequency values) set the monitoring up; r2124 and r5542 hold the alarm value and the line monitoring status word.