Alarm · SINAMICS G130, G150, S120, S150

A31920Encoder 1: Temperature sensor fault

What it means

A31920 reports that the evaluation of the temperature sensor connected to Encoder 1 has detected a fault: the measured sensor resistance lies outside the range that is plausible for the selected sensor type — either a wire breakage or a sensor that is not connected, or a resistance that is too low. The affected component is the Sensor Module Encoder 1; depending on the drive configuration, the same condition can also be issued as a fault or with no automatic reaction (N). The message value tells you which of the two causes the drive has detected and on which channel.

Why it appears

  • While evaluating the temperature sensor, the drive detected a fault (component: Sensor Module Encoder 1).
  • Fault cause 1 (01 hex): wire breakage or sensor not connected — the resistance is too high for the selected sensor type (KTY: R > 1630 Ohm, PT1000: R > 1720 Ohm).
  • Fault cause 2 (02 hex): measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm).

What to check

  1. Check that the encoder cable is the correct type and is correctly connected.
  2. Check the temperature sensor selection in p0600 to p0603 — the sensor type and signal source set there must match the sensor actually connected.
  3. If the cause persists, replace the Sensor Module (hardware defect or incorrect calibration data).

Reading the message value

  • Message value: fault cause (%1) and channel number (%2).
  • In r0949 (fault value) and r2124 (alarm value) the information is coded as 0000yyxx hex: yy = channel number, xx = error cause.
  • xx = 01 hex: wire breakage or sensor not connected; xx = 02 hex: measured resistance too low.
  • Additional values: only for internal Siemens troubleshooting.

Parameters the manual names

  • r0949 — fault value: read the coded cause of this message here (0000yyxx hex).
  • r2124 — alarm value: contains the same coded information while the message is present as an alarm.
  • p0491 — motor encoder fault response (ENCODER): the response parameter the manuals cross-reference for this message.
  • p0600 — motor temperature sensor for monitoring: check here which temperature sensor is selected for the monitoring.
  • p0603 — CI: motor temperature signal source: check the signal source from which the motor temperature is acquired.

Acknowledging and restarting

No acknowledgment is required for this alarm, and the drive takes no automatic reaction on it. Your task is to eliminate the cause at the sensor — the encoder cable, the selection in p0600 to p0603, or the Sensor Module itself. If the drive is configured to output the same condition as a fault, the manuals specify immediate acknowledgment.

The same on every family

Every manual that describes A31920 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Sensor Module Encoder 1SINAMICS S120, S150 List Manual · p. 3079
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Sensor Module Encoder 1SINAMICS G130, G150 List Manual · p. 1762

The drives this code lives on

A31920 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A31920 mean?

The temperature sensor evaluation on Sensor Module Encoder 1 has detected a fault: either a wire breakage or a sensor that is not connected, or a measured resistance that is too low for the selected sensor type (KTY, PTC or PT1000).

Which resistance values trigger A31920?

For a wire breakage or a missing sensor the resistance is too high (KTY: R > 1630 Ohm, PT1000: R > 1720 Ohm); for cause 2 it is too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm).

How do I fix alarm A31920?

Check that the encoder cable is the correct type and is correctly connected, verify the temperature sensor selection in p0600 to p0603, and if the cause persists, replace the Sensor Module (hardware defect or incorrect calibration data).

Does A31920 stop the drive, and must it be acknowledged?

No — the manuals list no reaction and no acknowledgment for the alarm. You can read the coded cause (0000yyxx hex: yy = channel number, xx = error cause) in r0949 or r2124.