Gas-actuated temperature switch
Description
These high-quality temperature switches have been developed especially for safety-critical applications. The high quality of the products and manufacturing in accordance with ISO 9001 ensure reliable monitoring of your plant. In production, the switches are traced by quality assurance software at every step and subsequently are 100 % tested.
In order to ensure as flexible operation as possible, the temperature switches are fitted with micro switches, which enable the switching of an electrical load of up to AC 250 V, 20 A directly.
For lower switching power ratings, such as for PLC applications, argon gas-filled micro switches with gold-plated contacts can be selected as an option.
Special features
- No power supply needed for switching of electrical loads
- Setting ranges from -30 ... +70 °C up to 0 ... 600 °C
- Robust switch enclosure from aluminium alloy, IP 66, NEMA 4X
- 1 or 2 independent set points, SPDT or DPDT, high switching power up to AC 250 V, 20 A
- Remote mounting with capillary ≤ 10 m
| Model | TAG |
| Subcategory | Gas-actuated temperature switch |
| Temperature ranges | −30…+70 °C · +0…+100 °C · +0…+160 °C · +0…+250 °C · +0…+400 °C · +0…+600 °C |
| Accuracy class | ≤ 0.5 % of span |
| Safety integrity level (SIL) | SIL 2 (option), per IEC 61508 |
| Process connection | ½ NPT male¾ NPT maleG ½ A maleG ¾ A male¾ NPT femaleM 20 x 1.5 femaleG ½ femaleG ¾ female½ NPT female |
| Process temperature | −40…+600 °C |
| Power supply | None (no power supply needed) |
| Electrical connection | ½ NPT female |
| Probe material | stainless steel |
| Ambient temperature | −40…+85 °C |
| IP rating | IP66 |
| Weight | 2.6 kg |
| Certifications | CERoHSREACHEACKOSHAINMETRO |
| Explosion protection | Ex d IIC T6/T4 GbEx tb IIIC T85/T135 DbATEX II 2 GDIECEx Ex d IIC T6/T4 GbIECEx Ex tb IIIC T85/T135 DbEACExKOSHAINMETRO |
| Sensor type | gas-actuated |
| Sensor class | SAMA class III B |
| Probe length | 163 mm |
| Probe diameter | 12 mm |
| Thermowell | No |
| Datasheet languages | EN |
| Contact version | Electrical rating (resistive load) | ||
|---|---|---|---|
| AC | DC | ||
| UN | 1 x SPDT, silver | 250 V, 15 A | 24 V, 2 A, 125 V, 0.5 A, 220 V, 0.25 A |
| US | 1 x SPDT, silver, hermetically sealed, argon gas filling 1) | 250 V, 15 A | 24 V, 2 A, 220 V, 0.5 A |
| UO | 1 x SPDT, gold-plated, hermetically sealed, argon gas filling 1) | 125 V, 1 A | 24 V, 0.5 A |
| UG | 1 x SPDT, gold-plated | 125 V, 1 A | 24 V, 0.5 A |
| UR | 1 x SPDT, silver, adjustable dead band | 250 V, 20 A | 24 V, 2 A, 220 V, 0.5 A |
| DN | 2 x SPDT or 1 x DPDT, silver | 250 V, 15 A | 24 V, 2 A, 125 V, 0.5 A, 220 V, 0.25 A |
| DS | 2 x SPDT or 1 x DPDT, silver, hermetically sealed, argon gas filling 1) | 250 V, 15 A | 24 V, 2 A, 220 V, 0.5 A |
| DO | 2 x SPDT, or 1 x DPDT gold-plated, hermetically sealed, argon gas filling 1) | 125 V, 1 A | 24 V, 0.5 A |
| DG | 2 x SPDT or 1 x DPDT, gold-plated | 125 V, 1 A | 24 V, 0.5 A |
| Setting range | Working range | Proof temperature | Fixed dead band | Adjustable dead band | |
|---|---|---|---|---|---|
| in °C | in °C | in °C | 1 contact UN, US, UO, UG in °C | 2 contacts DN, DS, DO, DG in °C | 1 contact UR in °C |
| -30 ... +70 | -40 ...+70 | 120 | ≤ 4.5 | ≤ 4.5 | 15 ... 35 |
| 0 ... 100 | -40 ...+100 | 120 | ≤ 4.5 | ≤ 4.5 | 15 ... 35 |
| 0 ... 160 | -40 ...+160 | 190 | ≤ 5 | ≤ 5 | 18 ... 35 |
| 0 ... 250 | -40 ...+250 | 300 | ≤ 6 | ≤ 6 | 21 ... 45 |
| 0 ... 400 | -40 ...+400 | 500 | ≤ 10 | ≤ 10 | 33 ... 77 |
| 0 ... 600 | -40 ...+600 | 600 | ≤ 17 | ≤ 17 | 50 ... 115 |
| Logo | Description | Country |
|---|---|---|
| EC declaration of conformity ■ Low voltage directive 2006/95/EC, EN 60730-1 ■ ATEX 1) directive 94/9/EC; annex III, IV II2GD | European Community | |
| IECEx 1) per IEC 60079-0, IEC 60079-1, IEC 60079-26, IEC 60079-31 Ex d IIC T6/T4 2) Gb Ex tb IIIC T85/T135 2) Db | IECEx member states | |
| EAC (option) Hazardous areas (option) | Eurasian Economic Community | |
| KOSHA (option) Hazardous areas | South Korea | |
| INMETRO (option) | Brazil |
| Logo | Description |
|---|---|
| SIL 2 rating (option) , per IEC 61508 Functional safety The electrical rating for DC applications is limited to 30V ...100 mA. |
Couldn't find the answer in the documentation? An engineer will reply within a business day.