Differential pressure and air flow controller
Description
The model A2G-540 is used to control differential pressure and volume flow of air and also non-aggressive and non-flammable gases in ventilation and air-conditioning technology. The A2G-540 can be used as a P-, PI-, PD- and PID controller.
By selecting the respective component manufacturer in the menu, the correct air flow calculation formula is automatically taken into account. To further optimise the air flow measurement under extreme ambient conditions such as altitude and high medium temperature, suitable sensors can be directly integrated.
The piezoresistive measuring element is temperaturecompensated and particularly stable over the long term. It records even the smallest pressure differences and thus ensures high reliability and the highest measurement accuracy. The measured values are available as analogue
Differential pressure and air flow controller, model A2G-540
voltage and current signals, digitally via the RS-485 interface using Modbus ® RTU or via LoRaWAN ® (LPWAN). Integration into any control system or directly into cloud solutions is therefore easily possible.
The A2G-540 has freely adjustable measuring ranges. The instrument can be set using the WIKA app and NFC and, depending on the version, using buttons and a display. Efficient project documentation is possible using instrument parameter file readout via NFC and smartphone. The indication of up to four measured values and two relay states can be read from all viewing angles thanks to 2" TFT colour display with traffic light function and individualised measurement parameter lettering.
The construction of the A2G-540 is robust and weather-proof (IP65). The case can be opened without tools thanks to the snap-on cover.
Special features
- Decentralised PID controller – up to four input signals – reduces cabling effort and installation costs
- Integrated air flow calculation based on all common formulas
- Optimisation of air flow measurement through additional pressure and/or temperature compensation
- IIoT-ready and future-proof thanks to analogue and digital signal transmission (Modbus ® ) as well as wireless (LoRaWAN ® )
- Time-saving instrument configuration and display of current measured values on the smartphone via NFC or WIKA app
Build a A2G-540 for your task
The article number is assembled automatically. If unsure — ask an engineer; we'll match the line's parameters.
- kind of measurementdp- and flow-controller
- Unit—
- operating Range—
- measuring range—
- signal output0...10 V, 3-wire
- Digital displaywithout
- zero point settingwithout
- analog out 2without
- Relayohne
- input signalwithout
- Special cable connectionwithout
- Accessorieswithout
- Certificateswithout
- Approvalswithout
- Additional ordering informationWithout
Finish your configuration
Select every option to submit the request.
| Model | A2G-540 |
| Product family | A2G |
| Subcategory | Differential pressure and air flow controller |
| Ambient temperature | −40…+60 °C |
| IP rating | IP65 |
| Weight | 0.32 kg |
| Certifications | RoHSWEEECEEMCREDEN 10204 2.2EN 10204 3.1 |
| Datasheet languages | EN |
| Specifications | 1 x analogue output 3-wire (multi range) | Modbus ® RTU (multi range) |
|---|---|---|
| Display | O | O |
| Additional analogue output | O | O |
| Signal inputs | O | O |
| Relay | O | O |
| Modbus ® | O | O |
| Automatic zero point setting | O | O |
| Wireless signal (LoRaWAN ® ) | O | O |
| NFC | ||
| Configure | ü | ü |
| Read | ü | ü |
| Case dimensions | → See dimensions on page 6 |
|---|---|
| Process connection 1) | |
| 2 x connecting nozzle | Ø 5 mm[0.19 in] /Ø 7 mm[0.27 in] |
| For hoses | With inner diameter 4 ... 6 mm[0.15 ... 0.23 in] |
| Case 1) | PC GF20 |
| Cover with insert sheet 1) | PC, transparent; ABS, RAL 9010 |
| Mounting plate 1) | PC, RAL 7035 |
| Weight | 260 ... 320 g [0,57 ... 0,70 lb] (depending on version) |
| Operating range 2) | Operating range 2) | Operating range 2) | Operating range 2) 3) | ||||
|---|---|---|---|---|---|---|---|
| ±250 Pa | ±1 inWC | ±2,500 Pa | ±10 inWC | ±7,000 Pa | ±28 inWC | ±12.000 Pa | ±48 inWC |
