AI helper
Describe the task — I'll match 3 WIKA models in 30 seconds
CS4R 1
CS4R
In stock at WIKA
WIKA · Temperature measurement · Family CS4R

Temperature controller for rail mounting

Compact digital temperature controller for DIN-rail mounting with multi-function input for Pt100, thermocouples, and standard signals, configurable control output, and optional heater burnout alarm and RS-485 interface.
Range
-200…2315 °C
Output
4-20mA · relay
Accuracy
±0.1 % ±1 digit (Pt100)
Protection
IP20
CEEAC
Price
From €217
Confirm at order time
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

The model CS4R is a compact digital temperature controller for the display, control and monitoring of temperature.

The controller features a multi-function input, meaning the configuration of the sensor input can be set. Thus the flexibility of the controller is considerably increased, and warehousing is made easier. An alarm output for monitoring the actual value is also available as standard.

The control parameters can be set across broad ranges. Auto-tuning, which facilitates finding the optimal control parameters, can be activated.

Temperature controller, model CS4R

The controllers are intended for DIN-rail mounting. The control output can be set either as relay (for slow control), as logic level for the control of electronic solid-state relays (for fast control and high current loads) or as a continuous 4 ... 20 mA output.

The versions with 4 ... 20 mA control output can be reconfigured by the user and operated as a transmitter with 4 ... 20 mA output signal.

A heater burnout alarm for the heater current monitoring and a serial interface RS-485 are available optionally.

