What it means
A03510 reports that at power-up the drive read its calibration data and found at least one calibration data point invalid. The manual describes the check in two variants: on drive objects that work with a Terminal Module, the Terminal Module 31 (TM31) calibration data is read in during ramp-up and checked for plausibility; on the vector drive objects and on the G120, it is the calibration data for the analog inputs that is read and checked with respect to plausibility during booting. Depending on the drive's configuration, the same condition can also be issued as a fault (F) or as a message with no reaction (N).
The manual's note on accuracy, quoted verbatim: In principle, operation could continue. The analog channel involved possibly does not achieve the specified accuracy.
Why it appears
- On drive objects that use a Terminal Module: the Terminal Module 31 (TM31) calibration data is read in during ramp-up and checked for plausibility, and at least one calibration data point was determined to be invalid.
- On the vector drive objects and on the G120: the calibration data for the analog inputs is read during booting and checked with respect to plausibility, and here too at least one calibration data point was determined to be invalid.
What to check
- Switch off and switch on the power supply for the Control Unit.
- Check the DRIVE-CLiQ wiring — the manual lists this step for the drives that work with Terminal Modules; for the G120 the remedy names only the power-supply step.
- If the message reoccurs, replace the module.
Reading the message value
The drive identifies the affected analog channel through the alarm value in r2124, which is interpreted binary. This decoding is printed for the entries describing the Terminal Module 31 (TM31) ramp-up check:
- Bit 1: 10 V value, analog input 0 invalid
- Bit 3: 10 V value, analog input 1 invalid
- Bit 4: Offset, analog output 0 invalid
- Bit 5: 10 V value, analog output 0 invalid
- Bit 6: Offset, analog output 1 invalid
- Bit 7: 10 V value, analog input 1 invalid
For the entries that describe the booting check of the analog inputs, the manual gives no bit decoding.
Parameters the manual names
- r2124 — alarm value: for this code, read it as a binary pattern to see which analog input or output had the invalid calibration data point (see the bit list above).
Acknowledging and restarting
As an alarm, the message requires no acknowledgment; when the drive is configured to raise the condition as a fault, it is acknowledged immediately by powering on (POWER ON). Restarting is the remedy itself: switch the power supply for the Control Unit off and on, and check the DRIVE-CLiQ wiring where the manual lists that step. If the message reoccurs, replace the module. Operation can continue in principle, but the analog channel involved may not achieve the specified accuracy.
What differs between the drive families
Straight from the manuals' own fields — A03510 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1516 |
| S120, S150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 2743 |
| S120, S150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 2744 |
| G130, G150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1517 |
| S120, S150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 2743 |
| S120, S150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 2744 |
| S120, S150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 2742 |
| G130, G150 | NONE | NONE | Hardware/software error (1) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1516 |
| G120 | NONE | NONE | Hardware/software error (1) | — | SINAMICS G120 · p. 867 |
The drives this code lives on
A03510 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A03510 on a SINAMICS drive mean?
The drive read its analog calibration data while starting and found at least one calibration data point invalid — on drives with a Terminal Module this is the Terminal Module 31 (TM31) data checked during ramp-up, on the vector drive objects and the G120 it is the analog input data checked during booting.
Can I keep operating with A03510 active?
Yes. The manual states that in principle operation could continue, but the analog channel involved possibly does not achieve the specified accuracy.
How do I clear A03510?
Switch the power supply for the Control Unit off and on and check the DRIVE-CLiQ wiring; if the message reoccurs, replace the module.
Which analog channel does A03510 refer to?
The alarm value in r2124, read as binary, names the channel — for example bit 1 means the 10 V value of analog input 0 is invalid and bit 4 means the offset of analog output 0 is invalid.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.