Alarm · SINAMICS G130, G150, S120, S150

A02020Function generator: Parameter cannot be changed

What it means

A02020 appears when a parameter setting belonging to the function generator is to be changed while the function generator is active. The function generator is controlled with p4800: as long as it reads 1, the drive refuses new values for the function generator parameters and signals this alarm instead. The alarm does not stop the drive — it only tells you that the change was not accepted until the function generator has been stopped. The manuals for the G130, G150, S120 and S150 describe it with the same wording, so one description covers all of them.

Why it appears

  • A function generator parameter was to be changed while the function generator is active (p4800 = 1). The drive only accepts changes to these settings when the function generator is stopped (p4800 = 0).

What to check

  1. Stop the function generator before parameterizing: set p4800 to 0.
  2. Make the required changes to the function generator parameters (p4810, p4812, p4813, p4815 and p4820 to p4829).
  3. If the function generator is still required, start it again: set p4800 to 1.

Parameters the manual names

  • p4800 — function generator control: set it to 0 to stop the function generator before you change any of the settings below, and back to 1 to start it again afterwards.
  • p4810 (operating mode), p4812 (physical address), p4813 (physical address reference value) and p4815 (drive number) — function generator settings that can only be written while the function generator is stopped.
  • p4820 (signal shape), p4821 (period duration), p4822 (pulse width), p4823 (bandwidth), p4824 (amplitude), p4825 (2nd amplitude), p4826 (offset), p4827 (ramp-up time to offset), p4828 (lower limit) and p4829 (upper limit) — the remaining function generator settings, likewise only changeable while it is stopped.

Acknowledging and restarting

The manual's note gives the reset sequence: The alarm is reset as follows: remove the cause of this alarm. - restart the function generator. In practice: stop the function generator with p4800 = 0, make the change that was refused, then start the function generator again with p4800 = 1 — once the cause is removed and the function generator is running again, the alarm clears.

The same on every family

Every manual that describes A02020 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2727
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1502

The drives this code lives on

A02020 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A02020 mean on a SINAMICS drive?

It means a function generator parameter was to be changed while the function generator is active (p4800 = 1). The drive refuses the change until the function generator is stopped.

How do I clear alarm A02020?

Set p4800 = 0 to stop the function generator, make the parameter change, and set p4800 = 1 again if the function generator is required. The alarm resets once its cause is removed and the function generator has been restarted.

Which parameters are affected by A02020?

The function generator settings p4810, p4812, p4813, p4815 and p4820 to p4829 — operating mode, physical address and its reference value, drive number, signal shape, period, pulse width, bandwidth, amplitudes, offset, ramp-up time and limits.

What is p4800 used for with this alarm?

p4800 is the function generator control: 0 stops the function generator so its parameters can be changed, and 1 starts it again afterwards.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A02xxx group · SINAMICS manuals · Siemens manuals