SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Alarm · SINAMICS G130, G150, S120, S150

A01944PB/PN: sign-of-life synchronism not reached

What it means

A01944 is the alarm "PB/PN: sign-of-life synchronism not reached" — PB stands for PROFIBUS and PN for PROFINET. It appears when the bus is in the data exchange state and clock-synchronous operation has been selected using the parameterizing telegram, but synchronization with the master sign-of-life (STW2.12 ... STW2.15) cannot be completed: the sign-of-life is changing differently from the way it was configured in the Tmapc time grid. The sign-of-life comes from the master, i.e. the higher-level control system, so this is a clock-synchronization problem between converter and master rather than a condition inside the converter. The manuals for the G130, G150, S120 and S150 families describe this alarm with the same cause and the same remedy.

Why it appears

  • The bus is in the data exchange state and clock-synchronous operation has been selected using the parameterizing telegram — this is the operating condition in which the drive expects to synchronize with the master sign-of-life.
  • Synchronization with the master sign-of-life (STW2.12 ... STW2.15) could not be completed because the sign-of-life is changing differently to how it was configured in the Tmapc time grid — the master is not stepping the sign-of-life in the pattern that was configured.

What to check

  1. Ensure that the master correctly increments the sign-of-life in the master application clock cycle Tmapc — if the master application does not step it as configured, correct it there.
  2. Correct the interconnection of the master sign-of-life at p2045, which selects the signal source for the PB/PN clock synchronous controller sign-of-life.

Parameters the manual names

  • p2045 — CI: PB/PN clock synchronous controller sign-of-life signal source / PB/PN ctr SoL s_s. This is the interconnection the remedy points to: check the signal source wired here and correct it so the master sign-of-life reaches the drive as configured.

Acknowledging and restarting

No acknowledgement is required for A01944, and the drive takes no automatic reaction when the alarm appears. The fix consists of the two remedy steps — correct incrementing of the sign-of-life in the master application clock cycle Tmapc and a correct interconnection of the master sign-of-life at p2045 — rather than of any resetting action on the converter.

The same on every family

Every manual that describes A01944 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONECommunication error to the higher-level control system (9)NoneSINAMICS S120, S150 List Manual · p. 2718
G130, G150NONENONECommunication error to the higher-level control system (9)NoneSINAMICS G130, G150 List Manual · p. 1494

The drives this code lives on

A01944 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A01944 mean?

It means PB/PN: sign-of-life synchronism not reached. In clock-synchronous PROFIBUS or PROFINET operation the drive could not synchronize with the master sign-of-life (STW2.12 ... STW2.15) because the sign-of-life changes differently than configured in the Tmapc time grid.

How do I clear A01944?

Make sure the master increments the sign-of-life correctly in the master application clock cycle Tmapc, and correct the interconnection of the master sign-of-life at p2045. No acknowledgement of the alarm itself is required.

Which SINAMICS drives are affected by A01944?

The alarm is described for the G130, G150, S120 and S150 families, and the manuals that print it give the same cause and the same remedy for all of them.

Which parameter is behind A01944?

p2045, the CI signal source for the PB/PN clock synchronous controller sign-of-life. The remedy for A01944 is to correct the master sign-of-life interconnection made through this parameter.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A01xxx group · SINAMICS manuals · Siemens manuals