Special features

  • Control mode configurable (PID, PI, PD, ON / OFF )
  • Integrated auto-tuning
  • Selectable control output - relay, logic or 4 ... 20 mA
  • Multi-function input for Pt100, thermocouples and standard industrial signals
  • Design with heater burnout alarm and serial interface
Identification
ModelCS4R
SubcategoryTemperature controller
Measuring range
Temperature ranges−200…+1370 °C · −200…+1000 °C · +0…+1760 °C · +0…+1820 °C · −200…+800 °C · −200…+400 °C · −200…+1300 °C · +0…+1390 °C · +0…+2315 °C · −200…+850 °C
Accuracy
Accuracy class±0.1 % ±1 digit (Pt100), ±0.2 % ±1 digit (thermocouples and voltage/current signals)
Electrical characteristics
Output signal4-20mA · relay · logic level · RS-485
Power supplyAC 100...240 V, 50/60 Hz or AC/DC 24 V
Electrical connectionTerminal connections
Operating environment
Ambient temperature+0…+50 °C
IP ratingIP20
Weight0.15 kg
Certifications and approvals
Certifications
CEEAC
Additional details
Sensor typePt100, JPt100, Type K, J, R, S, E, T, N, PL-II, C
Datasheet languagesEN
Tables from datasheet
Display
Actual value7-segment LED, 4-digit, red, character size 7.5 mm[0,3 in]
Set point7-segment LED, 4-digit, green, character size 7.5 mm[0,3 in]
Indication range-1999 ... 9999
Input
Number and type1 multi-function input for resistance thermometers, thermocouples and standard signals
Input configurationSelectable via terminal connections and menu-driven programming
Resistance thermometerPt100, JPt100, 3-wire, max. permissible resistance per connecting cable:10Ω
ThermocouplesTypes K, J, R, S, E, T, N, PL-II, C (W/Re5-26): max. permissible external resistance:100Ω Type B: max. permissible external resistance:40Ω
Standard signals0 ... 20 mA, 4 ... 20 mA: Input impedance 50 Ω{external measurement shunt} max. permissible input current:100mA 0 ... 1 V: Input impedance>1MΩ max. permissible input voltage:5V 0 ... 5 V, 1 ... 5 V, 0 ... 10 V: Input impedance > 100 kΩ max. permissible input voltage:15V
Measuring time250 ms
Control output
Number and type3 different versions are possible
Relay contactLoad:AC 250 V, 3 A (resistive load) AC 250 V, 1 A (inductive load, cos ϕ = 0.4)
Logic levelDC 0 ...12V max. 40 mA(short-circuit proof) For the control of an electronic switch relay (solid-state relay, SSR)
{Analogue current signal}4 ... 20 mA, max. load 550Ω The control output 4 ... 20 mAcan be reconfigured to a transmitter output 4 ...20mA
Control modePID, PI, PD, P, ON/OFF (configurable) To determine the control parameters for PID control, auto-tuning can be activated.
Proportional band0 ...110%
Integral time0 ... 1,000 s
Derivative time0 ... 300 s
Cycle time1 ... 120 s (not available with analogue current signal control output)
HysteresisOnly available with ON/OFF control mode Thermocouples and resistance thermometers: 0.1 ... 100.0 °C Standard signals: 1 ... 1,000 (with a scaling of the input with one decimal point, this is taken over by the hysteresis)
Alarm output
Alarm outputOpen-collector Load:DC 24 V, max. 0.1 A
Alarm output 1For the actual value and control loop monitoring Alarm type, switch behaviour, hysteresis and time delay can be set
{Heater burnout alarm} 1)For single-phase heating systems (not possible with analogue current signal control output), optionally configured up to max. 5 A, 10 A, 20 A or 50 A, the current transformer is included in the delivery
View all (9)
Performance data
{Serial interface}RS-485 The transmission rate can be set (2,400 bps, 4,800 bps, 9,600 bps or 19,200 bps).
Power supply■ AC 100 ... 240 V, 50/60 Hz (max. permissible 85 ... 264 V) or ■ AC/DC 24 V, 50/60 Hz (max. permissible 20 ... 28 V)
Power consumptionapprox.6VA
Ambient conditions
Ambient temperature0 ... 50 °C [32 °F ...+ 122 °F]
Storage temperature-20 ...+50 °C [-4 °F ...+ 122 °F]
Humidity35 ... 85 %r.h. (non-condensing)
Case
MaterialPolycarbonate
ColourLight grey
Weightapprox. 150 g [0,33 lbs]
MountingSnap-in mechanism for mounting on DIN rails
Input signalsMeasuring spanMeasuring error of the span in%
StandardExceptions
Current signals
0 ... 20 mA, 4 ...20mA-1999 ... 9999 1)±0.2 %±1digit-
Voltage signals
0 ... 1 V, 0 ... 5 V, 0 ...10V-1999 ... 9999 1)±0.2 %±1digit-
1 ...5V-1999 ... 9999 1)±0.2 %±1digit-
Thermocouples
Type K (NiCr-Ni)-200 ... +1,370 °C -199.9 ... +400.0 °C-320 ... +2,500 °F -199.9 ... +750.0 °F±0.2 %±1digit 2) ±2 K≤ 0 °C: ±0.4 %±1digit ≤ 0 °C: ±0.4 %±1digit
Type J (Fe-CuNi)-200 ... +1,000 °C-320 ... +1,800 °F±0.2 %±1digit 2)≤ 0 °C: ±0.4 %±1digit
Type R (PtRh-Pt)0 ... 1,760 °C0 ... 3,200 °F±0.2 %±1digit 2)≤ 200 °C: ±6 K
Type S (PtRh-Pt)0 ... 1,760 °C0 ... 3,200 °F±0.2 %±1digit 2)≤ 200 °C: ±6 K
Type B (PtRh-PtRh)0 ... 1,820 °C0 ... 3,300 °F±0.2 %±1digit 2)≤ 300 °C: without details
Type E (NiCr-CuNi)-200 ...+800 °C-320 ... +1,500 °F±0.2 %±1digit 2)≤ 0 °C: ±0.4 %±1digit
TypeT (Cu-CuNi)-199.9 ... +400.0 °C-199.9 ... +750.0 °F±2 K≤ 0 °C: ±0.4 %±1digit
Type N (NiCrSi-NiSi)-200 ... +1,300 °C-320 ... +2,300 °F±0.2 %±1digit 2)≤ 0 °C: ±0.4 %±1digit
Type PL-II0 ... 1,390 °C0 ... 2,500 °F±0.2 %±1digit 2)-
Type C (W/Re5-26)0 ... 2,315 °C0 ... 4,200 °F±0.2 %±1digit 2)-
Resistance thermometer
Pt100 (3-wire)-200 ...+850 °C -199.9 ... +850.0 °C-300 ... +1,500 °F -199.9 ... +999.9 °F±0.1 %±1digit 2) ±0.1 %±1digit 2)-
1) Adjustable decimal point 2) Referred to the measuring span in °C JPt100 (3-wire)-200 ...+500 °C -199.9 ... +500.0 °C-300 ...+900 °F -199.9 ... +900.0 °F±0.1 %±1digit 2) ±1 K-
Logo DescriptionCountry
EC declaration of conformityEuropean Community
EMCdirective EN 55011:2009+A1:2010 EN 61000-6-2:2005 EN 61000-6-4:2007 + A1:2011 EN 61326-1:2013 (group 1, class A) and interference immunity (industrial Low voltage directive