AI helper
Describe the task — I'll match 3 WIKA models in 30 seconds
EGS80 1
EGS80
On order
WIKA · Force measurement · Family EGS

Digital limit switch

Digital limit switch for force transducers and load cells with galvanic isolation, 0/4...20 mA input, two relays, and scalable analogue output.
Output
0 ... 20 mA or 4 ... 20 mA
Protection
IP20
RoHSCEULCSAUL 508CSA 22.2 no. 143
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

The EGS80 limit switch is suitable for a multitude of measuring requirements. It is used universally, in combination with force transducers of all types or load cells, in force or weight monitoring in conveyor systems, cranes, hoists etc. This limit switch allows galvanic isolation between field circuits and control circuits and can also be used as a galvanic isolator.

Both 2- and 3-wire transmitters as well as active sources with signal 0/4 ... 20 mA can be connected. The input has line break and cable short-circuit monitoring. As outputs, there are 2 relays and one active current output 0/4 ... 20 mA available. The current output is freely scalable. The measured value display is a small LC display - 17 different display units, such as kg, t, N, bar etc. are selectable.

For further approvals see page 3

Digital limit switch, model EGS80

It is operated via the control panel on the front of the instrument or via the free PC software. The software enables easy and fast parameterisation. A file with the setting parameters can be created, saved and loaded into any model EGS80 limit switch. If several instruments must be parameterised identically, the time required is significantly reduced. An adapter cable for the PC connection with 'USB type A to audio plug' can be supplied as accessories.

Special features

  • Analogue input 0/4 ... 20 mA, 2- and 3-wire
  • Galvanic isolation, line break (LB) and short-circuit (SC) monitoring
  • Easy setting of extensive functions on the instrument or via PC software
  • Two potential-free relay contacts (change-over) with status LED and a freely-programmable analogue output (0 ... 20 mA)
Identification
ModelEGS80
Product familyEGS
SubcategoryDigital limit switch
Accuracy
Safety integrity level (SIL)SIL 2 per IEC 61508
Process conditions
Mounting typeDIN rail 35 mm
Electrical characteristics
Output signal0 ... 20 mA or 4 ... 20 mA
Operating environment
Ambient temperature−20…+60 °C
IP ratingIP20
Weight0.3 kg
Certifications and approvals
Certifications
RoHSCEULCSAUL 508CSA 22.2 no. 143
Additional details
Datasheet languagesEN
Tables from datasheet
Model EGS80
Input
Input signal0/4 ...20mA
Input resistance45 Ω(terminals 2, 3)
Open-circuit voltageDC 24V / 33mA
Available voltage> DC 15V for 20mA
Influence of the ambient temperature0.003 %/K (30 ppm)
Line fault monitoringLine break < 0.2 mA, short-circuit > 22mA
Accuracy< 30 µA
Rated temperature range-20 …+60 °C [-4 ... 140 °F]
Altitude< 2,000 mabove sea level
DisplayLC display, LEDs
Output I, II
Control systemRelay
Contact loadAC 250V / 2 A/cos φ≥0.7;DC 40V / 2 A
Mechanical lifetime5 x 10 7 switching cycles
Response delay≤ 200 ms with a step of 0 ...20mA
Output III
Analogue output0 ... 20 mAor 4 ...20mA
Open-circuit voltage≤ DC 24V
Load≤ 650Ω
Error signaldownscale ≤ 3.6 mA, upscale ≥ 21.5 mA(in accordance with NAMUR NE43)
Resolution≤ 10 μA
Accuracy< 20 μA
Influence of the ambient temperature0.005 %/K (50 ppm)
Response time< 650 ms with a step from 0 ... 20 mAat the input, 90 %of the output signal final value
LinearisationNumber of linearisation steps: max. 20
Galvanic isolation
Input/other circuits reinforced insulation in acc. with IEC/EN 61010-1Rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation in acc. with IEC/EN 61010-1Rated insulation voltage 300 Veff
Output I, II, III reinforced insulation between themselves in acc. with IEC/EN 61010-1Rated insulation voltage 300 Veff
Output III/supply reinforced insulation in acc. with IEC/EN 61010-1Rated insulation voltage 300 Veff
Interface/supply reinforced insulation in acc. with IEC/EN 61010-1Rated insulation voltage 300 Veff
Supply voltage■ DC20…90V ■ AC 48…253V
Dissipation loss2W/3VA
Power consumption2.2W/ 4VA
Settling timeEnergized/De-energized delay 0 ... 250 s, settable
Ingress protectionIP20
Electromagnetic compatibility■ EN 61326-1:2013 (industrial areas) ■ NE 21:2006
Low voltageEN 61010-1:2010
Safety integrity level (SIL)Up to SIL 2 per IEC 61508
MountingDIN rail 35 mm[1.378 in] per EN 60715:200
WeightApprox. 300 g [0.66 lbs]
LogoDescriptionCountry
EU declaration of conformity ■ EMCdirective ■ RoHS directiveEuropean Union
UL Per UL 508 and CSA 22.2 no. 143USA and Canada