What it means
Alarm A13031 tells you that one of the available periods of the Trial License function has expired. The Control Unit issues the alarm; the drive does not react to it automatically and no acknowledgement is needed. What the alarm asks for is a licensing decision: start another trial period, deactivate the functions that require a license, or license the drive unit properly. The neighbouring Trial License alarms — A13030, A13032 and A13033 — cover the other stages of the trial license and are described on their own pages.
Why it appears
- A period that was granted for the Trial License function has run out.
What to check
- Read the Trial License status in r9919 to see the licensing state the Control Unit is reporting.
- If required, start an additional period by setting p9918 = 1.
- Deactivate the functions that require a license.
- Alternatively, license the drive unit appropriately.
Parameters the manual names
- p9918 (Licensing active Trial License) — set to 1 here to start an additional Trial License period.
- r9919 (Licensing Trial License status) — read here which status the Trial License function currently reports.
Acknowledging and restarting
No acknowledgement step is required for this alarm; it is settled by one of the remedies above. The manual adds a caution: A license that is not adequate will only become evident after the next time the system runs up.
The same on every family
Every manual that describes A13031 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | Control Unit (CU) | SINAMICS S120, S150 List Manual · p. 2934 |
The drives this code lives on
A13031 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A13031 mean?
It reports that one of the available periods of the Trial License function has expired. The Control Unit raises the alarm, the drive takes no automatic action, and no acknowledgement is needed.
How do I clear alarm A13031?
Either start an additional trial period by setting p9918 = 1, deactivate the functions that require a license, or license the drive unit appropriately.
Which parameter shows the Trial License status?
r9919 (Licensing Trial License status). Read it to see the state the Trial License function is currently in.
Why can a licensing problem only show up later?
The manual notes that a license that is not adequate only becomes evident after the next time the system runs up, so check the licensing state again after the next run-up.