Differential pressure sensor
Description
The model A2G-50 differential pressure sensor is used for measuring differential pressures of gaseous media in ventilation and air-conditioning applications.
It is based on the piezoresistive measurement principle. This compact differential pressure sensor offers excellent performance and high quality at an attractive price.
Electrical analogue output signals for both measurands (0 … 10 V or 4 … 20 mA) or the digital Modbus ® versions enable the direct connection to control systems or the building automation system.
The pressure range as well as the unit and the response time can be individually adapted in the instrument via jumpers.
The measured differential pressure is also shown on the LC display and transmitted via the analogue or digital output signals. The LC display and the clear menu navigation enable a time-saving and simple commissioning.
for further approvals, see page 5
Differential pressure sensor, model A2G-50
Special features
- Electrical output signal 0 ... 10 V or 4 ... 20 mA
- Modbus ® output signal
- LC display
- Maintenance-free
- Maximum operating pressure 20 kPa
| Model | A2G-50 |
| Product family | A2G |
| Subcategory | Differential pressure sensor |
| Pressure ranges | -100…100 Pa · 0…1000 Pa · 0…1500 Pa · 0…2000 Pa · 0…2500 Pa · 0…7000 Pa · 0…250 Pa · 0…100 Pa · 0…500 Pa · 0…3000 Pa · 0…4000 Pa · 0…5000 Pa · 0…8000 Pa · 0…9000 Pa · 0…10000 Pa · 0…12000 Pa · -250…250 Pa · -500…500 Pa · -1000…1000 Pa · -25…25 Pa · -50…50 Pa · -250…2500 Pa · -250…7000 Pa · 0…7500 Pa · 0…50 Pa · 0…25 Pa |
| Accuracy class | 1 % ±2 Pa, 1 % ±1 Pa |
| Accuracy standard | EN 837 |
| Process connection | For hoses with inner diameter 4 ... 6 mmLower mount for hoses with inner diameter 4 ... 6 mm |
| Process temperature | −20…+50 °C |
| Output signal | 0 ... 10 V · 4 ... 20 mA · Modbus® |
| Power supply | DC 14 … 30 V or AC 24 V ±10 %, DC 9 … 30 V or AC 24 V ±10 %, DC 24 V ±10 % |
| Electrical connection | M16 cable gland, with strain relief Screw terminals max. 1.5 mm² |
| Case material | Plastic (ABS), ABS |
| Wetted parts material | ABS (connecting nozzle) |
| Ambient temperature | −40…+70 °C |
| IP rating | IP54 |
| Weight | 0.15 kg |
| Certifications | RoHSEMC DirectiveEU declaration of conformityRoHS directiveCE |
| Datasheet languages | EN, DE |
| Case | Plastic (ABS) |
|---|---|
| Ingress protection (IP code) per IEC 60529 | IP54 |
| Weight | 150 g [0.33 lb] |
| Measuring range | ||||
|---|---|---|---|---|
| Unit | 0 …2,500 Pa 0 …2,000 Pa 0 …1,500 Pa 0 …1,000 Pa 0 …500 Pa 0 …250 Pa 0 …100 Pa -100 …+100 Pa Pa kPa | 0 …7,000 Pa 0 …5,000 Pa 0 …4,000 Pa 0 …3,000 Pa 0 …2,500 Pa 0 …2,000 Pa 0 …1,500 Pa 0 …1,000 Pa | -250 …+250 Pa -100 …+100 Pa -50 …+50 Pa -25 …+25 Pa 0 …250 Pa 0 …100 Pa 0…50Pa 0…25Pa | 0 …12,000 Pa 0 …10,000 Pa 0 …9,000 Pa 0 …8,000 Pa 0 …7,500 Pa 0 …7,000 Pa -1,000 …+1,000 Pa -500 …+500 Pa |
| mbar inWC mmWC | Adjustable in the menu | |||
| Digital display | ||||
| Type of display | LC display (optionally) | |||
| Backlighting | Yes | |||
| Number of lines, digits | 2 lines (12 characters/line) Line 1: Active measurement Line 2: Units |
| Connection location | Lower mount For hoses with inner diameter 4 ... 6 mm[0.16 ... 0.24 in] |
|---|---|
| Material | ABS (connecting nozzle) |
| Signal type | DC 0 ... 10 V, 3-wire 4 ... 20 mA, 3-wire Modbus ® |
|---|
View all (11)
| Modbus ® | |
|---|---|
| Baud rate | 9600 19200 38400 |
| Adjustable in the configuration | |
| Protocol | Modbus ® via serial interface |
| Measuring range | -250 …+2,500 Pa -250 …+7,000 Pa |
| Transmission mode | RTU |
| Interface | RS-485 |
| Addresses | 1 …247 addresses selectable in the configuration menu |
| Byte format | (11 bits) in RTU mode Coding system: 8 bits binary |
| Bits per byte: 1 start bit 8 data bits, least significant bit is sent first 1 bit for parity 1 stop bit |
| Current consumption | ||
|---|---|---|
| DC 0 ...10V | < 1.0W | |
| 4 ...20mA | < 1.2W | |
| Modbus ® | < 1.3W | |
| Auxiliary power U B | ||
| With automatic zero point setting | AC 24V or DC 24V ±10% | |
| Without automatic zero point setting | Output signal 0 ...10V | DC 14 …30Vor AC 24V ±10% |
| Output signal4…20mA | DC 9 …30Vor AC 24V ±10% | |
| Load | ||
| Current output | Max. 500 Ω, min.20Ω | |
| Voltage output | 1 kΩ |
| Connection type | M16 cable gland, with strain relief Screw terminals max.1.5mm 2 Standard version with clamping area 4.5 ... 10 mm[0.18 ... 0.39 in] |
|---|
| Medium temperature range | -20 …+50 °C [-4 …+122 °F] 5 …+50 °C [23 …122 °F], with automatic zero point setting |
|---|---|
| Ambient temperature range | -40 …+70 °C [-40 …+158 °F] |
| Humidity | 5 ... 95 %relative humidity |
| Condensation | Non-condensing |
| Logo | Description | Region |
|---|---|---|
| EU declaration of conformity | European Union | |
| EMCDirective | ||
| RoHS directive |
| Logo | Description | Region |
|---|---|---|
| EAC EMCDirective | Eurasian Economic Community | |
| PAC Kazakhstan Metrology, measurement technology | Kazakhstan | |
| - | MChS Permission for commissioning | Kazakhstan |
| - | PAC Ukraine Metrology, measurement technology | Ukraine |
| Model | Description | Order number |
|---|---|---|
| Static duct probes with combi hose connection for pressure measuring hoses Ø 4 …7mm[0,16 ... 0,28 in] | ||
| Insertion length 100 mm[3.94 in] | 40232981 | |
| Insertion length 150 mm[5.91 in] | 40232999 | |
| Insertion length 200 mm[7.87 in] | 40233006 | |
| Measuring hoses | ||
| PVC hose, inner diameter 4 mm[0.16 in], roll of 25m [82.0 ft] | 40217841 | |
| PVC hose, inner diameter 6 mm[0.24 in], roll of 25m [82.0 ft] | 40217850 | |
| Silicone hose, inner diameter 4 mm[0.16 in], roll of 25m [82.0 ft] | 40217906 | |
| Silicone hose, inner diameter 6 mm[0.24 in], roll of 25m [82.0 ft] | 40217914 | |
| Duct connectors for measuring hoses Ø 4 …6mm[0,16 ... 0,24 in] | 40217507 |