Safety message · SINAMICS G120, G130, G150, S120, S150

C30712SI Motion P2: Defect in F-IO processing

What it means

C30712 is a safety message of the SI Motion P2 functions. When the drive cross-checks and compares its two monitoring channels, it has detected a difference between parameters or between the results of the F-IO processing and has therefore initiated STOP F. One of the monitoring functions no longer reliably functions, i.e. safe operation is no longer possible.

Together with this message the drive also displays safety message C30711 with message value 0 because STOP F was initiated. If at least one monitoring function is active, safety message C30701 SI Motion: STOP B initiated is output after the parameterized timer has expired.

Why it appears

  • Cross checking and comparing of the two monitoring channels revealed a difference between parameters or between the results of the F-IO processing.
  • As a result of this difference the drive initiated STOP F: one of the monitoring functions no longer reliably functions, so safe operation is no longer possible.

What to check

  1. Check the parameterization in the parameters involved and correct it if required.
  2. Ensure equality by copying the SI data to the second channel — the G120 manual phrases this as copying the SI data to processor 2 — and then carry out an acceptance test.
  3. Check the monitoring clock cycle for equality (p9500, p9300): the S120/S150 and G130/G150 manuals list this step for the clock cycles of the Control Unit (p9500) and the Motor Module (p9300); the G120 remedy ends with the copy and the acceptance test.

Reading the message value

  • The message value contains the number of the cross-compared data that resulted in this message.
  • Interpret the value as a decimal number: it is read in r9749 on S120, S150, G130 and G150, and in r2124 on G120.
  • The manual refers to safety message C01712 for the description of the message values; that description is not repeated with this code.

Parameters the manual names

  • r9749 (SI message value) — on S120, S150, G130 and G150 the drive enters the number of the cross-compared data that caused C30712 here; read it and interpret it decimal.
  • r2124 (alarm value) — on G120 the message value of this safety message is read here, interpreted as a decimal number.
  • p9500 (SI Motion monitoring clock cycle, Control Unit) — check this clock cycle as part of the equality check when clearing the message.
  • p9300 (SI Motion monitoring clock cycle, Motor Module) — the counterpart to p9500; check both clock cycles for equality.

Acknowledging and restarting

Once the cause has been corrected, the safety message is acknowledged and the drive can be restarted. The standard acknowledgment is a POWER ON; the manuals additionally describe a safe acknowledgment without a POWER ON via the onboard F-DI (only CU310-2), via PROFIsafe or via the machine control panel. For G120 the manual names acknowledgment via F-DI or PROFIsafe.

What differs between the drive families

Straight from the manuals' own fields — C30712 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONEIMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS S120, S150 List Manual · p. 3007
G130, G150NONEIMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS G130, G150 List Manual · p. 1698
G120IMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)SINAMICS G120 · p. 928

The drives this code lives on

C30712 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS safety message C30712 mean?

When cross-checking and comparing its two monitoring channels, the drive found a difference between parameters or results of the F-IO processing and initiated STOP F. One of the monitoring functions no longer reliably functions, so safe operation is no longer possible.

How do I fix fault C30712?

Check the parameterization of the parameters involved, copy the SI data to the second channel and then carry out an acceptance test. The S120, S150, G130 and G150 manuals additionally require checking the monitoring clock cycle for equality (p9500, p9300).

Can C30712 be acknowledged without a POWER ON?

Yes, the manuals describe safe acknowledgment without a POWER ON via the onboard F-DI (only CU310-2), via PROFIsafe or via the machine control panel. For G120 the manual names acknowledgment via F-DI or PROFIsafe.

Where is the message value of C30712 shown and what does it contain?

It is read in r9749 (or in r2124 on G120), interpreted as a decimal number, and contains the number of the cross-compared data that caused the message. The description of the individual message values is given with safety message C01712.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.