Differential pressure transmitter Eco
Description
The model A2G-55 Eco differential pressure transmitter is used for detecting small air flows in air-conditioning systems and for measuring low pressures in environmental, laboratory and clean room applications (air, non-aggressive gases).
It is based on the piezoresistive measuring principle. This compact differential pressure transmitter offers excellent performance and high quality at an attractive price.
The A2G-55 is available in a variety of unchangeable pressure ranges. Electrical analogue output signals for both measurement parameters (0 ... 10 V or 4 ... 20 mA) enable the direct connection to control systems or the building automation system. With its ingress protection of IP65, the measuring instrument is ideally suited for outdoor application.
for further approvals see page 4
Differential pressure transmitter Eco, model A2G-55
Special features
- Output signal 0 ... 10 V or 4 ... 20 mA
- Maintenance-free
- Simple operation
- High accuracy
| Model | A2G-55 |
| Product family | A2G |
| Subcategory | Differential pressure transmitter |
| Pressure ranges | 0…250 Pa · 0…500 Pa · 0…750 Pa · 0…1000 Pa · 0…1250 Pa · 0…2500 Pa · 0…3750 Pa · 0…5000 Pa |
| Accuracy class | ±2.5%FS |
| Process connection | For hoses with inner diameter 5.5mm |
| Process temperature | −10…+50 °C |
| Output signal | 0 ... 10 V · 4 ... 20 mA |
| Power supply | DC 13 ... 32 V (AC 13 ... 32 V optional) |
| Electrical connection | Cable gland M16, Screw terminals max. 1.5mm² |
| Case material | Plastic (ABS), ABS |
| Ambient temperature | −10…+50 °C |
| IP rating | IP65 |
| Weight | 0.07 kg |
| Certifications | CERoHSWEEEEACGOSTKazInMetrMTSCHSUkrSEPROUzstandard |
| Datasheet languages | EN, DE |
| Specifications | |
|---|---|
| Measuring element | Piezo measuring cell |
| Measuring range | ■ 0 ... 250 Pa ■ 0 ... 500 Pa ■ 0 ... 750 Pa ■ 0 ... 1,000 Pa ■ 0 ... 1,250 Pa ■ 0 ... 2,500 Pa ■ 0 ... 3,750 Pa ■ 0 ... 5,000 Pa |
| Accuracy | ±2.5%FS |
| Type of mounting | Vertical wall mounting |
| Process connection | For hoses with inner diameter 5.5mm |
| Electrical connection | Cable gland M16 Screw terminals max.1.5mm 2 |
| Output signal | 0 …10V(4 …20mAoptional) |
| Supply voltage | DC 13 ...32V (AC 13 ...32V optional) |
| Case | Plastic (ABS) |
| Permissible temperatures ■ Ambient temperature ■ Medium temperature | -10 ...+50 °C -10 ...+50 °C |
| Ingress protection | IP65 |
| Weight | 70 g |
| Description | Order number |
|---|---|
| Measuring hoses | |
| PVC hose, inner diameter 4 mm, roll at 25m | 40217841 |
| PVC hose, inner diameter | 40217850 |
| Silicone hose, inner diameter | 40208940 |
| Silicone hose, inner diameter | 40208958 |
| Duct connector for hose 4 and6mm | 40217507 |
| Logo | Description | Country |
|---|---|---|
| EC declaration of conformity ■ EMCdirective ■ RoHS conformity ■ WEEE directive | European Union | |
| EAC (option) Import certificate | Eurasian Economic Community | |
| GOST (option) Metrology, measurement technology | Russia | |
| KazInMetr (option) Metrology, measurement technology | Kazakhstan | |
| - | MTSCHS (option) Permission for commissioning | Kazakhstan |
| UkrSEPRO (option) Metrology, measurement technology | Ukraine | |
| Uzstandard (option) Metrology, measurement technology | Uzbekistan |
Couldn't find the answer in the documentation? An engineer will reply within a business day.