| -25 …+25 | -0.1 ... +0.1 | -500 …+500 | -2 ...+2 | 0 …1,000 | 0 ... 4 | 0 …5.000 | 0 ... 20 |
| -50 …+50 | -0.2 ... +0.2 | -1,000 …+1,000 | -4 ...+4 | 0 …1,500 | 0 ... 6 | 0 …6.000 | 0 ... 24 |
| -100 …+100 | -0.4 ... +0.4 | 0 …250 | 0 ... 1 | 0 …2,000 | 0 ... 8 | 0 …7.000 | 0 ... 28 |
| -150 …+150 | -0.6 ... +0.6 | 0 …500 | 0 ... 2 | 0 …2,500 | 0 ... 10 | 0 …7.500 | 0 ... 30 |
| 0…25 | 0 ... 0.1 | 0 …1,000 | 0 ... 4 | 0 …3,000 | 0 ... 12 | 0 …8.000 | 0 ... 32 |
| 0…50 | 0 ... 0.2 | 0 …1,500 | 0 ... 6 | 0 …4,000 | 0 ... 16 | 0 …9.000 | 0 ... 36 |
| 0 …100 | 0 ... 0.4 | 0 …2,000 | 0 ... 8 | 0 …5,000 | 0 ... 20 | 0 …10.000 | 0 ... 40 |
| 0 …250 | 0 ... 1 | 0 …2,500 | 0 ... 10 | 0 …7,000 | 0 ... 28 | 0 …12.000 | 0 ... 48 |
| Pressure type | Differential pressure |
|---|---|
| Unit | |
| Differential pressure | ■ Pa ■ kPa ■ mbar ■ mmWC ■ inWC |
| Air flow | ■ l/s ■ m 3 /s ■ m 3 /h ■ cfm |
| Air velocity | ■ m/s ■ fpm |
| Air flow measuring range | 0 ...999,999m 3 /h |
| Operating pressure | ■ ±250 ... ±2.500 Pa [±1 ...±10 inWC]: 10 kPa [40 inWC] ■ ±7.000 ... ±12.000 Pa [±28 ...±48 inWC]: 100 kPa [400 inWC] |
| Measuring element | Piezo measuring cell |
| Digital display | |
| Display resolution | 240 x 320 dpi |
| Type of display | 2"TFT colour display |
| Dashboard function | Indication of up to four measured values and two relay states possible; automatic size scaling depending on the number of measured values displayed. Indicated values can be given any alphanumeric designation. |
| Colour configuration | Range of setting possibilities; colours definable via RGB code. |
| Alarm function | Definition of two limit values possible; on reaching these limit values, a colour change can be defined for each (e.g.'Warning' and 'Alarm') |
View all (8)
| Accuracy 1) | 0.50%FS 2) | |||
|---|---|---|---|---|
| Operating range | ±250 Pa [ ±1 inWC] | ± 2,500 Pa [ ± 10 inWC] | ± 7,000 Pa [ ± 28 inWC] | ± 12,000 Pa [ ± 48 inWC] |
| Temperature range | ||||
| Compensated 3) TC 4) offset (% FS/K) | 0.015% | 0.01% | 0.008% | 0.005% |
| Uncompensated 5) TC 4) offset (% FS/K) | 0.025% | 0.02% | 0.02% | 0.01% |
| Compensated 3) TC 4) span (% FS/K) | 0.02% | 0.02% | 0.01% | 0.01% |
| Uncompensated 5) TC 4) span (% FS/K) | 0.03% | 0.02% | 0.02% | 0.02% |
| Zero point setting | ■ Manually via push button on the PCB ■ 'myWIKA wireless device' app ■ Automatic 6) |
| Logo | Description | Region |
|---|---|---|
| EU declaration of conformity | European Union | |
| EMCdirective | ||
| RED - Radio Equipment Directive | ||
| RoHS directive | ||
| WEEE directive |
| Certificates | ■ Without ■ Measurement report per EN 837 ■ 2.2 test report per EN 10204 (e.g. state-of-the-art manufacturing, material proof, indication accuracy) ■ 3.1 inspection certificate per EN 10204 (e.g. material proof for wetted metal parts, indication accuracy, calibration certificate) |
|---|
| Model | Description | Order number |
|---|---|---|
| Measuring hoses | ||
| PVC hose, inner diameter 4 mm[0.16 in], roll at 25 m[82.02 ft] | 40217841 | |
| PVC hose, inner diameter 6 mm[0.24 in], roll at 25 m[82.02 ft] | 40217850 | |
| Silicone hose, inner diameter 4 mm[0.16 in], roll at 25 m[82.02 ft] | 40217906 | |
| Silicone hose, inner diameter 6 mm[0.24 in], roll at 25 m[82.02 ft] | 40217914 | |
| Duct connector for measuring hoses Ø4…6mm[0.16 …0.24 in] | 40217507 | |
| Multiple sealing inserts (for M20 cable gland) | ||
| Sealing insert with 2 bores at Ø4mm[0.16 in];PU 10 x | 40444284 | |
| Sealing insert with 2 bores at Ø6mm[0.24 in];PU 10 x | 40444285 | |
| Sealing insert with 4 bores at Ø5mm[0.20 in];PU 10 x | 40444286 | |
| Sealing plug for sealing insert with 4 bores, each with Ø5mm[0.20 in]; PU 50 x | 40454873 | |
| - | LoRaWAN ® gateway, preconfigured for WIKA network server Gateway for indoor use Gateway for outdoor use | On request |
Couldn't find the answer in the documentation? An engineer will reply within a business day.
Ask an engineer →304 standard articles of family A2G
If you know the code — pick directly. If not — use the configurator in mode “01”.