GDM-100 1
GDM-100
On order
WIKA · SF6 gas solutions · Family GDM

Gas density monitor

With calibration valve for calibration
Range
1.6…25 bar
Output
Magnetic snap-action contact
Accuracy
±1 % at +20 °C
Protection
IP65
CERoHSEU declaration of conformityChina RoHS directive
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

The WIKA gas density measuring instruments provide reliable warnings against dangerously low gas levels, even under extreme ambient conditions. Electrical switch contacts warn the plant operator when the gas density drops below defined levels due to leakage.

Via the on-site indication, the pressure based on 20 °C [68 °F] can be read directly on the instrument.

With regard to switchgear safety, asset protection and environmental protection, it is common to perform functional checks on a regular basis. Article 5 of EU regulation no. 517/2014 on fluorinated greenhouse gases, provides for checking of the leakage detection system at least every 6 years if it contains > 22 kg [48.50 lb] SF₆ gas and the plant was commissioned after 01 January 2017.

Gas density monitor with calibration valve, model GDM-100

With the help of the firmly welded calibration valve, the gas density monitor can be shut off from the process and calibrated without having to disassemble it. This not only reduces maintenance time but also minimises the risks of SF₆ gas emissions and potential leakages during recommissioning.

When connecting a calibration system (e.g. model ACS-10 or model BCS-10) to the calibration valve, the gas density monitor is automatically disconnected from the gas compartment and a calibration can be performed. Following the calibration process, the calibration system can then be disconnected from the calibration valve and the connection to the gas compartment is reestablished automatically.

The calibration valve is also available as a retrofit solution for gas density monitors already installed in the field, as model GLTC-CV, and can be mounted between the gas compartment and gas density monitor.

Special features

  • Local indication with switch contacts
  • Temperature-compensated and hermetically sealed, therefore no influence of temperature fluctuations, height differences and atmospheric pressure fluctuations
  • Compensation possible for gas mixtures
  • Functional check or calibration possible without dismounting, in accordance with EU regulation no. 517/2014 on fluorinated greenhouse gases
  • Test connection is welded to prevent leakage
Identification
ModelGDM-100
Product familyGDM
SubcategoryWith calibration valve
Measuring range
Pressure ranges1.6…25 bar
Density reference temperature20 °C
Accuracy
Accuracy class±1 % at +20 °C, ±2.5 % at -20 ... +60 °C
Process conditions
Process connection
G ½ B per EN 837, lower mountG 1/2 B per EN 837, lower mount
Electrical characteristics
Output signalMagnetic snap-action contact
Switching contacts1
Materials
Wetted parts materialStainless steel
Operating environment
Ambient temperature−20…+60 °C
IP ratingIP65
Weight0.8 kg
Certifications and approvals
Certifications
CERoHSEU declaration of conformityChina RoHS directive
Additional details
Temperature compensationYes
Datasheet languagesEN
Tables from datasheet
Basic information
Nominal size100
Window■ Laminated safety glass ■ Acrylic glass
Case■ Stainless steel, with gas filling ■ Stainless steel, with fill fluid Leakage rate: ≤ 1 · 10 -5 mbar · l / s
Calibration pressure P ETo customer specification
Measuring element
MaterialStainless steel, welded
Leakage rate≤ 1 · 10 -8 mbar · l / s
Test methodHelium mass spectrometry
Movement■ Stainless steel ■ Bimetal link (temperature compensation)
RingBayonet bezel, stainless steel, secured by means of 3 welding spots
Accuracy specifications
Accuracy■ ±1 %at an ambient temperature of +20 °C [68 °F] ■ ±2.5 %at an ambient temperature of -20 …+60 °C [-4 ...+140 °F] and with calibration pressure in accordance with reference isochore (reference diagram KALI-Chemie AG, Hanover, prepared by Dr. Döring 1979)
Scale range
Scale rangeVacuum and overpressure range with measuring span of 1.6 ... 25 bar [23.20 ... 362.59 psi] (at an ambient temperature of 20 °C [68 °F] and gaseous phase)
Dial
Scale colourRed, yellow, green
MaterialAluminium
Pointer
Instrument pointerAluminium, black
Process connection
SizeG½BperEN837, lower mount
Material (wetted)Stainless steel, spanner flats 22 mm[0.86 in]
View all (10)
Operating conditions
Operating temperature■ -20 ...+60 °C [-4 ...+140 °F], gaseous phase ■ -40 ...+60 °C [-40 ...+140 °F]
Storage temperature range-50 ...+60 °C [-58 ...+140 °F]
Relative humidity, condensation≤ 90 %r.h. (non-condensing)
Ingress protectionIP65 per IEC/EN 60529
Weight in kg■ With gas filling: approx. 0.8 kg [1.76 lb] ■ With fill fluid: approx. 1.2 kg [2.64 lb]
Electrical connection
Connection typeCable socket with compression fitting M20 x 1.5
Wire cross-sectionWire cross-section max. 2.5 mm²
Switch contact■ 1 magnetic snap-action contact ■ 2 magnetic snap-action contacts ■ 3 magnetic snap-action contacts
Switching direction■ Falling pressure ■ Rising pressure
Switching function at nominal pressure■ Normally open ■ Normally closed ■ Change-over contact (max. 2 switch points)
Circuit■ Galvanically connected (not for change-over contact) ■ Galvanically isolated
Switching accuracy
Switch point = calibration pressure P ESee accuracy specifications
Switch point ≠ calibration pressure P EParallel to the reference isochore of the calibration pressure
Max. switching voltageAC 250V
Switching power■ With gas filling:30W/ 50 VA, max. 1 A ■ With fill fluid:20W/ 20 VA, max. 1 A
Material of switch contacts80 %Ag/ 20 %Ni, gold-plated
Further information on magnetic snap-action contacts in data sheet AC 08.01
High-voltage test 100%2 kV, 50 Hz, 1 s
LogoDescriptionCountry
EU declaration of conformityEuropean Union
LogoDescription
-China RoHS directive
ModelDescriptionOrder number
Calibration valve for retrofitting to gas density monitors and other leakage detection systems already installed in the field, model GLTC-CV Any arrangement of the test valve possible Other process connections on request → SeeWIKA data sheet SP 61.1614484687
Adapter from test connection (M26 x 1.5) to quick coupling14146937
Protective cap for test connection (M26 x 1.5)14193772
Calibration system for gas density instrumentation → SeeWIKA data sheet SP 60.0814424241
DescriptionOrder number
Adapter from test connection (M26 x 1,5) to RECTUS quick coupling14146937
Tool set to actuate the shut-off valve14232498
Wrench socket for shut-off valve (4KT 5,2 mm1/)14146708
Protection cap for test connection (M26 x 1,5)14193772
Protection cap for shut-off valve (silicone)14183253