WIKA · Pressure measurement · Family DI35
High-quality digital indicator for panel mounting
With multi-function input or with two inputs for standard signals
Output
4 ... 20 mA · 0 ... 20 mA
Accuracy
≤ ±0.01 ... 0.1 % of span ±1 digit
Protection
IP65/IP00
CEEACRoHSGOSTBelGIM
Price
On request
Depends on configuration
Description
The model DI35 digital indicator is a multi-function and very accurate instrument for a wide variety of measuring tasks. It is available in two different versions:
Special features
- Multi-function input (29 calibrated input configurations) or double input (0/4 ... 20 mA, DC 0 ... 10 V) with calculation function
- Accuracy ±0.01 ... 0.1 % of the span ±1 digit (depends on the input configuration)
- Transmitter power supply, MIN/MAX memory, HOLD/TARE/Totaliser function
- Linearisation with up to 30 programmable points
- Up to four freely programmable switch contacts (optionally)
Identification
| Model | DI35-M |
| Product family | DI35 |
| Subcategory | Digital indicator |
Accuracy
| Accuracy class | ≤ ±0.01 ... 0.1 % of span ±1 digit |
| Accuracy standard | EN 61326 |
Electrical characteristics
| Output signal | 4 ... 20 mA · 0 ... 20 mA · DC 0 ... 10 V · 0-10V · RS-232 · RS-485 |
| Power supply | AC 100 ... 240 V, 50/60 Hz, DC 100 ... 240 V or DC 10 ... 40 V, AC 18 ... 30 V, 50/60 Hz |
| Electrical connection | Removable plug-in terminal |
| Switching function | Freely programmable |
| Switching contacts | 4 |
Materials
| Case material | Glass-fibre reinforced polycarbonate, black, Glass-fibre reinforced polycarbonate |
Operating environment
| Ambient temperature | +0…+50 °C |
| IP rating | IP65/IP00 |
| Weight | 0.35 kg |
Certifications and approvals
| Certifications | CEEACRoHSGOSTBelGIM |
Additional details
| Datasheet languages | EN |
Tables from datasheet
Selectable versions
| Standard | AC 100 ... 240 V, 50/60 Hz, DC 100 ...240V |
|---|---|
| Option | DC 10 ... 40 V, AC 18 ... 30 V, 50/60 Hz |
Selectable versions
| Option 1 | RS-232 (not galvanically isolated) |
|---|---|
| Option 2 | RS-232 (galvanically isolated) |
| Option 3 | RS-485 (not galvanically isolated, only for point- to-point connection) |
| Option 4 | RS-485 (galvanically isolated, only for point-to- point connection) |
| Input signals | Measuring span | Measuring error in %of the measuring span 1) | Minimum measuring time | ||
|---|---|---|---|---|---|
| DI35-M | DI35-D | ||||
| 1-channel measurement | 2-channel measurement | ||||
| Current signals | 0 ...20mA | ≤ ±0.02 %±1digit | 0.02 s | 0.02 s | 0.04 s |
| 4 ...20mA | ≤ ±0.02 %±1digit | 0.02 s | 0.02 s | 0.04 s | |
| Voltage signals | DC 0 ...18mV | ≤ ±0.06 %±1digit | 0.02 s | - | - |
| DC 0 ...35mV | ≤ ±0.06 %±1digit | 0.02 s | - | - | |
| DC 0 ...75mV | ≤ ±0.04 %±1digit | 0.02 s | - | - | |
| DC 0 ...150mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC 0 ...300mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC 0 ...600mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC 0 ...1,250mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC 0 ...2,500mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC 0 ...5V | ≤ ±0.02 %±1digit | 0.02 s | - | - | |
| DC 0 ...10V | ≤ ±0.01 %±1digit | 0.02 s | 0.02 s | 0.04 s | |
| Thermocouples | |||||
| Type B, PtRh-PtRh | -100 ... +1,810 °C | ≤ ±0.10 %±1digit | 0.04 s | - | - |
| Type E, NiCr-CuNi | -260 ... +1,000 °C | ≤ ±0.06 %±1digit | 0.04 s | - | - |
| Type J, Fe-CuNi | -210 ... +1,200 °C | ≤ ±0.05 %±1digit | 0.04 s | - | - |
| Type K, NiCr-Ni | -250 ... +1,271 °C | ≤ ±0.05 %±1digit | 0.04 s | - | - |
| Type L, Fe-CuNi | -200 ...+900 °C | ≤ ±0.06 %±1digit | 0.04 s | - | - |
| Type N, NiCrSi-NiSI | -250 ... +1,300 °C | ≤ ±0.06 %±1digit | 0.04 s | - | - |
| Type R, PtRh-Pt | 0 ... 1,760 °C | ≤ ±0.07 %±1digit | 0.04 s | - | - |
| Type S, PtRh-Pt | 0 ... 1,760 °C | ≤ ±0.06 %±1digit | 0.04 s | - | - |
| Type T, Cu-CuNi | -240 ...+400 °C | ≤ ±0.07 %±1digit | 0.04 s | - | - |
| Resistance thermometer 2) | |||||
| Pt100 (2-/4-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.04 s | - | - |
| Pt100 (3-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.06 s | - | - |
| Pt200 (2-/4-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.04 s | - | - |
| Pt200 (3-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.06 s | - | - |
| Pt500 (2-/4-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.04 s | - | - |
| Pt500 (3-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.06 s | - | - |
| Pt1000 (2-/4-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.06 s | - | - |
| Pt1000 (3-wire) | -200 ...+850 °C | ≤ ±0.04 %±1digit | 0.04 s | - | - |
| Input signals | Measuring span | Measuring error in %of the measuring span 1) | Minimum measuring time | ||
