AI helper
Describe the task — I'll match 3 WIKA models in 30 seconds
A2G-50 1
A2G-50
On order
WIKA · Pressure measurement · Family A2G

Differential pressure sensor

For ventilation and air-conditioning
Range
-1000…12000 Pa
Output
0 ... 10 V · 4 ... 20 mA
Accuracy
1 % ±2 Pa
Protection
IP54
RoHSEMC DirectiveEU declaration of conformityRoHS directiveCE
Price
On request
Depends on configuration
Request a quote
+38 (067) 285-77-70·info@avigan.com.uaViberTelegram

Description

The model A2G-50 differential pressure sensor is used for measuring differential pressures of gaseous media in ventilation and air-conditioning applications.

It is based on the piezoresistive measurement principle. This compact differential pressure sensor offers excellent performance and high quality at an attractive price.

Electrical analogue output signals for both measurands (0 … 10 V or 4 … 20 mA) or the digital Modbus ® versions enable the direct connection to control systems or the building automation system.

The pressure range as well as the unit and the response time can be individually adapted in the instrument via jumpers.

The measured differential pressure is also shown on the LC display and transmitted via the analogue or digital output signals. The LC display and the clear menu navigation enable a time-saving and simple commissioning.

for further approvals, see page 5

Differential pressure sensor, model A2G-50

Special features

  • Electrical output signal 0 ... 10 V or 4 ... 20 mA
  • Modbus ® output signal
  • LC display
  • Maintenance-free
  • Maximum operating pressure 20 kPa
Identification
ModelA2G-50
Product familyA2G
SubcategoryDifferential pressure sensor
Measuring range
Pressure ranges-100…100 Pa · 0…1000 Pa · 0…1500 Pa · 0…2000 Pa · 0…2500 Pa · 0…7000 Pa · 0…250 Pa · 0…100 Pa · 0…500 Pa · 0…3000 Pa · 0…4000 Pa · 0…5000 Pa · 0…8000 Pa · 0…9000 Pa · 0…10000 Pa · 0…12000 Pa · -250…250 Pa · -500…500 Pa · -1000…1000 Pa · -25…25 Pa · -50…50 Pa · -250…2500 Pa · -250…7000 Pa · 0…7500 Pa · 0…50 Pa · 0…25 Pa
Accuracy
Accuracy class1 % ±2 Pa, 1 % ±1 Pa
Accuracy standardEN 837
Process conditions
Process connection
For hoses with inner diameter 4 ... 6 mmLower mount for hoses with inner diameter 4 ... 6 mm
Process temperature−20…+50 °C
Electrical characteristics
Output signal0 ... 10 V · 4 ... 20 mA · Modbus®
Power supplyDC 14 … 30 V or AC 24 V ±10 %, DC 9 … 30 V or AC 24 V ±10 %, DC 24 V ±10 %
Electrical connectionM16 cable gland, with strain relief Screw terminals max. 1.5 mm²
Materials
Case materialPlastic (ABS), ABS
Wetted parts materialABS (connecting nozzle)
Operating environment
Ambient temperature−40…+70 °C
IP ratingIP54
Weight0.15 kg
Certifications and approvals
Certifications
RoHSEMC DirectiveEU declaration of conformityRoHS directiveCE
Additional details
Datasheet languagesEN, DE
Tables from datasheet
Basic information
CasePlastic (ABS)
Ingress protection (IP code) per IEC 60529IP54
Weight150 g [0.33 lb]
Measuring range
Unit0 …2,500 Pa 0 …2,000 Pa 0 …1,500 Pa 0 …1,000 Pa 0 …500 Pa 0 …250 Pa 0 …100 Pa -100 …+100 Pa Pa kPa0 …7,000 Pa 0 …5,000 Pa 0 …4,000 Pa 0 …3,000 Pa 0 …2,500 Pa 0 …2,000 Pa 0 …1,500 Pa 0 …1,000 Pa-250 …+250 Pa -100 …+100 Pa -50 …+50 Pa -25 …+25 Pa 0 …250 Pa 0 …100 Pa 0…50Pa 0…25Pa0 …12,000 Pa 0 …10,000 Pa 0 …9,000 Pa 0 …8,000 Pa 0 …7,500 Pa 0 …7,000 Pa -1,000 …+1,000 Pa -500 …+500 Pa
mbar inWC mmWCAdjustable in the menu
Digital display
Type of displayLC display (optionally)
BacklightingYes
Number of lines, digits2 lines (12 characters/line) Line 1: Active measurement Line 2: Units
Process connection
Connection locationLower mount For hoses with inner diameter 4 ... 6 mm[0.16 ... 0.24 in]
MaterialABS (connecting nozzle)
Output signal
Signal typeDC 0 ... 10 V, 3-wire 4 ... 20 mA, 3-wire Modbus ®
View all (11)
Communication
Modbus ®
Baud rate9600 19200 38400
Adjustable in the configuration
ProtocolModbus ® via serial interface
Measuring range-250 …+2,500 Pa -250 …+7,000 Pa
Transmission modeRTU
InterfaceRS-485
Addresses1 …247 addresses selectable in the configuration menu
Byte format(11 bits) in RTU mode Coding system: 8 bits binary
Bits per byte: 1 start bit 8 data bits, least significant bit is sent first 1 bit for parity 1 stop bit
Voltage supply and performance data
Current consumption
DC 0 ...10V< 1.0W
4 ...20mA< 1.2W
Modbus ®< 1.3W
Auxiliary power U B
With automatic zero point settingAC 24V or DC 24V ±10%
Without automatic zero point settingOutput signal 0 ...10VDC 14 …30Vor AC 24V ±10%
Output signal4…20mADC 9 …30Vor AC 24V ±10%
Load
Current outputMax. 500 Ω, min.20Ω
Voltage output1 kΩ
Electrical connection
Connection typeM16 cable gland, with strain relief Screw terminals max.1.5mm 2 Standard version with clamping area 4.5 ... 10 mm[0.18 ... 0.39 in]
Operating conditions
Medium temperature range-20 …+50 °C [-4 …+122 °F] 5 …+50 °C [23 …122 °F], with automatic zero point setting
Ambient temperature range-40 …+70 °C [-40 …+158 °F]
Humidity5 ... 95 %relative humidity
CondensationNon-condensing
LogoDescriptionRegion
EU declaration of conformityEuropean Union
EMCDirective
RoHS directive
LogoDescriptionRegion
EAC EMCDirectiveEurasian Economic Community
PAC Kazakhstan Metrology, measurement technologyKazakhstan
-MChS Permission for commissioningKazakhstan
-PAC Ukraine Metrology, measurement technologyUkraine
ModelDescriptionOrder number
Static duct probes with combi hose connection for pressure measuring hoses Ø 4 …7mm[0,16 ... 0,28 in]
Insertion length 100 mm[3.94 in]40232981
Insertion length 150 mm[5.91 in]40232999
Insertion length 200 mm[7.87 in]40233006
Measuring hoses
PVC hose, inner diameter 4 mm[0.16 in], roll of 25m [82.0 ft]40217841
PVC hose, inner diameter 6 mm[0.24 in], roll of 25m [82.0 ft]40217850
Silicone hose, inner diameter 4 mm[0.16 in], roll of 25m [82.0 ft]40217906
Silicone hose, inner diameter 6 mm[0.24 in], roll of 25m [82.0 ft]40217914
Duct connectors for measuring hoses Ø 4 …6mm[0,16 ... 0,24 in]40217507