Alarm · SINAMICS G130, G150, S120, S150

A31999Encoder 1: Unknown alarm

What it means

A31999 tells the technician that the Sensor Module for encoder 1 has raised an alarm which the firmware in the Control Unit cannot interpret — the manuals call it an Unknown alarm. The manuals name the situation in which this happens: the firmware on the Sensor Module is more recent than the firmware on the Control Unit, so the Control Unit does not yet know this alarm. The number of the new alarm is output in the message value. Depending on how the drive is configured, the same condition can also be issued as a fault (F) or as a message with no automatic reaction (N).

Why it appears

  • An alarm has occurred on the Sensor Module for encoder 1 that the Control Unit firmware cannot interpret.
  • The firmware on the Sensor Module is more recent than the firmware on the Control Unit — the situation in which the manuals say this message can appear.

What to check

  1. Read the alarm value in r2124 as a decimal number: it contains the number of the new alarm that the Sensor Module has issued.
  2. If you need to know what this new alarm means, look it up in a more recent description of the Control Unit, as the note to this message recommends.
  3. Compare the firmware versions: r0148 shows the Sensor Module firmware version, r0018 shows the Control Unit firmware version.
  4. Apply one of the two remedies the manuals give: replace the firmware on the Sensor Module with an older firmware version, or upgrade the firmware on the Control Unit so that it can interpret the new alarm.

Reading the message value

  • The message value reads New message: %1 — the drive inserts the number of the new alarm raised on the Sensor Module for encoder 1.
  • The alarm value is stored in r2124 and is to be interpreted as a decimal number; its content is the alarm number itself.

Parameters the manual names

  • r2124 (Alarm value) — holds the alarm value of this message; read it as a decimal number to obtain the number of the unknown Sensor Module alarm.
  • r0148 (SM FW version) — shows the firmware version on the Sensor Module; the manual references it when an older Sensor Module firmware is to be loaded.
  • r0018 (CU FW version) — shows the firmware version of the Control Unit; the manual references it when the Control Unit firmware is to be upgraded.
  • p0491 (Motor encoder fault response ENCODER) — sets the drive's response to a motor encoder fault; the manual's note points to this parameter alongside this alarm.

Acknowledging and restarting

As an alarm, A31999 requires no acknowledgment. If the drive configuration issues the same condition as a fault instead, it is acknowledged immediately with POWER ON. An acknowledgment alone does not resolve the firmware difference between Sensor Module and Control Unit — the manuals' remedies are the firmware measures described in the checks above.

The same on every family

Every manual that describes A31999 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEActual position/speed value incorrect or not available (11)Sensor Module Encoder 1SINAMICS S120, S150 List Manual · p. 3081
G130, G150NONENONEActual position/speed value incorrect or not available (11)Sensor Module Encoder 1SINAMICS G130, G150 List Manual · p. 1763

The drives this code lives on

A31999 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A31999 mean on a SINAMICS drive?

The Sensor Module for encoder 1 has issued an alarm that the Control Unit firmware cannot interpret, which the manuals say happens when the Sensor Module firmware is more recent than the Control Unit firmware. The number of the new alarm appears in the message value and in r2124, interpreted as a decimal number.

How do I fix alarm A31999?

Read the alarm number in r2124, compare the firmware versions in r0148 (Sensor Module) and r0018 (Control Unit), then either load an older firmware version on the Sensor Module or upgrade the Control Unit firmware. An acknowledgment alone does not remove the firmware mismatch.

Does A31999 have to be acknowledged?

No — as an alarm it requires no acknowledgment. If the drive is configured to raise the same condition as a fault instead, it is acknowledged immediately with POWER ON.

Where can I find out what the unknown alarm behind A31999 means?

The note to this message recommends reading about the significance of the new alarm in a more recent description of the Control Unit. The alarm number itself is stored in r2124 as a decimal value.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A31xxx group · SINAMICS manuals · Siemens manuals