Radio unit with LoRaWAN ® , 4 ... 20 mA input signal
Description
Wherever centralised, web-based remote monitoring of measuring instrument data is required, the IIoT-capable WIKA radio unit model NETRIS ® 2 finds it application.
The Ex radio unit receives the data via the two intrinsically safe, analogue 4 ... 20 mA input signals. The fully encapsulated instrument with IP55 ingress protection transmits the received data continuously to a cloud via configurable data packets with LoRaWAN ® (Long Range Wide Area Network).
Battery-operated wireless transmission via LoRaWAN ® is based on LPWAN technology to enable high transmission ranges and long battery life.
For further approvals, see page 5
WIKA radio unit, model NETRIS ® 2
The radio unit is connected to a suitable measuring instrument via cable.
The simple web configuration via the cloud and the LoRaWAN ® network enables the complete end-to-end encryption with bidirectional communication for safe IIoT applications.
The WIKA radio unit NETRIS ® 2 is part of the WIKA IIoT solution. With this, WIKA offers a holistic solution for your digitalisation strategy.
Special features
- IIoT-capable with LoRaWAN ® transmission
- Battery-operated LoRaWAN ® wireless transmission based on LPWAN technology
- High transmission range for the measured values (up to 10 km [6 mi]) with long battery life (up to 10 years)
- Two intrinsically safe analogue input signals with 4 ... 20 mA
- The determination of differential pressures is possible
| Security | Full end-to-end encryption → For details on security, see website: https://lora-alliance.org |
|---|
| Battery pack | WIKA Lithium thionyl chloride / Hybrid layer capacitor (HLC) battery, 3.6 V, potted Model Eve BN2D150 |
|---|---|
| Battery voltage | DC 3.6V |
| Battery life | Max. 10 years → At reference conditions a measurement and a transmission every hour (24 x a day) takes place at spreading factor 10. |
| Connection type | Board connector |
|---|---|
| Wire cross-section | 0.05mm 2 ...1.5mm 2 |
| Pin assignment | → See table 'Pin assignment' |
| Short-circuit resistance | Yes |
| Reverse polarity protection | Yes |
| Sealing inserts ∅ | ■ 4.5 ... 5 mm[1.77 ... 0.20 in] ■ 6 mm[0.24 in] ■ 7.2 mm[0.28 in] ■ 8.6 mm[0.34 in] ■ 10 mm[0.39 in] ■ 4.5 ... 5 mm[1.77 ... 0.20 in] (dual) |
| Ambient temperature range | -30 °C [-22 °F] ≤ Ta ≤ +60 °C [+140 °F] |
|---|---|
| Storage temperature range | -40 ...+70 °C [-40 ...+158 °F] |
| Humidity | 20 ... 90 %relative humidity |
| Condensation | Non-condensing |
| Vibration resistance per IEC 60068-2-6 | a = 1g (7 ... 18 Hz) 10 .... 14.53 Hz |
| A = 0.8 mm(18 ... 50 Hz) | |
| a = 5g (50 ... 200 Hz) ¹⁾ | |
| Shock resistance per IEC 60068-2-31 ¹⁾ | 25g, 6 ms |
| Free fall per IEC 60068-2-31 | |
| Individual packaging | 1.2 m[3.94 ft] |
| Multiple packaging | 0.5 m[1.6 ft] |
| Ingress protection per IEC/EN 60529 | IP55/57 |
View all (7)
| Logo | Description | Region | |
|---|---|---|---|
| EU declaration of conformity | European Union | ||
| EU declaration of conformity | European Union | ||
| - Ex i Zone 0 gas IECEx Hazardous areas - Ex i Zone 0 gas | II 1(1)G Ex ia [ia Ga] IIC T3 Ga Ex ia [ia Ga] IIC T3 Ga | International |
| Ex marking | |||||
|---|---|---|---|---|---|
| Parameters | |||||
| Max. voltage U o | ≤ 26V | ||||
| Max. current I o | ≤ 90mA | ||||
| Max. power P o | ≤ 550mW | ||||
| Internal capacitance C i | 3.6 nF | ||||
| Internal inductance L i | 0.3mH | ||||
| Output parameters 1) | |||||
| Gases of group IIB | Max. external inductance L 0 | 25.7mH | 19.7mH | 9.7mH | 4.7mH |
| Max. external capacitance C 0 | 446 nF | 486 nF | 566 nF | 686 nF | |
| Gases of group IIC | Max. external inductance L 0 | 2.2mH | 1.7mH | 0.7mH | 0.2mH |
| Max. external capacitance C 0 | 37 nF | 43 nF | 60 nF | 78 nF | |
| Temperature ranges | |||||
| Temperature class | T3 |
| Description | Order number | |
|---|---|---|
| Battery pack | WIKA Lithium thionyl chloride / Hybrid layer capacitor (HLC) battery, 3.6 V, potted Model Eve BN2D150 | 14635440 |
Couldn't find the answer in the documentation? An engineer will reply within a business day.