|---|---|---|---|---|---|
| DI35-M | DI35-D | ||||
| 1-channel measurement | 2-channel measurement | ||||
| Current signals | 0 ...2mA | ≤ ±0.02 %±1digit | 0.02 s | - | - |
| 0 ...5mA | ≤ ±0.02 %±1digit | 0.02 s | - | - | |
| 0 ...20mA | ≤ ±0.02 %±1digit | 0.02 s | 0.02 s | 0.04 s | |
| 4 ...20mA | ≤ ±0.02 %±1digit | 0.02 s | 0.02 s | 0.04 s | |
| Voltage signals | DC -18 ...+18mV | ≤ ±0.06 %±1digit | 0.02 s | - | - |
| DC -35 ...+35mV | ≤ ±0.06 %±1digit | 0.02 s | - | - | |
| DC -75 ...+75mV | ≤ ±0.04 %±1digit | 0.02 s | - | - | |
| DC -150 ...+150mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC -300 ...+300mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC -500 ...+600mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC -500 ...+1,250mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC -500 ...+2,500mV | ≤ ±0.03 %±1digit | 0.02 s | - | - | |
| DC -1 ...+5V | ≤ ±0.02 %±1digit | 0.02 s | - | - | |
| DC -1 ...+10V | ≤ ±0.01 %±1digit | 0.02 s | 0.02 s | 0.04 s | |
| Resistance (2-, 3-, or 4-wire) | 0 ...100Ω | ≤ ±0.04 %±1digit | 0.04 s | - | - |
| 0 ... 1 kΩ | ≤ ±0.04 %±1digit | 0.04 s | - | - | |
| 0 ... 10 kΩ | ≤ ±0.04 %±1digit | 0.04 s | - | - |
View all (11)
| Terminal | Case labelling | Meaning | |
|---|---|---|---|
| 21 | S1 | Switch contact 1 1) | Normally closed |
| 22 | Normally open | ||
| 23 | COM | ||
| 24 | S2 | Switch contact 2 1) | Normally closed |
| 25 | Normally open | ||
| 26 | COM | ||
| 27 | S3 | Switch contact 3 1) | Normally closed |
| 28 | Normally open | ||
| 29 | COM | ||
| 30 | S4 | Switch contact 4 1) | Normally closed |
| 31 | Normally open | ||
| 32 | COM | ||
| 41 | GND | Serial interface RS232 1) | |
| Serial interface RS485 1) | |||
| 42 | TxD | Serial interface RS232 1) | |
| Data B(+) | Serial interface RS485 1) | ||
| 43 | RxD | Serial interface RS232 1) | |
| Data A(-) | Serial interface RS485 1) |
| Terminal | Case labelling | Meaning |
|---|---|---|
| 1 | Measuring input Resistance thermometer | |
| 2 | Measuring input Resistance thermometer | |
| 3 | Measuring input Resistance thermometer | |
| + | Voltage measuring signal ≤ 2.5V | |
| + | Thermocouple measuring signal | |
| 4 | Measuring input Resistance thermometer | |
| - | Voltage measuring signal ≤ 2.5V | |
| - | Thermocouple measuring signal | |
| 5 | + | Voltage measuring signal |
| 6 | + | Current measuring signal |
| 7 | - | Voltage measuring signal |
| - | Current measuring signal | |
| 8 | + | Analogue output 1) |
| 9 | - | |
| 10 | + | Transmitter power supply |
| 11 | - | |
| 12 | + | Digital input |
| 13 | L | Power supply |
| 14 | N |
Plug A (input 1)
| Terminal | Case labelling | Meaning |
|---|---|---|
| 1 | + | Current measuring signal Channel |
| 2 | NC | Not connected |
| 3 | - | Current measuring signal |
| 4 | NC | Not connected |
Plug B (input 2)
| Terminal | Case labelling | Meaning |
|---|---|---|
| 1 | + | Current measuring signal Channel |
| 2 | NC | Not connected |
| 3 | - | Current measuring signal |
| 4 | NC | Not connected |
Plug C (switching outputs)
| Terminal | Case labelling | Meaning |
|---|---|---|
| 1 | S1 | Normally closed |
| 2 | Normally open | |
| 3 | COM | |
| 4 | S2 | Normally closed |
| 5 | Normally open | |
| 6 | COM |
Plug D (digital output, analogue output, interface
| Terminal | Meaning | |
|---|---|---|
| 1 | Digital input, supply DC 24 V, ≤ 50mA | |
| 2 | Analogue output 0/4 ...20mA+ | |
| 3 | Digital input + | |
| 4 | Analogue output 0/4 ... 20 mAand DC 0 ...10V - | |
| 5 | Analogue output 0 ...10V + | |
| 6 | GND | Serial interface RS232 |
| Serial interface RS485 | ||
| 7 | TxD | Serial interface RS232 |
| Data B(+) | Serial interface RS485 | |
| 8 | RxD | Serial interface RS232 |
| Data A(-) | Serial interface RS485 |
| Logo | Description | Country |
|---|---|---|
| EU declaration of conformity ■ EMCdirective, EN 61326 emission (group 1, class B) and interference immunity (industrial application) ■ Low voltage directive ■ RoHS directive | European union | |
| EAC ■ Electromagnetic compatibility ■ Low voltage directive | Eurasian Economic Com - munity | |
| GOST Metrology, measurement technology | Russia | |
| BelGIM Metrology, measurement technology | Belarus |
Industry
Machinery
Machine building and plant construction · Test benches
Couldn't find the answer in the documentation? An engineer will reply within a business day.
Ask an engineer →All variants · Article table
1 standard articles of family DI35
If you know the code — pick directly. If not — use the configurator in mode “01”.
Stock:
SKUConfigurationPriceStockAction
Showing 1 of 1. Price on request — an engineer will quote your configuration.