WIKA · SF6 gas solutions · Family GPU
SF 6 service equipment with safety system
For filling, cleaning and recovery of SF 6 gas
Range
0…50 bar abs
Protection
IP42
CERoHS
Price
On request
Depends on configuration
Special features
- Oil-less compressor and vacuum compressor
- Option for on-site gas filtration to the desired humidity
- Digital filling control to prevent gas cylinders from freezing
- Low maintenance effort
- SIL 2 certified safety control, sensors and load cell
Identification
| Product family | GPU |
| Subcategory | Handling equipment |
Measuring range
| Pressure ranges | 0…10 bar abs · 0…50 bar abs · 0…1.2 bar abs · 0…10 bar abs. · 0…50 bar abs. · 0…1.2 bar abs. |
Accuracy
| Safety integrity level (SIL) | SIL 2 |
Process conditions
| Process connection | DN 20DN 40 |
Operating environment
| Ambient temperature | +0…+40 °C |
| IP rating | IP42 |
| Weight | 800 kg |
Certifications and approvals
| Certifications | CERoHS |
Additional details
| Datasheet languages | EN |
Tables from datasheet
| Basic information | ||
|---|---|---|
| Models | ||
| GPU-B-2000 | SF₆ handling equipment in fully automated basic version | |
| GPU-S-2000 | SF₆ handling equipment with additional SIL 2 safety control | |
| GPU-B-3000 | SF₆ handling equipment at the highest performance level | |
| GPU-S-3000 | SF₆ handling equipment with additional SIL 2 safety control and the highest performance level | |
| Digital display | 10'-colour LCD touchscreen | |
| Connections | ||
| Gas-insulated switchgear (GIS) | 1 x valve DN 20 | Pressure range: 0 ... 10 bar abs. [0 ... 145 psi abs.] |
| Gas cylinder | 2 x valve DN 20 | Pressure range: 0 ... 50 bar abs. [0 ... 725 psi abs.] |
| Atmosphere | 1 x valve DN 20 | Pressure range: 0 ... 1.2 bar abs. [0 ... 17 psi abs.] |
| Operating voltage | ■ AC 400 V, 3-phase, 50/60 Hz ±10% ■ AC 240 V, 3-phase, 50/60 Hz ±10% ■ AC 208 V, 3-phase, 50/60 Hz ±10% | |
| Filter element | ■ Molecular sieve ■ Aluminium oxide ■ Particle filter: 1 μm ■ Max. water absorption: 75 g [2.65 oz] or 2 x 75 g [2.65 oz] | |
| Integrated tank, storage capacity | ■ Without tank ■ 300 litres ■ 600 litres ■ Stowage for 6 gas cylinders ■ Stowage for 10 gas cylinders | |
| Integrated gas cylinder scales | Without scales | - |
| Without scales with pull-out, fixed to the GPU | Measuring range 0 ... 120 kg [0 ... 264.56 lb] Accuracy: ±50 g [±1.76 oz] | |
| Mobile scales | Measuring range 0 ... 136 kg [0 ... 299.83 lb] Accuracy: ±68 g [±2.4 oz] | |
| Extension of function | ■ Humidity sensor to measure the humidity content and filtering to a target humidity value ■ Additional process connection for the simultaneous evacuation of air from gas compartments. | |
| Tyres | ■ Solid rubber,∅200mm [7.874 in], with rollover protection ■ Chassis with solig rubber wheels, 406 x 103 mm[15.98 x 4.05 in] | |
| Ingress protection | IP42 | |
| Weight | ||
| Without tank | Approx. 800 kg [1,764 lb] | |
| Without tank and wheels | Approx. 800 kg [1,764 lb] | |
| With empty 300-litre tank | Approx. 1,250 kg [2,756 lb] | |
| With empty 600-litre tank | Approx. 1,300 kg [2,867 lb] | |
| With empty stowage for 6 gas cylinders | Approx. 1,050 kg [2,315 lb] | |
| With empty stowage for 10 gas cylinders | Approx. 1,175 kg [2,591 lb] |
Operating conditions
| Operating temperature | 0 ... 40 °C [32 ... 104 °F] |
|---|---|
| Storage temperature range | -20 ...+60 °C [-4 ...+140 °F] |
| Humidity | < 95 %relative humidity |
| Condensation | Non-condensing |
Oil-less compressor (SF₆ gas)
| Output pressure | Gas flow rate |
|---|---|
| 50 bar abs. | ■ 6 m³/h at 50 Hz ■ 7.3 m³/h at 60 Hz |
| ■ 10.2 m³/h at 50 Hz ■ 12.3 m³/h at 60 Hz | |
| ■ 15 m³/h at 50 Hz ■ 18.5 m³/h at 60 Hz |
Oil-less vacuum compressor (SF₆ gas)
| Final vacuum | Gas flow rate |
|---|---|
| < 5 mbar abs. | ■ 4.8 m³/h at 50 Hz ■ 5.8 m³/h at 60 Hz |
| < 1 mbar abs. | 10 m³/h at 50/60 Hz |
| ■ 18 m³/h at 50 Hz ■ 21 m³/h at 60 Hz | |
| ■ 35 m³/h at 50 Hz ■ 43 m³/h at 60 Hz |
View all (7)
| Vacuum pump (air) | |
|---|---|
| Final vacuum | Gas flow rate |
| < 0.1 mbar abs. | ■ 40 m³/h at 50 Hz ■ 48 m³/h at 60 Hz |
| ■ 63 m³/h at 50 Hz ■ 76 m³/h at 60 Hz | |
| ■ 100 m³/h at 50 Hz ■ 120 m³/h at 60 Hz | |
| ■ 85 m³/h at 50 Hz dry-running vacuum pump ■ 110 m³/h at 60 Hz dry-running vacuum pump |
| Logo | Description | Country |
|---|---|---|
| EU declaration of conformity | European Union | |
| EMCDirective | ||
| Machinery Directive | ||
| RoHS directive |
| Description | Order number | |
|---|---|---|
| Hoses 1) | ||
| Nominal width DN 8 | 3 m[9.84 ft] | 14294449 |
| 5 m[16.40 ft] | 14330878 | |
| 10 m[32.81 ft] | 14335098 | |
| 15 m[49.20 ft] | 14307929 | |
| Nominal width DN 20 | 3 m[9.84 ft] | 14290070 |
| 5 m[16.40 ft] | 14307900 | |
| 10 m[32.81 ft] | 14327574 | |
| 15 m[49.20 ft] | 14307926 | |
| Adapter | ||
| DN 8 (male) to DN 20 (female), brass | 14096583 | |
| DN 8 (female) to DN 20 (male), brass | 14284870 | |
| Oil for vacuum pump, 1 litre | On request | |
| GPU-x-x000 filter set | 14418175 | |
| Service kit for compressor (SF₆ gas) | On request (serial number of the equipment is required) | |
| Service kit for vacuum compressor (SF₆ gas) | On request (serial number of the equipment is required) | |
| Service kit for vacuum pump (air) | On request (serial number of the equipment is required) | |
| GPU-x-x000 Tarpaulin | 14182499 (only for version with 300-litre tank) | |
| Trailer | On request |
Application areas not described yet
Describe your operating conditions — our engineer will suggest a model and use case.
Couldn't find the answer in the documentation? An engineer will reply within a business day.
Ask an engineer →All variants · Article table
1 standard articles of family GPU
If you know the code — pick directly. If not — use the configurator in mode “01”.
Stock:
SKUConfigurationPriceStockAction
Showing 1 of 1. Price on request — an engineer will quote your configuration.