Fault · SINAMICS G130, G150, S120, S150

F01688SI Motion CU: Actual value synchronization not permissible

What it means

F01688 is raised in the Control Unit (CU) when the SI Motion safety function "actual value synchronization" is enabled in a combination that is not permissible. The manual names three such combinations: enabling the function for a 1-encoder system, enabling it simultaneously with a monitoring function with absolute reference — SCA (Safe Cam) or SLP (Safely Limited Position) — and enabling it simultaneously with "Safe position via PROFIsafe". Both list manuals that describe this fault state the same causes and the same remedy, and both note that the fault results in a STOP A that cannot be acknowledged.

Why it appears

  • Actual value synchronization has been enabled although the drive is a 1-encoder system.
  • Actual value synchronization and a monitoring function with absolute reference — SCA (Safe Cam) or SLP (Safely Limited Position) — are enabled simultaneously.
  • Actual value synchronization and "Safe position via PROFIsafe" are enabled simultaneously.

What to check

  1. Establish which combination is parameterized: the SI Motion safety functions are enabled at the Control Unit via p9501, and the encoder of the second SI Motion channel is assigned via p9526.
  2. If actual value synchronization is enabled for a 1-encoder system: either parameterize a 2-encoder system or deselect the "actual value synchronization" function.
  3. If actual value synchronization is enabled together with a monitoring function with absolute reference (SCA/SLP): deselect either the "actual value synchronization" function or the monitoring functions with absolute reference, and then carry out a POWER ON.
  4. If actual value synchronization is enabled together with "Safe position via PROFIsafe": either deselect the "actual value synchronization" function or do not enable "Safe position via PROFIsafe".

Parameters the manual names

  • p9501 — SI Motion enable safety functions (Control Unit): the parameter with which the SI Motion safety functions are enabled at the Control Unit; this is where "actual value synchronization" or a conflicting monitoring function has to be deselected so the fault can be remedied.
  • p9526 — SI Motion encoder assignment second channel: the assignment of the encoder to the second SI Motion channel; the manual refers to it when the remedy is to parameterize a 2-encoder system instead.

Acknowledging and restarting

This fault results in a STOP A that cannot be acknowledged, so the message cannot simply be reset while the impermissible combination is still parameterized. First remove the combination — deselect "actual value synchronization" or the conflicting function, or parameterize a 2-encoder system — and then carry out a POWER ON, which is the acknowledgement the remedy prescribes for this fault.

What differs between the drive families

Straight from the manuals' own fields — F01688 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2668
G130, G150OFF2IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1457

The drives this code lives on

F01688 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01688 mean on a SINAMICS drive?

The SI Motion function "actual value synchronization" has been enabled in a combination that is not permissible: on a 1-encoder system, together with a monitoring function with absolute reference (SCA/SLP), or together with Safe position via PROFIsafe.

How do I clear fault F01688?

It cannot simply be acknowledged — the fault triggers a STOP A that cannot be acknowledged. Deselect "actual value synchronization" or the conflicting function (or parameterize a 2-encoder system) and then carry out a POWER ON.

Can actual value synchronization be used with only one encoder?

No. The manual states that enabling actual value synchronization for a 1-encoder system is not permissible; either deselect the function or parameterize a 2-encoder system, for which p9526 assigns the second encoder channel.

Which parameters belong to fault F01688?

p9501, with which the SI Motion safety functions are enabled at the Control Unit, and p9526, the SI Motion encoder assignment of the second channel.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals